Section 2VAC5-585-2270 - Backflow prevention device, carbonator
Universal Citation: 2 VA Admin Code 2VAC5-585-2270
Current through Register Vol. 41, No. 3, September 23, 2024
A. If not provided with an air gap as specified under 2VAC5-585-2200, a dual check valve with an intermediate vent preceded by a screen of not less than 100 mesh to one inch (100 mesh to 25.4mm) shall be installed upstream from a carbonating device and downstream from any copper in the water supply line.P
B. A dual check valve attached to the carbonator need not be of the vented type if an air gap or vented backflow prevention device has been otherwise provided as specified under subsection A of this section.
Statutory Authority: § 3.2-5121 of the Code of Virginia.
Disclaimer: These regulations may not be the most recent version. Virginia may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.