Utah Administrative Code
Topic - Public Safety
Title R710 - Fire Marshal
Rule R710-8 - Day Care Rules
Section R710-8-4 - Additions
Universal Citation: UT Admin Code R 710-8-4
Current through Bulletin 2024-06, March 15, 2024
(1) Places of religious worship shall not be required to meet the provisions of this rule in order to operate a nursery or day care while religious services are being held in the building.
(2) Family day care.
(a) Family day care units shall have on each
floor occupied by clients, two separate means of egress, arranged so that if
one is blocked the other will be available.
(b) Family day care units that are located in
the basement or on the second story shall be provided with two means of egress,
one of which shall discharge directly to the outside.
(i) Type 1 family day care units, located on
the ground level or in a basement, may use an emergency escape or rescue
openings as allowed in IFC, Chapter 10, Section 1030.
(c) Family day care units shall not be
located above the second story.
(d)
In family day care units, clients under the age of two shall not be located
above or below the first story.
(i) Clients
under the age of two may be housed above or below the first story where there
is at least one exit that leads directly to the outside and complies with IFC,
Section 1011 or Section 1012 or Section 1027.
(e) Family day care units located in split
entry/split level type homes in which stairs to the lower level and upper level
are equal or nearly equal, may have clients housed on both levels when approved
by the AHJ.
(f) Family day care
units shall have a portable fire extinguisher on each level occupied by
clients, which shall have a classification of not less than 2A:10BC, and shall
be serviced in accordance with NFPA, Standard 10, Standard for Portable Fire
Extinguishers.
(g) Family day care
units shall have single station smoke detectors in good operating condition on
each level occupied by clients. Battery operated smoke detectors shall be
permitted if the facility demonstrates testing, maintenance, and battery
replacement to insure continued operation of the smoke detectors.
(h) Rooms in family day care units that are
provided for clients to sleep or nap, shall have at least one opening or door
approved for emergency escape.
(i)
Fire drills shall be conducted in family day care units quarterly and shall
include the complete evacuation from the building of all clients and staff.
(i) At least annually, in type I family day
care units, the fire drill shall include the actual evacuation using the escape
or rescue opening, if one is used as a substitute for one of the required means
of egress.
(3) Day care centers.
(a) Day care centers shall
comply with either I-4 requirements or E requirements of the IBC, whichever is
applicable for the type of day care center.
(b) Emergency evacuation drills shall be
completed as required in IFC, Chapter 4, Section 405.
(4) Requirements for all day care.
(a) Heating equipment in spaces occupied by
children shall be provided with partitions, screens, or other means to protect
children from hot surfaces and open flames.
(b) A fire escape plan shall be completed and
posted in a conspicuous place.
(i) All staff
shall be trained on the fire escape plan and procedure.
(c) The AHJ shall insure at each inspection
there is sufficient adult staff to client ratios to allow safe and orderly
evacuation in case of fire.
(i) For day care
involving children, the AHJ may use the care giver to children ratios
established in rule by the Department of Health as an established
guideline.
Disclaimer: These regulations may not be the most recent version. Utah may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.