Utah Administrative Code
Topic - Environmental Quality
Title R309 - Drinking Water
Rule R309-511 - Hydraulic Modeling Requirements
Section R309-511-7 - Hydraulic Model Design Elements Report
Current through Bulletin 2024-18, September 15, 2024
The public water system or its agent shall prepare a Hydraulic Model Design Elements Report along with, and in support of, the certification stated in R309-511-6(1). The Hydraulic Model Design Elements Report shall contain, but is not limited to, the following elements:
(1) if the public drinking water system provides water for outdoor use, the report must describe the criteria used to estimate this demand. If the irrigation demand map in R309-510-7(3) is not used, the report shall provide justification for the alternative demands used in the model. If the irrigation demands are based on the map in R309-510-7(3) the report must identify the irrigation zone number, a statement and/or map of how the irrigated acreage is spatially distributed, and the total estimated irrigated acreage. The indicated irrigation demands must be used in the model simulations;
(2) the total number of connections served by the water system including existing connections and anticipated new connections served by the water system after completion of the construction of the project;
(3) the total number of equivalent residential connections (ERC) including both existing connections as well as anticipated new connections associated with the project. The number of ERCs must include high as well as low- volume water users. The determination of the ERCs shall be based on flow requirements using the anticipated demand as outlined in R309-510, or based on alternative sources of information that are deemed acceptable by the Director;
(4) the methodology used for calculating demand and allocating it to the model; a summary of pipe length by diameter; a hydraulic schematic of the distribution piping showing pressure zones, general pipe connectivity between facilities and pressure zones, storage, elevation and sources; and a list or ranges of values of the friction coefficient used in the hydraulic model according to pipe material and condition in the system. All coefficients of friction used in the hydraulic analysis shall be consistent with standard practices;
(5) a statement stating either "yes fire hydrants exist or will exist within the system" or "there are no fire hydrants connected to the system and there is no plan to add fire hydrants with this project." Either statement will require the identification of the local fire authority's name, address, and contact information, as well as the fire flow quantity and duration if required;
(6) the locations of the lowest pressures within the distribution system, and areas identified by the hydraulic model as not meeting each scenario of the minimum pressure requirements in R309-105-9; and,
(7) calibration method and quantitative summary of the calibration results (e.g., comparison tables, graphs).