Utah Administrative Code
Topic - Environmental Quality
Title R309 - Drinking Water
Rule R309-520 - Facility Design and Operation: Disinfection
Section R309-520-9 - Ozone
Universal Citation: UT Admin Code R 309-520-9
Current through Bulletin 2024-18, September 15, 2024
(1) General Requirements.
(a) Ozone is approved as a primary
disinfectant, but is not approved as a secondary disinfectant for the
distribution system because of its rapid decomposition in aqueous solution. A
different disinfectant approved for secondary disinfection must be used if a
minimum disinfection residual is required in the distribution system. Ozone may
also be used for taste and odor control, oxidation of inorganic and organic
compounds and for enhanced performance of other water treatment processes such
as microflocculation and filtration. Some of the requirements of this section
may not be applicable if ozone is used only for reasons other than primary
disinfection.
(b) Pilot studies or
bench scale studies shall be conducted for all surface waters unless there is
sufficient data available from other studies performed on the same water
source. The studies shall determine the initial ozone demand, the rate of ozone
decay, the minimum and maximum ozone dosages for the range of water conditions
for disinfection "CT" compliance, and the ozone dosage required for other
desired benefits. Pilot studies or bench scale studies shall take into account
the seasonal and other variations of the source water. Plans for pilot studies
or bench scale studies shall be reviewed and accepted by the Director prior to
commencement of the studies.
(2) Ozone Generation.
(a) The ozone system should be designed with
backup capability such that required inactivation can be achieved with one
generator out of service.
(b) The
ozone generators shall be housed in an enclosed temperature controlled building
for protection. Adequate ventilation shall be provided in the building, and be
capable of providing six or more air changes per hour when needed in case of an
ozone leak.
(c) The ozone
generators shall be of the medium or high frequency type.
(d) The power supply units for the ozone
generators shall have a backup electrical power source, normally an emergency
generator, or the system shall have an alternate primary disinfection system
that may be used in case of an electrical power outage.
(e) The ozone generators shall be
water-cooled with a maximum increase in cooling water temperature of 10 degrees
F (5.6 degrees C). If necessary, the cooling water should be treated to
minimize corrosion, scaling, and microbiological fouling of the water side of
the tubes. A closed-loop cooling water system may be used to assure proper
water conditions are maintained. The power supply units to the ozone generators
may also be water cooled.
(f) The
ozone generators shall comply with Section 3705 of Chapter 37, "Ozone Gas
Generators," of the 2006 International Fire Code.
(3) Ozone Generator Feed Gas.
(a) Feed gas may be air, vaporized high
purity liquid oxygen, or oxygen enriched air. Oxygen may be generated on-site
or delivered in bulk. Oxygen-enriched air is typically generated
on-site.
(b) The design of the feed
gas system must ensure that the maximum dew point of the feed gas of -76
degrees F (-60 degrees C) is not exceeded at any time.
(c) Liquid Oxygen Feed Gas Systems.
(i) Liquid oxygen storage tanks shall be
sized to provide a minimum of a 7-day supply to the ozone generators at the
maximum operating rate.
(ii) There
shall be two or more vaporizers to convert liquid oxygen to the gaseous form.
Vaporizers must be capable of maintaining oxygen flow at the minimum design air
temperature with one unit on standby.
(iii) Liquid oxygen storage tanks and system
shall comply with Chapters 40, "Oxidizers," of the 2006 International Fire
Code.
(d) Air or Oxygen
Enriched Air Feed Gas Systems.
(i) There shall
be two or more air compressors to supply air. The capacity of the compressors
shall be such that the demand during maximum ozone production and for other
compressed air uses at the treatment plant can be met when the largest
compressor is out of service.
(ii)
Entrainment separators, refrigeration dryers, desiccant dryers, and filters
shall be used as necessary to provide a sufficiently dried, dust-free, and
oil-free feed gas to the ozone generators. Multiple units of this equipment
shall be used so that the ozone generation is not interrupted in the event of a
breakdown.
(4) Ozone Contactors.
(a) An ozone contactor shall consist of two
or more chambers to provide for introduction of ozone into the water and
contact time. In a water treatment plant, ozone may be introduced in the raw
water, or ozone may be introduced later in the process, such as to settled
water after solids have been removed. An ozone contactor must be a closed
vessel that is kept under less than atmospheric pressure to prevent escape of
ozone gas. The materials of construction must be ozone-resistant to prevent
premature failure of the contactor.
(b) Ozone gas may be injected into the water
under positive pressure through bubble diffusers using porous-tube or dome
diffusers. Alternatively, ozone gas may be injected into the water using side
stream injection. This is where ozone gas is drawn into the side stream using
negative pressure, which is generated in a pipe section with a
venturi.
(c) An ozone contactor
shall be designed to achieve a minimum transfer efficiency of 85
percent.
(d) Multiple sampling
points shall be provided in an ozone contactor to enable sampling of treated
water for purposes of determining an accurate measure of the concentration to
be used in the "CT" disinfection calculation.
(e) A recommended minimum disinfection
contact time is ten minutes.
(f)
Ozone contactors shall have provision for cleaning, maintenance, and drainage
of the contactor. Each contactor chamber shall be equipped with an access
hatchway or other means of entry.
(g) An ozone contactor shall have an
emergency off-gas pressure/vacuum relief system to prevent damage to the
unit.
(h) A system must be provided
for worker safety at the end of the ozone contactor for compliance with OSHA
standards. Specifically, ozone levels in the gas space above treated water that
has exited the contactor must not exceed the established OSHA 8-hour exposure
limit of 0.1 ppm. This system may be an ozone residual quenching system where a
chemical is used to destroy remaining ozone in the water, or this system may be
a monitoring system that provides sufficient time to lower the residual ozone
level in the water by natural decay to an acceptable level. Any chemical used
to quench residual ozone shall comply with ANSI/NSF Standard 60.
(5) Off-Gas Destruction Units.
(a) A system for treating the final off-gas
from each ozone contactor must be provided in order to meet safety standards.
Systems using thermal destruction or catalytic destruction may be used. At
least two units shall be provided which are each capable of handling the entire
off-gas flow.
(b) Exhaust blowers
shall be provided in order to draw off-gas from the contactor into the
destruction units.
(c) Provisions
must be made to drain water from condensation in the off-gas piping and to
protect the destruction units and piping from moisture and other impurities
that may cause damage.
(d) The
maximum allowable ozone concentration in the gas discharge from a destruction
unit is 0.1 ppm by volume. Provisions may be made for temporary transient
concentration spikes that may exceed this limit.
(6) Piping and Connections.
(a) Because ozone is a strong oxidant,
consideration shall be given to piping materials used in ozone service.
Generally, only low carbon 304L and 316L stainless steel should be used for
ozone gas service.
(b) Connections
on piping used for ozone service should be welded where possible. Threaded
connections should be avoided for ozone gas piping because of their tendency to
leak. Connections with meters, valves, or other equipment should be made with
flanged joints with ozone-resistant gaskets.
(c) A positive-closing 90-degree turn
isolation valve, or other equivalent means, shall be provided in the piping
between an ozone generator and a contactor to prevent moisture from reaching
the ozone generator during shutdowns.
(7) Instrumentation and Monitoring.
(a) A flow meter shall be provided to measure
the flow rate of the water being treated. A temperature gauge or transmitter
shall also be provided to measure the temperature of the water being treated.
The pH shall also be measured to indicate changes in the water being
treated.
(b) An ozone gas analyzer,
a flow meter, and a temperature measurement shall be provided on the gaseous
ozone feed line going to the ozone injection point.
(c) Ozone aqueous residual analyzers shall be
provided to measure the ozone residual concentration in the water being treated
in order to determine "CT" credit.
(d) An ozone gas analyzer shall be provided
on the gas discharge of each ozone destruction unit, or combined vent gas
discharge, to determine the exiting ozone concentration.
(e) Ambient ozone monitors shall be installed
in the vicinity of the ozone generators, the ozone contactors, the ozone
destruction units, and other areas where ozone gas may accumulate.
(f) A continuous dew point monitor shall be
provided on the feed gas line to the ozone generators.
(g) Instrumentation such as pressure gauges,
temperature gauges, flow meters, and power meters shall be provided as
necessary to monitor the feed gas system, ozone generators, power supply units,
and cooling water to protect the equipment and monitor performance.
(8) Alarms and Shutdowns.
(a) An ambient ozone monitor shall be
provided.
(b) The design shall
include alarms and shutdowns.
(9) Safety.
(a) Training shall be provided to the
operators of ozone systems by the manufacturers of the ozone equipment, or
other professionals with experience in ozone treatment, to promote the safe
operation of the systems.
(b)
Appropriate signs shall be installed around ozone and liquid oxygen equipment
to warn operators, emergency responders, and others of the potential
dangers.
(c) A means shall be
provided, such as portable purge air blowers and portable monitors, to reduce
residual ozone levels in an ozone contactor or other equipment to safe levels
prior to entry for repair, maintenance, or emergency.
(10) Operation and Maintenance.
(a) An ambient ozone monitor should activate
an alarm when the ozone level exceeds 0.1 ppm. Because the natural ozone levels
can exceed 0.1 ppm under certain atmospheric conditions, it is permissible to
set the alarm level at a slightly higher level to avoid nuisance alarms. Ozone
generator shutdown shall occur when ambient levels exceed 0.3 ppm in the
vicinity of an ozone generator or a contactor. Operators of the water treatment
system may set the alarm level and the shutdown level lower at their
discretion. It is required that an ozone ambient monitor activates a local
audible alarm and/or flashing light warning, in addition to an alarm at the
operator control system panel.
(b)
There shall be an alarm/shutdown to prevent the dew point of the feed gas
exceeding the maximum of -76 degrees F (-60 degrees C).
(c) Alarms and shutdowns shall be programmed
based on the pressure gauges, temperature gauges, flow meters, and power
meters, to protect the feed gas system, ozone generators, power supply units,
and cooling water system.
Disclaimer: These regulations may not be the most recent version. Utah may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.