Utah Administrative Code
Topic - Environmental Quality
Title R309 - Drinking Water
Rule R309-525 - Facility Design and Operation: Conventional Surface Water Treatment
Section R309-525-16 - In-Plant Finished Drinking Water Storage
Current through Bulletin 2024-18, September 15, 2024
(1) General.
In addition to the following, the applicable design standards of R309-545 shall be followed for plant storage.
Backwash water tanks shall be sized, in conjunction with available pump units and finished water storage, to provide the backwash water required by R309-525-15(7). Consideration shall be given to the backwashing of several filters in rapid succession.
Clearwell storage shall be sized, in conjunction with distribution system storage, to relieve the filters from having to follow fluctuations in water use.
(2) Adjacent Compartments.
Finsihed drinking water shall not be stored or conveyed in a compartment adjacent to unsafe water when the two compartments are separated by a single wall. The Director may grant an exception to this requirement for small "package" treatment plants using metal tanks of sufficient wall thickness.
(3) Basins and Wet-Wells.
Receiving basins and pump wet-wells for finished drinking water shall be designed as drinking water storage structures. (See Section R309-545)