Utah Administrative Code
Topic - Environmental Quality
Title R309 - Drinking Water
Rule R309-550 - Facility Design and Operation: Transmission and Distribution Pipelines
Section R309-550-8 - Installation of Water Mains
Current through Bulletin 2024-18, September 15, 2024
(1) Standards.
The specifications shall incorporate the provisions of the manufacturer's recommended installation procedures or the following applicable standards:
(2) Bedding.
A continuous and uniform bedding shall be provided in the trench for all buried pipe. Stones larger than the backfill materials described below shall be removed for a depth of at least 6 inches below the bottom of the pipe.
(3) Backfill.
Backfill material shall be tamped in layers around the pipe and to a sufficient height above the pipe to adequately support and protect the pipe. The material and backfill zones shall be as specified by the standards referenced in Subsection (1), above. As a minimum:
(4) Dropping Pipe into Trench.
Under no circumstances shall the pipe or accessories be dropped into the trench.
(5) Burial Cover.
All water mains shall be covered with sufficient earth or other insulation to prevent freezing, unless they are part of a noncommunity system that can be shut-down and drained during winter months when temperatures are below freezing.
(6) Thrust Blocking.
All tees, bends, plugs, and hydrants shall be provided with thrust blocking, anchoring, tie rods, or restraint joints designed to prevent movement. Restraints shall be sized to withstand the forces experienced.
(7) Pressure and Leakage Testing.
All types of installed pipe shall be pressure tested and leakage tested in accordance with AWWA Standard C600-10.
(8) Surface Water Crossings.
(9) Sealing Pipe Ends During Construction.
The open ends of all pipelines under construction shall be covered and effectively sealed at the end of the day's work.
(10) Disinfecting Water Lines.
All new water mains or appurtenances shall be disinfected in accordance with AWWA Standard C651-05 or a method approved by the Director. The specifications shall include detailed procedures for the adequate flushing, disinfection and microbiological testing of all water mains. On all new and extensive distribution system construction, evidence of satisfactory disinfection shall be provided to the Division. Samples for coliform analyses shall be collected after disinfection is complete and the system is refilled with drinking water. A standard heterotrophic plate count is advisable. The use of water for public drinking water purposes shall not commence until the bacteriologic tests indicate the water is free from contamination.