Utah Administrative Code
Topic - Environmental Quality
Title R309 - Drinking Water
Rule R309-545 - Facility Design and Operation: Drinking Water Storage Tanks
Section R309-545-8 - Tank Elevation and Burial

Universal Citation: UT Admin Code R 309-545-8

Current through Bulletin 2024-06, March 15, 2024

(1) Flood Elevation.

The bottom of a ground-level or buried drinking water storage tank shall be located at least 3 feet above the 100-year flood level or the highest known maximum flood elevation, whichever is higher.

(2) Ground Water.

When the bottom of a drinking water storage tank will be placed below the normal ground surface, it shall be placed above the local ground water table.

(3) Covered Roof.

When the roof of a drinking water storage tank will be covered by earth, the roof shall be sloped to drain toward the outside edge of the tank.

Disclaimer: These regulations may not be the most recent version. Utah may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.