(1) The owner or operator shall ensure that all control equipment on storage vessels is properly installed and maintained.
(2) The owner or operator shall conduct routine inspections from the top of the tank for external floating roofs or through roof hatches for internal floating roofs at six month or shorter intervals to insure there are no holes, tears, or other openings in the seal or seal fabric.
(3) A close visible inspection of the primary seal of an external floating roof is to be conducted at least once per year from the roof top unless such inspection requires detaching the secondary seal, which would result in damage to the seal system.
(4) Whenever a tank is emptied and degassed for maintenance, an emergency, or any other similar purpose, a close visible inspection of the cover and seals shall be made.
(5) The director must be notified 7 days prior to the refilling of a tank that has been emptied, degassed for maintenance, an emergency, or any other similar purpose. Any non-compliance with this rule must be corrected before the tank is refilled.