Current through Bulletin 2024-18, September 15, 2024
11.0 General. Standards in this section apply
to wells greater than 30 feet. For shallow water well requirements, see Section
R655-4-17.
11.1 Approved Products,
Materials, and Procedures. 11.1.1 Any product, material or procedure designed
for use in the drilling, construction, cleaning, renovation, development pump
installation or repair, or abandonment of water production or non-production
wells, which has received certification and approval for its intended use by
the National Sanitation Foundation (NSF) under ANSI-NSF Standard 60 or 61, the
American Society for Testing Materials (ASTM), the American Water Works
Association (AWWA) or the American National Standards Institute (ANSI) may be
utilized. Other products, materials or procedures may also be utilized for
their intended purpose upon manufacturers certification that they meet or
exceed the standards or certifications referred to in this section and upon
state engineer approval.
11.1.2 Public supply
wells are also regulated by the Division of Drinking Water, and there are
additional construction requirements in Rule R309-515.
11.2 Well Casing - General
11.2.1 Drillers Responsibility. It shall be
the sole responsibility of the well driller to determine the suitability of any
type of well casing for the particular well being constructed, in accordance
with these minimum requirements.
11.2.2 Casing Stick-up. The well casing shall
extend a minimum of 18 inches above finished ground level and the natural
ground surface should slope away from the casing. A secure sanitary,
weatherproof mechanically secured cap, seal, or a completely welded cap shall
be placed on the top of the well casing to prevent contamination of the well.
If a vent is placed in the cap, it shall be properly screened to prevent access
to the well by debris, insects, or other animals.
11.2.3 Steel Casing. All steel casing
installed in Utah shall be in new or like-new condition, being free from pits
or breaks, clean with all potentially dangerous chemicals or coatings removed,
and shall meet the minimum specifications listed in Table 6 of this rule. To
utilize steel well casing, or steel blank casing and screen combinations, that
does not fall within the categories specified in Table 6, the driller shall
receive written approval from the state engineer. All steel casing installed in
Utah shall meet or exceed the minimum ASTM, ANSI, or AWWA standards for steel
pipe as described in Subsection R655-4-11 (11.1) unless otherwise approved by
the state engineer. Applicable standards may include and are incorporated by
reference into this rule:
AWWA A100-AWWA Standard for Water Wells, 2020 Edition.
ASTM A53/A53M-20 Standard Specifications for Pipe, Steel,
Black and Hot-Dipped, Zinc-Coated, Welded and Seamless, 2020 Edition.
ASTM A139/A139M-16 Standard Specification for Electric-Fusion
(Arc)-Welded Steel Pipe (NPS 4 and over), 2016 Edition.
AWWA C200-2017 Standard for Steel Water Pipe, 6 Inches and
Larger, 2017 Edition.
ASTM A589/A589M-06 (2018) Standard Specification for Seamless
and Welded Carbon Steel Water-Well Pipe, 2018 Edition.
ASTM A106/A106M-19a Standard Specification for Seamless
Carbon Steel Pipe for High Temperature Service, 2019 Edition
ASTM A778/A778M-16 (2021) Standard Specifications for Welded,
Unannealed Austenitic Stainless Steel Tubular Products, 2021 Edition.
ASTM A252/A252M-19 Standard Specification for Welded and
Seamless Steel Pipe Piles, 2019 Edition.
ASTM A312/A312M-21 Standard Specification for Seamless,
Welded, and Heavily Cold Worked Austenitic Stainless Steel Pipes, 2021
Edition.
ASTM A409/A409M-19 Standard Specification for Welded Large
Diameter Austenitic Steel Pipe for Corrosive or High Temperature Service, 2019
Edition.
ASTM A606/A606M-18 Standard Specification For Steel, Sheet
And Strip, High-Strength, Low-Alloy, Hot-Rolled And Cold-Rolled, With Improved
Atmospheric Corrosion Resistance, 2018 Edition.
TABLE 6
Minimum Wall Thickness for Steel Well Casing
|
Depth Nominal Casing Diameter
|
0 to 200 feet
|
200 to 300 feet
|
300 to 400 feet
|
400 to 600 feet
|
600 to 800 feet
|
800 to 1000 feet
|
1000 to 1500 feet
|
1500 to 2000 feet
|
5
|
250
|
250
|
250
|
250
|
250
|
250
|
250
|
250
|
6
|
250
|
250
|
250
|
250
|
250
|
250
|
250
|
250
|
8
|
250
|
250
|
250
|
250
|
250
|
250
|
250
|
250
|
10
|
250
|
250
|
250
|
250
|
250
|
250
|
312
|
312
|
12
|
250
|
250
|
250
|
250
|
250
|
250
|
312
|
312
|
14
|
250
|
250
|
250
|
250
|
312
|
312
|
312
|
312
|
16
|
250
|
250
|
312
|
312
|
312
|
312
|
375
|
375
|
18
|
250
|
312
|
312
|
312
|
375
|
375
|
375
|
438
|
20
|
250
|
312
|
312
|
312
|
375
|
375
|
375
|
438
|
22
|
312
|
312
|
312
|
375
|
375
|
375
|
375
|
438
|
24
|
312
|
312
|
375
|
375
|
375
|
438
|
|
|
30
|
312
|
375
|
375
|
438
|
438
|
500
|
|
|
Note: Minimum wall thickness is in inches.
For nominal casing diameters less than five inches,
the minimum wall thickness must be equivalent to ASTM Schedule 40.
For any other casing diameter not addressed
Subsection R655-4-11 (11.2), approval by the state engineer is required.
0.250 = 1/4, 0.312 = 5/16, 0.375 = 3/8, 0.438 =
7/16.
|
11.2.4 Plastic and Other Non-metallic Casing.
11.2.4.1 Materials. PVC well casing and
screen may be installed in Utah upon obtaining permission of the well owner.
Other types of non-metallic casing or screen must be approved by the state
engineer before installation. Plastic well casing and screen shall be
manufactured and installed to conform with the American National Standards
Institute (ANSI) or the American Society for Testing and Materials (ASTM)
Standard F480-14, 2022 Edition, which is incorporated by reference to this
rule. Casing and screen meeting this standard is normally marked "WELL CASING"
and with the ANSI-ASTM designation "F480, SDR-17 or similar standard dimension
ratio." All plastic casing and screen for use in potable water supplies shall
be manufactured to be acceptable to the American National Standards Institute's
National Sanitation Foundation (NSF) standard 61. Other types of plastic
casings and screens may be installed upon manufacturers certification that such
casing meets or exceeds the ASTM-SDR specification or ANSI-NSF approval and
upon state engineer approval.
11.2.4.2 Minimum Wall Thickness and Depth
Requirements. PVC well casing and screen for non-production wells with a
nominal diameter equal to or less than four inches shall meet the minimum wall
thickness required under ASTM Standard F480-95 SDR 21 or a Schedule 40
designation. PVC well casing and screen used for non-production well purposes
with a nominal diameter greater than four inches shall meet the minimum wall
thickness required under ASTM Standard F480-95 SDR 17 or a Schedule 80
designation. PVC well casing and screen used for water production well purposes
shall meet the minimum wall thickness required under ASTM Standard F480-95 SDR
17 or a Schedule 80 designation. Additionally, caution should be used when
other than factory slots or perforations are added to PVC well casing. The
installation of hand cut slots or perforations significantly reduces the
collapse strength tolerances of unaltered casings. The depth at which plastic
casing and screen is placed in a well shall conform to the minimum requirements
and restrictions as outlined in ASTM Standard F480-14, 2022 Edition and to PVC
casing manufacturer recommendations. Liner pipe does not need to meet these
wall thickness requirements if it is placed inside of a casing that does meet
these wall thickness requirements.
11.2.4.3 Fiberglass Casing. Fiberglass
reinforced plastic well casings and screens may be installed in wells upon
obtaining permission of the well owner. All fiberglass casing or screens
installed in wells for use in potable water supplies shall be manufactured to
be acceptable by ANSI-NSF Standard 61 and upon state engineer
approval.
11.2.4.4 Driving
Non-metallic Casing. Non-metallic casing shall not be driven, jacked, or
dropped and may only be installed in an oversized borehole.
11.2.4.5 Protective Casing. If plastic or
other non-metallic casing is utilized, the driller shall install a protective
steel casing which complies with Subsection R655-4-11 (11.2.3) or an equivalent
protective covering approved by the state engineer over and around the well
casing at ground surface to a depth of at least 2-1/2 feet. If a pitless
adapter is installed on the well, the bottom of the protective cover shall be
placed above the pitless adapter or well connection. If the pitless adapter is
placed in the protective casing, the protective casing shall extend below the
pitless entrance in the well casing and be sealed both on the outside of the
protective casing and between the protective casing and well casing. The
protective cover shall be sealed in the borehole in accordance with the
requirements of Subsection R655-4-11 (11.4). The annular space between the
protective cover and non-metallic casing shall also be sealed with acceptable
materials in accordance with Subsection R655-4-11 (11.4). A sanitary,
weather-tight seal or a completely welded cap shall be placed on top of the
protective cover, thus enclosing the well itself. If the sanitary seal is
vented, screens shall be placed in the vent to prevent debris insects, and
other animals from entering the well. This protective casing requirement does
not apply to monitor wells.
11.3 Casing Joints.
11.3.1 General. All well casing joints shall
be made water tight. In instances in which a reduction in casing diameter is
made, there shall be enough overlap of the casings to prevent misalignment and
to insure the making of an adequate seal in the annular space between casings
to prevent the movement of unstable sediment or formation material into the
well, in addition to preventing the degradation of the water supply by the
migration of inferior quality water through the annular space between the two
casings.
11.3.2 Steel Casing. All
steel casing shall be screw-coupled or welded. If the joints are welded, the
weld shall meet American Welding Society standards and be at least as thick as
the wall thickness of the casing and shall consist of at least two beads for
the full circumference of the joint and be fully penetrating. Spot welding of
joints is prohibited. State engineer approval must be obtained for other steel
casing joint types such as splined joints or dielectric couplings.
11.3.3 Plastic Casing. All plastic well
casing shall be mechanically screw-coupled, chemically welded, cam-locked or
lug coupled to provide water tight joints as per ANSI-ASTM F480-95. Metal
screws driven into casing joints shall not be long enough to penetrate the
inside surface of the casing. Metal screws should be used only when surrounding
air temperatures are below 50 degrees Fahrenheit (F) which retards the normal
setting of the cement. Solvent-welded joints shall not impart taste, odors,
toxic substances, or bacterial contamination to the water in the
well.
11.4 Surface Seals
and Interval Seals.
11.4.1 General. Before
the drill rig is removed from the drill site of a well, a surface seal shall be
installed. Well casings shall be sealed to prevent the possible downward
movement of contaminated surface waters in the annular space around the well
casing. The seal shall also prevent the upward movement of artesian waters
within the annular space around the well casing. Depending upon hydrogeologic
conditions around the well, interval seals may need to be installed to prevent
the movement of groundwater either upward or downward around the well from
zones that have been cased out of the well due to poor water quality or other
reasons. The following surface and interval seal requirements apply equally to
rotary drilled, cable tool drilled, bored, jetted, augered, and driven wells
unless otherwise specified.
11.4.2
Seal Material.
11.4.2.1 General. The seal
material shall consist of neat cement grout, sand cement grout, unhydrated
bentonite, or bentonite grout as defined in Section
R655-4-2. Use of
sealing materials other than those listed in Section R655-4-11 must be approved
by the state engineer. Bentonite drilling fluid, also known as drilling mud,
dry drilling bentonite, or drill cuttings are not an acceptable sealing
material. In no case shall drilling mud, drill cuttings, drill chips, or
puddling clay be used, or allowed to fill, partially fill, or fall into the
required sealing interval of a well during construction of the well. The
annular space to be grouted must be protected from collapse and the
introduction of materials other than grout. All hydrated sealing materials,
such as neat cement grout, sand cement grout, and bentonite grout, shall be
placed by tremie pipe, pumping, or pressure from the bottom of the seal
interval upwards in one continuous operation when placed below a depth of 30
feet or when placed below static groundwater level. Neat cement and sand cement
grouts must be allowed to cure a minimum of 24 hours before well drilling,
construction, or testing may be resumed. Allowable setting times may be reduced
or lengthened by use of accelerators or retardants specifically designed to
change setting time, at the approval of the state engineer. The volume of
annular space in the seal interval shall be calculated by the driller to
determine the estimated volume of seal material required to seal the annular
space. The driller shall place at least the volume of material equal to the
volume of annular space, thus ensuring that a continuous seal is placed. The
driller shall maintain the well casing centered in the borehole during seal
placement using centralizers or other means to ensure that the seal is placed
radially and vertically continuous. Neat cement and sand cement grout shall not
be used for surface or interval seals with PVC and other approved non-metallic
casing unless specific state engineer approval is obtained.
11.4.2.2 Bentonite Grout. Bentonite used to
prepare grout for sealing shall have the ability to gel; not separate into
water and solid materials after it gels; have a hydraulic conductivity or
permeability value of 10E-7 centimeters per second or less; contain at least
20% solids by weight of bentonite, and have a fluid weight of 9.5 pounds per
gallon or greater and be specifically designed for sealing. In addition, if a
bentonite grout is to be placed in the vadose zone, also known as the
unsaturated interval, then clean rounded fine sand shall be added to the
bentonite grout to increase the overall solids content and stabilize the grout
from dehydrating and cracking in that interval. For 20% solids bentonite grout,
at least 100 pounds of clean rounded fine sand shall be added per 50 pounds of
bentonite. For 30% solids bentonite grout, at least 50 pounds of clean fine
sand shall be added per 50 pounds of bentonite. Bentonite grout shall not be
used for sealing intervals of fractured rock or sealing intervals of highly
unstable material that could collapse or displace the sealing material, unless
otherwise approved by the state engineer. Bentonite grout shall not be used as
a sealing material where rapidly flowing groundwater might erode it. Bentonite
or polymer drilling fluid, also known as drilling mud, does not meet the
definition of a grout with respect to density, gel strength, and solids content
and shall not be used for sealing purposes. At no time shall bentonite grout
contain materials that are toxic, polluting, develop odor or color changes, or
serve as a micro-bacterial nutrient. All bentonite grout shall be prepared and
installed according to the manufacturer's instructions and this rule. All
additives must be certified by a recognized certification authority such as NSF
and approved by the state engineer. All bentonite used in any well shall be
certified by NSF-ANSI approved standards for use in potable water supply wells,
or equivalent standards as approved by the state engineer.
11.4.2.3 Unhydrated Bentonite. Unhydrated
bentonite, such as granular, tabular, pelletized, or chip bentonite, may be
used in the construction of well seals above a depth of 50 feet. Unhydrated
bentonite can be placed below a depth of 50 feet when placed inside the annulus
of two casings, when placed using a tremie pipe, or by using a placement method
approved by the state engineer. The bentonite material shall be specifically
designed for well sealing and be within industry tolerances. All unhydrated
bentonite used for sealing must be free of organic polymers and other
contamination. Placement of bentonite shall conform to the manufacturer's
specifications and instructions and result in a seal free of voids or bridges.
Granular or powdered bentonite shall not be placed under water by gravity
feeding from the surface. When placing unhydrated bentonite, a sounding or
tamping tool shall be run in the sealing interval during pouring to measure
fill-up rate, verify a continuous seal placement, and to break up possible
bridges or cake formation.
11.4.3 Seal and Unperforated Casing
Placement.
11.4.3.1 General Seal
Requirements. The surface seal must be placed in an annular space that has a
minimum diameter of four inches larger than the nominal size of the permanent
well casing. This amounts to a 2-inch annulus. The surface seal must extend
from land surface to a minimum depth of 30 feet. The completed surface seal
must fully surround the permanent well casing, must be evenly distributed, free
of voids, and extend to undisturbed or recompacted soil. In unconsolidated
formations such as gravels, sands, or other unstable conditions when the use of
drilling fluid or other means of keeping the borehole open are not employed,
either a temporary surface casing with a minimum depth of 30 feet and a minimum
nominal diameter of four inches greater than the outermost permanent casing
shall be utilized to ensure proper seal placement or the well driller shall
notify the state engineer's office that the seal will be placed in a
potentially unstable open borehole without a temporary surface casing by
telephone or fax in conjunction with the Start Card submittal to provide an
opportunity for the state engineer's office to inspect the placement of the
seal. If a temporary surface casing is utilized, the surface casing shall be
removed in conjunction with the placement of the seal. Alternatively, conductor
casing may be sealed permanently in place to a depth of 30 feet with a minimum
2-inch annular seal between the surface casing and borehole wall. If the
temporary surface casing is to be removed, the surface casing shall be
withdrawn as sealing material is placed between the outermost permanent well
casing and borehole wall. The sealing material shall be kept at a sufficient
height above the bottom of the temporary surface casing as it is withdrawn to
prevent caving of the borehole wall. If the temporary conductor casing is
driven in place without a 2-inch annular seal between the surface casing and
borehole wall, the surface casing shall be removed. Specific state engineer
approval must be obtained on a case by case basis for any variation of these
requirements. Surface seals and unperforated casing shall be installed in wells
located in unconsolidated formation such as sand and gravel with minor clay or
confining units; unconsolidated formation consisting of stratified layers of
materials such as sand, gravel, and clay or other confining units; and
consolidated formations according to the following procedures.
11.4.3.2 Unconsolidated Formation without
Significant Confining Units. This includes wells that penetrate an aquifer
overlain by unconsolidated formations such as sand and gravel without
significant clay beds of at least six feet in thickness or other confining
formations. The surface seal must be placed in a 2-inch annular space to a
minimum depth of 30 feet. Permanent unperforated casing shall extend at least
to a depth of 30 feet and also extend below the lowest anticipated pumping
level. Additional casing placed in the open borehole below the required depths
noted in Section R655-4-11 shall meet the casing requirements of Subsection
R655-4-9 (9.2) unless the casing is installed as a liner inside a larger diameter
approved casing.
11.4.3.3
Unconsolidated Formation with Significant Confining Units. This includes wells
that penetrate an aquifer overlain by clay or other confining formations that
are at least six feet thick. The surface seal must be placed in a 2-inch
annular space to a minimum depth of 30 feet and at least five feet into the
confining unit above the water bearing formation. Unperforated casing shall
extend from ground surface to at least 30 feet and to the bottom of the
confining unit overlying the water bearing formation. If necessary to complete
the well, a smaller diameter casing, liner, or well screen may be installed
below the unperforated casing. The annular space between the two casings shall
be sealed with grout, bentonite, or a mechanical packer. Additional casing
placed in the open borehole below the required depths noted in Section
R655-4-11 shall meet the casing requirements of Subsection R655-4-11 (11.2)
unless the casing is installed as a liner inside a larger diameter approved
casing.
11.4.3.4 Consolidated
Formation. This includes drilled wells that penetrate an aquifer, either within
or overlain by a consolidated formation. The surface seal must be placed in a
2-inch annular space to a minimum depth of 30 feet and at least five feet into
competent consolidated formation. Unperforated permanent casing shall be
installed to extend to a depth of at least 30 feet and the lower part of the
casing shall be driven and sealed at least five feet into the consolidated
formation. If necessary to complete the well, a smaller diameter casing, liner,
or well screen may be installed below the unperforated casing. The annular
space between the two casings shall be sealed with grout, bentonite, or a
mechanical packer. Additional casing placed in the open borehole below the
required depths noted in Section R655-4-11 shall meet the casing requirements
of Subsection R655-4-11 (11.2) unless the casing is installed as a liner inside
a larger diameter approved casing.
11.4.3.5 Sealing Artesian Wells. Unperforated
well casing shall extend into the confining stratum overlying the artesian
zone, and shall be adequately sealed into the confining stratum to prevent both
surface and subsurface leakage from the artesian zone. If leaks occur around
the well casing or adjacent to the well, the well shall be completed with the
seals, packers, or casing necessary to eliminate the leakage. The driller shall
not move the drilling rig from the well site until leakage is completely
stopped, unless authority for temporary removal of the drilling rig is granted
by the state engineer, or when loss of life or property is imminent. If the
well flows naturally at land surface due to artesian pressure, the well shall
be equipped with a control valve so that the flow can be completely stopped.
The control valve must be available for inspection by the state engineer at all
times. All flowing artesian water supply wells shall be tested for artesian
shut-in pressure in pounds per square inch and rate of flow in cubic feet per
second, or gallons per minute, under free discharge conditions. This data shall
be reported on the well log.
11.4.3.6
Exceptions: With state engineer approval, exceptions to minimum
seal depths can be made for shallow wells where the water to be produced is at
a depth less than 30 feet. In no case shall a surface seal extend to a total
depth less than 10 feet below land surface.
11.4.4 Interval Seals. Formations containing
undesirable materials such as fine sand and silt that can damage pumping
equipment and result in turbid water, contaminated groundwater, or poor quality
groundwater must be sealed off so that the unfavorable formation cannot
contribute to the performance and quality of the well. These zones, as well as
zones with significantly differing pressures, must also be sealed to eliminate
the potential of cross contamination or commingling between two aquifers of
differing quality and pressure. Unless approved by the state engineer,
construction of wells that cause the commingling or cross connection of
otherwise separate aquifers is not allowed.
11.4.5 Other Sealing Methods. In wells where
the methods of well sealing described in Section R655-4-11 do not apply,
special sealing procedures can be approved by the state engineer upon written
request by the licensed well driller.
11.5 Special Requirements for Oversized and
Gravel Packed Wells. This section applies to wells in which casing is installed
in an open borehole without driving or drilling in the casing and an annular
space is left between the borehole wall and well casing. For example, mud
rotary wells, flooded reverse circulation wells, and air rotary wells in open
bedrock.
11.5.1 Oversized Borehole. The
diameter of the borehole shall be at least four inches larger than the outside
diameter of the well casing to be installed to allow for proper placement of
the gravel pack or formation stabilizer and adequate clearance for grouting and
surface seal installations. To accept a smaller diameter casing in any
oversized borehole penetrating unconsolidated or stratified formations, the
annular space must be sealed in accordance with Subsection R655-4-11 (11.4). To
minimize the risk of:
1) borehole caving or
collapse;
2) casing failure or
collapse; or
3) axial distortion of
the casing, it is required that the entire annular space in an oversized
borehole between the casing and borehole wall be filled with formation
stabilizer such as approved seal material, gravel pack, filter material or
other state engineer-approved materials. Well casing placed in an oversized
borehole should be suspended at the ground surface until all formation
stabilizer material is placed to reduce axial distortion of the casing if it is
allowed to rest on the bottom of an open oversized borehole. To accept a
smaller diameter casing, the annular space in an oversized borehole penetrating
unconsolidated formations with no confining layer must be sealed in accordance
with Subsection R655-4-11 (11.4) to a depth of at least 30 feet or from static
water level to ground surface, whichever is deeper. The annular space in an
oversized borehole penetrating stratified or consolidated formations must be
sealed in accordance with Subsection R655-4-11 (11.4) to a depth of at least 30
feet or five feet into an impervious strata such as clay or competent
consolidated formation overlying the water producing zones back to ground
surface, whichever is deeper. Especially in the case of an oversized borehole,
the requirements of Subsection R655-4-11 (11.4.4) regarding interval sealing
must be followed.
11.5.2
Gravel Pack or Filter Material. The gravel pack or filter material shall
consist of clean, well-rounded, chemically stable grains that are smooth and
uniform. The filter material should not contain more than 2% by weight of thin,
flat, or elongated pieces and should not contain organic impurities or
contaminants of any kind. To assure that no contamination is introduced into
the well via the gravel pack, the gravel pack must be washed with a minimum 100
ppm solution of chlorinated water or dry hypochlorite mixed with the gravel
pack at the surface before it is introduced into the well. See Table 7 of this
rule for required amount of chlorine material.
11.5.3 Placement of Filter Material. All
filter material shall be placed using a method that through common usage has
been shown to minimize a) bridging of the material between the borehole and the
casing, and b) excessive segregation of the material after it has been
introduced into the annulus and before it settles into place. It is not
acceptable to place filter material by pouring from the ground surface unless
proper sounding devices are utilized to measure dynamic filter depth, evaluate
pour rate, and minimize bridging and formation of voids.
11.5.4 No Surface Casing Used. If no
permanent conductor casing is installed, neat cement grout, sand cement grout,
bentonite grout, or unhydrated bentonite seal shall be installed in accordance
with Subsection R655-4-11 (11.4).
11.5.5 Permanent Conductor Casing Used. If
permanent conductor casing is installed, it shall be unperforated and installed
and sealed in accordance with Subsection R655-4-11 (11.4). After the gravel
pack has been installed between the conductor casing and the well casing, the
annular space between the two casings shall be sealed by either welding a
watertight steel cap between the two casings at land surface or filling the
annular space between the two casings with neat cement grout, sand cement
grout, bentonite grout, or unhydrated bentonite from at least 50 feet to the
surface and in accordance with Subsection R655-4-11 (11.4). If a hole will be
created in the permanent conductor casing to install a pitless adapter into the
well casing, the annual space between the conductor casing and well casing
shall be sealed to at least a depth of 30 feet with neat cement grout, sand
cement grout, bentonite grout, or unhydrated bentonite. A waterproof cap or
weld ring sealing the two casings at the surface by itself without the annular
seal between the two casings is unacceptable when a pitless adapter is
installed in this fashion. Moreover in this case, the annular space between the
surface casing and well casing must be at least 2 inches to facilitate seal
placement.
11.5.6 Gravel Feed Pipe.
If a gravel feed pipe, used to add gravel to the gravel pack after well
completion, is installed, the diameter of the borehole in the sealing interval
must be at least four inches in diameter greater than the permanent casing plus
the diameter of the gravel feed pipe. The gravel feed pipe must have at least
2-inches of seal between it and the borehole wall. The gravel feed pipe must
extend at least 18 inches above ground and must be sealed at the top with a
watertight cap or plug.
11.5.7
Other Gravel Feed Options. If a permanent surface casing or conductor casing is
installed in the construction of a filter pack well, a watertight, completely
welded, steel plate, also known as a weld ring, at least 3/16 of an inch in
thickness shall be installed between the inner production casing and the outer
surface or conductor casing at the wellhead. A watertight fill port with
threaded cap may be installed for placing additional filter pack material in
the well.
11.6
Protection of the Aquifer.
11.6.1 Drilling
Fluids and LCMs. The well driller shall take due care to protect the producing
aquifer from clogging or contamination. Organic substances or phosphate-based
substances shall not be introduced into the well or borehole during drilling or
construction. Every effort shall be made to remove all substances and materials
introduced into the aquifer or aquifers during well construction. "Substances
and materials" shall mean all bentonite-and polymer-based drilling fluids,
filter cake, and any other inorganic substances added to the drilling fluid
that may seal or clog the aquifer. All polymers and additives used in any well
shall be certified by NSF-ANSI approval standards for use in potable water
supply wells, or equivalent standards as approved by the state engineer. The
introduction of lost circulation materials (LCM's) during the drilling process
shall be limited to those products that will not present a potential medium for
bacterial growth or contamination. Only LCM's which are non-organic, which can
be safely broken down and removed from the borehole, may be utilized.
Unacceptable LCM materials include paper or wood products, brans, hulls,
grains, starches, hays or straws, and proteins. This is especially important in
the construction of wells designed to be used as a public water system supply.
All polymers and additives used in any well shall be certified by NSF-ANSI
approval standards for use in potable water supply wells, or equivalent
standards as approved by the Division. The product shall be clearly labeled as
meeting these standards. Polymers and additives must be designed and
manufactured to meet industry standards to be nondegrading and must not act as
a medium which will promote growth of microorganisms.
11.6.2 Containment of Drilling Fluid.
Drilling or circulating fluid introduced into the drilling process shall be
contained in a manner to prevent surface or subsurface contamination and to
prevent degradation of natural or man-made water courses or impoundments.
Requirements regarding the discharges to waters of the state are promulgated
under Section
R317-8-2 and regulated by the Utah Division of Water Quality, 801-536-6146. Pollution of
waters of the state is a violation of Title 19 Chapter 5, Utah Water Quality
Act.
11.6.3 Mineralized,
Contaminated or Polluted Water. When a water bearing stratum that contains
nonpotable mineralized, contaminated or polluted water is encountered, the
stratum shall be adequately sealed off so that contamination or co-mingling of
the overlying or underlying groundwater zones will not occur. Water bearing
zones with differing pressures must also be isolated and sealed off in the well
to avoid aquifer depletion, wasting of water, and reduction of aquifer
pressures.
11.6.4 Down-hole
Equipment. All tools, drilling equipment, and materials used to drill, repair,
renovate, clean, or install a pump in a well shall be free of contaminants
before beginning well construction or other in-well activity. Contaminants
include lubricants, fuel, or bacteria that will reduce the well efficiency, and
any other items that will be harmful to public health or the resource or reduce
the life of the water well. It is recommended that excess lubricants placed on
drilling equipment be wiped clean before insertion into the borehole.
11.6.5 Well Disinfection and Chlorination of
Water. No contaminated or untreated water shall be placed in a well during
construction. Water should be obtained from a chlorinated municipal system.
Where this is not possible, the water must be treated to give at least 100
parts per million free chlorine residual. Upon completion of a well or work on
a well, the driller or pump installer shall disinfect the well using accepted
disinfection procedures to give at least 100 parts per million free chlorine
residual equally distributed in the well water from static level to the bottom
of the well. A chlorine solution designated for potable water use prepared with
either calcium hypochlorite in powdered, granular, or tablet form or sodium
hypochlorite in liquid form shall be used for water well disinfection.
Off-the-shelf chlorine compounds intended for home laundry use, pool or
fountain use should not be used if they contain additives such as antifungal
agents, silica, or scents. Products labeled with "Ultra" may contain these
additives. Table 7 provides the amount of chlorine compound required per 100
gallons of water or 100 feet linear casing volume of water to mix a 100 parts
per million solution. Disinfection situations not depicted in Table 7 must be
approved by the state engineer. Additional recommendations and guidelines for
water well system disinfection are available from the state engineer upon
request.
TABLE 7
Amount of Chlorine Compound for Each 100 Feet of
Water Standing in the Well - 100 ppm solution
|
Well Diameter inches
|
Ca-HyCLT* 25% HOCL ounces
|
Ca-HyCLT 65% HOCL ounces
|
Na-HyCLT** 12-trade % fluid ounces
|
Na-HyCLT** 100% Cl2 pounds
|
2
|
1.00
|
0.50
|
3.5
|
0.03
|
4
|
3.50
|
1.50
|
7.0
|
0.06
|
6
|
8.00
|
3.00
|
16.0
|
0.12
|
8
|
14.50
|
5.50
|
28.0
|
0.22
|
10
|
22.50
|
8.50
|
45.0
|
0.34
|
12
|
32.50
|
12.00
|
64.0
|
0.50
|
14
|
44.50
|
16.50
|
88.0
|
0.70
|
16
|
58.00
|
26.00
|
112
|
0.88
|
20
|
90.50
|
33.00
|
179
|
1.36
|
For every 100 gallons of water, add:
|
5.50
|
2.00
|
11.5
|
0.09
|
Note: *Calcium Hypochlorite - solid
**Sodium Hypochlorite - liquid
***Liquid Chlorine
|
11.7 Special Requirements.
11.7.1 Explosives. Explosives used in well
construction shall not be detonated within the section of casing designed or
expected to serve as the surface seal of the completed well, whether or not the
surface seal has been placed. If explosives are used in the construction of a
well, their use shall be reported on the official well log. In no case shall
explosives, other than explosive shot perforators specifically designed to
perforate steel casing, be detonated inside the well casing or liner
pipe.
11.7.2 Access Port. Every
well shall be equipped with a usable access port so that the position of the
water level, or pressure head, in the well can be measured at all
times.
11.7.3 Completion or
Abandonment. A licensed driller shall not remove the drill rig from a well site
unless the well is completed or abandoned. Completion of a well shall include
all surface seals, gravel packs or curbs required. Dry boreholes, or otherwise
unsuccessful attempts at completing a well, shall be properly abandoned in
accordance with Section
R655-4-14.
Upon completion, all wells shall be equipped with a watertight,
tamper-resistant casing cap or sanitary seal.
11.7.4 Surface Security. If it becomes
necessary for the driller to temporarily discontinue the drilling operation
before completion of the well or otherwise leave the well or borehole
unattended, the well or borehole must be covered securely to prevent
contaminants from entering the casing or borehole and rendered secure against
entry by children, vandals, domestic animals, and wildlife.
11.7.5 Pitless Adapters and Units. Pitless
adapters or units are acceptable to use with steel well casing as long as they
are installed in accordance with manufacturers recommendations and
specifications as well as meet the Water Systems Council Pitless Adapter
Standard (PAS-97) which are incorporated by reference and are available from
Water Systems Council, 13 Bentley Dr., Sterling, VA 20165, phone 703-430-6045,
fax 703-430-6185, email watersystemscouncil.org. The pitless adaptor, including
the cap or cover, casing extension, and other attachments, must be so designed
and constructed to be secure, water tight, and to prevent contamination of the
potable water supply from external sources. Pitless wellhead configurations
shall have suitable access to the interior of the well to measure water level
and for well disinfection purposes. Pitless configurations shall be of
watertight construction throughout and be constructed of materials at least
equivalent to and having wall thickness and strength compatible to the casing.
Pitless adapters or units are not recommended to be mounted on PVC well casing.
If a pitless adapter is to be used with PVC casing, it should be designed for
use with PVC casing, and the driller should ensure that the weight of the pump
and column do not exceed the strength of the PVC well casing. If it is known
that a pitless adapter or unit will be installed on a well, a cement grout seal
shall not be allowed within the pitless unit or pitless adaptor sealing
interval as the well is being constructed. The pitless adapter or unit sealing
interval shall be sealed with unhydrated bentonite as the well is constructed
and before pitless installation. Upon pitless adapter or unit installation, the
surface seal below the pitless connection shall be protected and maintained.
After the pitless adapter or unit has been installed, the associated excavation
around the well from the pitless connection to ground surface shall be
backfilled and compacted with low permeability fill that includes clay. The
pitless adapter or unit, including the cap or cover, pitless case and other
attachments, shall be designed and constructed to be watertight to prevent the
entrance of contaminants into the well from surface or near-surface
sources.
11.7.6 Hydraulic
Fracturing. The hydraulic fracturing pressure shall be transmitted through a
drill string and shall not be transmitted to the well casing. Hydraulic
fracturing intervals shall be at least 20 feet below the bottom of the
permanent casing of a well. All hydraulic fracturing equipment shall be
thoroughly disinfected with a 100 part per million chlorine solution before
insertion into the well. The driller shall include the appropriate hydraulic
fracturing information on the well log including methods, materials, maximum
pressures, location of packers, and initial or final yields. In no case shall
hydrofacturing allow commingling of waters within the well bore. Clean sand or
other material such as propping agents approved by the Division may be injected
into the well to hold the fractures open when pressure is removed.
11.7.7 Static Water Level, Well Development,
and Well Yield. To fulfill the requirements of Subsection
R655-4-4 (4.5.2), new wells designed to produce water shall be developed to remove drill
cuttings, drilling mud, or other materials introduced into the well during
construction and to restore the natural groundwater flow to the well to the
extent possible. After a water production well is developed, a test should be
performed to determine the rate at which groundwater can be reliably produced
from the well. Following development and testing, the static water level in the
well should also be measured. Static water level, well development information,
and well yield information shall be noted on the official submittal of the well
log by the well driller.
11.7.8
Packers. Packers shall be of a material that will not impart taste, odor, toxic
substances or bacterial contamination to the water in the well.
11.7.9 Screens. Screens must be constructed
of corrosion-resistant material and sufficiently strong to withstand stresses
encountered during and after installation. Screen slot openings, screen length,
and screen diameter should be sized and designed to provide sufficient open
area consistent with strength requirements to transmit sand-free water from the
well. Screens should be installed so that exposure above pumping level will not
occur.
11.7.10 Openings in the
Casing. There shall be no opening in the casing wall between the top of the
casing and the bottom of the required casing seal except for pitless adapters,
measurement access ports, and other approved openings installed in conformance
with these standards. In no case shall holes be cut in the casing wall for
lifting or lowering casing into the well bore unless such holes are properly
welded closed and watertight before placement into the well bore.
11.7.11 Casing vents. If a well requires
venting, it must terminate in a down-turned position at least 18-inches above
ground level, at or above the top of the casing or pitless unit and be covered
with a 24 mesh corrosion-resistant screen.