(1) Size and Color.
Tags shall be not more than five and one-half inches in height, nor less than four and one-half inches in height, and not more than three inches in width, nor less than two and one-half inches in width.
(2) Attaching Tag.
One service tag shall be attached to each portable fire extinguisher in such a position as to be conveniently inspected.
(3) Tag Information.
(4) Legibility.
(5) Format.
Subject to the use requirements of Section 6.4, the following format shall be used for all service tags:
EXAMPLE OF SERVICE TAG
Exception: Service tags may be printed or otherwise established for any number of years not in excess of five years.
ILLUSTRATION ON FILE IN STATE FIRE MARSHAL'S OFFICE
(6) New Tag.
A new service tag shall be attached to the extinguisher each time a service is performed.
(7) Tag Wording.
The following wording shall be placed at the top or reinforced ring end of every tag: "DO NOT REMOVE, BY ORDER OF THE STATE FIRE MARSHAL".
(8) Removal.
No person or persons shall remove a service tag, hydrostatic test tag or label, 6 year maintenance service tag or label, or verification of service collar, except when further service is performed. At that time the expired tag, label or collar shall be removed and a new tag, label or collar shall replace the expired one. No person or persons shall deface, modify, or alter any service tag, hydrostatic test tag or label, 6 year maintenance service tag or label, or verification of service collar that is required to be attached to any portable fire extinguisher.
(9) Restrictive Use.