Rule R307-315 - NO[x] Emission Controls for Natural Gas-Fired Boilers 2.0-5.0 MMBtu
Section R307-315-4 - Requirements
Universal Citation: UT Admin Code R 307-315-4
Current through Bulletin 2024-06, March 15, 2024
(1) A person that:
(a) begins construction, or modification of a
boiler;
(b) replaces a burner in a
boiler having only a single burner; or
(c) replaces 50% or more of the burners in a
multi-burner boiler for a boiler meeting the requirements of Section
R307-315-2 shall install a
burner that meets a NOx emission rate of nine parts per
million by volume (ppmv) or less at 3% volume stack gas oxygen on a dry
basis.
(2) An owner or operator of a boiler subject to Subsection R307-315-4(1) shall:
(a) operate and maintain the boiler
and boiler subsystems, including burners, according to the manufacturer's
instructions;
(b) determine
continued compliance based on Section
R307-315-6; and
(c) meet the applicable recordkeeping
requirements for any control device.
Disclaimer: These regulations may not be the most recent version. Utah may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.