Utah Administrative Code
Topic - Environmental Quality
Title R309 - Drinking Water
Rule R309-545 - Facility Design and Operation: Drinking Water Storage Tanks
Section R309-545-13 - Tank Overflow

Universal Citation: UT Admin Code R 309-545-13

Current through Bulletin 2024-06, March 15, 2024

All water storage tanks shall be provided with an overflow that discharges at an elevation between 12 and 24 inches above the ground surface or the rim of the receiving basin. The discharge shall be directed away from the tank and shall not cause erosion.

(1) Diameter.

Overflow pipes shall be of sufficient capacity to permit waste of water in excess of the filling rate.

(2) Slope.

Overflow pipes shall be sloped for complete drainage.

(3) Screen.

Overflow pipes shall be screened with No. 4 mesh non-corrodible screen installed at a location least susceptible to damage by vandalism.

(4) Visible Discharge.

Overflow pipes shall be located so that any discharge is visible.

(5) Cross Connections.

Overflow pipes shall not be connected to, or discharge into, any sanitary sewer system.

Disclaimer: These regulations may not be the most recent version. Utah may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.