Current through Reg. 49, No. 52; December 27, 2024
(a) Site selection.
In the selection of a site for a lift station, consideration shall be given to
accessibility and potential nuisance aspects. The station shall be protected
from the 100-year flood and shall be accessible during a 25-year flood. All
lift stations shall be intruder-resistant with a controlled access. Lift
stations should be located as remotely as possible from populated
areas.
(b) Design.
(1) Small lift stations. Lift stations
designed for a discharge capacity of less than 100 gallons per minute will be
reviewed on a case-by-case basis by the commission and shall be used only for
institutional use or other locations where it is necessary to pump the sewage
from a single building, school, or other measurable source establishment into
the sanitary sewer lines. If the location of the discharge does not provide a
positive head due to elevation, then a positive pressure control valve shall be
provided. Ejectors may be used for this type of lift station. Whenever a lift
station handles waste from two or more residential housing units, or from any
public establishment, standby pumps shall be provided. In the case of ejectors
or eductors, two air compressors shall be provided. Grinder pumps should be
used for all small installations.
(2) Dry well sump pump. The following design
considerations shall be addressed in providing dry well sump pumps.
(A) Two separate sump pumps should be
provided for removal of leakage or water from the dry well floor.
(B) The discharge pipe level from the sump
pumps shall be above the maximum liquid level of the wet well. A check valve
should be installed on the discharge side of each sump pump.
(C) All floor and walkway surfaces shall have
an adequate slope to a point of drainage with sufficient measures taken to
maximize traction and safety.
(D)
Motors to drive sump pumps shall be located above the height of the maximum
liquid level in the wet well. As an alternate, sump pumps may be of the
submersible type.
(3)
Pump controls. All lift stations shall have automatically operated pump control
mechanisms. Pump control mechanisms shall be located so that they will not be
affected by flow currents in the wet well. Provisions shall be made to prevent
grease and other floating materials and rags in the wet well from interfering
with the operation of the controls. When a float tube is located in the dry
well, its height shall be such as to prevent overflow of the sewage into the
dry well. Pump control mechanisms which depend on a bubbler in the wet well
shall be equipped with a backup air supply system. All connections to level
controls in the wet well shall be accessible at all times. The circuit
breakers, indicator lights, pump control switches, and other electrical
equipment should be located on a control panel at least three feet above ground
surface elevation. If controls are located in a dry well, the dry well shall be
protected from flooding.
(4) Wet
wells.
(A) Wet wells and dry wells, including
their superstructure, shall be separated by at least a watertight and gastight
wall with separate lockable entrances provided to each. Equipment requiring
regular or routine inspection and maintenance shall not be located in the wet
well, unless the maintenance can be accomplished without entering the wet
well.
(B) Based on design flow, wet
well capacity should provide a pump cycle time of not less than six minutes for
those lift stations using submersible pumps and not less than 10 minutes for
other nonsubmersible pump lift stations.
(C) All influent gravity lines into a wet
well shall be located where the invert is above the "off" setting liquid level
of the pumps, and preferably should be located above the lead pump "on"
setting.
(5) Stairways.
Stairways with non-slip steps shall be provided in all underground dry wells.
Removable ladders may be provided in small stations where it is impractical to
install stairways.
(6) Ventilation.
Ventilation shall be provided for lift stations, including both wet and dry
wells.
(A) Passive ventilation such as
gooseneck type or turbine ventilators designed to prevent possible entry of
insects or birds shall be provided in all wet wells if mechanical ventilation
is not provided. All mechanical and electrical equipment in wet wells should be
explosion-proof and spark-proof construction if mechanical ventilation is not
provided.
(B) Mechanical
ventilation shall be provided for all dry wells below the ground surface. The
ventilation equipment shall have a minimum capacity of six air changes per hour
under continuous operations. At least a capacity of 30 air changes per hour
shall be required where the operation is intermittent. All intermittently
operated venting equipment shall be interconnected with the stations lighting
system.
(7) Wet well
slopes. The bottom of wet wells shall have a minimum slope of 10% to the pump
intakes and shall have a smooth finish. There shall be no projections in the
wet well which will allow deposition of solids under ordinary operating
conditions. Antivortex baffling should be considered for the pump suctions in
all large sewage pumping stations (greater than five million gallons per day
(mgd) firm pumping capacity).
(8)
Hoisting equipment. Hoisting equipment or access by hoisting equipment for the
removal of pumps, motors, valves, etc., shall be incorporated in the station
design.
(9) Dry wells and valve
vault drains. Drains from dry wells or valve vaults to the wet well shall be
equipped with suitable devices to prevent entry of potentially hazardous
gases.
(c) Pumps.
(1) General. All raw sewage pumps shall be of
a non-clog design, capable of passing 2 1/2 inch diameter spheres, and shall
have no less than three-inch diameter suction and discharge openings.
Inspection and cleanout plates, located both on the suction and discharge sides
of each pumping unit, are suggested for all nonsubmersible pumps so as to
facilitate locating and removing blockage-causing materials. Where such
openings are not provided on the pumps, a hand hole in the first fitting
connected to the suction of each pump shall be provided. All pumps shall be
securely supported so as to prevent movement during operation. For submersible
pumps, rail-type pump support systems incorporating manufacturer-approved
mechanisms designed to allow the operator to remove and replace any single pump
without first entering or dewatering the wet well should be provided.
(2) Lift station pumping capacity. The firm
pumping capacity of all lift stations shall be such that the expected peak flow
can be pumped to its desired destination. Firm pumping capacity is defined as
total station maximum pumping capacity with the largest pumping unit out of
service.
(3) Variable capacity
pumps. Lift stations or transfer pumping facilities at a wastewater treatment
plant or those discharging directly to the treatment plant where the plant's
permitted daily average flow is equal to or greater than 100,000 gallons per
day shall be provided with three or more pumps or with duplex automatically
controlled variable capacity pumps or other automatic flow control devices. The
pumps or other devices shall be adjusted for actual flow conditions and
controlled to operate so as to minimize surges in the treatment units. No
single pumping unit shall have a capacity greater than the design peak flow of
the wastewater treatment plant unless flow splitting/equalization is
provided.
(4) Pump head
calculations. The engineering design report accompanying the plans shall
include system curves, pump curves, and head calculations. Calculations and
pump curves at both minimum (all pumps off) and maximum (last normal operating
pump on) static heads and for a C value of both 100 and 140 must be provided
for each pump and for the combination of pumps (modified pump curves). Where a
suction lift is required, the report shall include a calculation of the
available net positive suction head (NPSH) and a comparison of that value to
the required NPSH for the pump as furnished by the pump manufacturer.
(5) Self-priming pumps. Only self-priming
pumps or pumps with acceptable priming systems, as demonstrated by a reliable
record of satisfactory operation, shall be used where the suction head is
negative. All self-priming pumps shall include a means for venting the air back
to the wet well when the pump is priming.
(6) Pump positioning. All raw sewage pumps,
other than submersible pumps without "suction" piping and self-priming units
capable of satisfactory operation under any negative suction heads anticipated
for the lift station under consideration, shall be positioned such that the
pumps always experience, during their normal on-off cycling, a positive static
suction head.
(7) Grinder pumps.
See § 317.2(d) of this title (relating to Sewage Collection System).
(d) Piping.
(1) Pump suctions. Each pump shall have a
separate suction pipe. Cavitation may be avoided by using eccentric reducers in
lieu of typical reducers in order to prevent air pockets from forming in the
suction line.
(2) Valves. Full
closing valves shall be installed on the discharge piping of each pump and on
the suction of all dry pit pumps. A check valve shall be installed on the
discharge side of each pump, preceding the full closing valve. Check valves
should be of a swing check type with external levers. Rubberball check valves
may be used for grinder pump installations in lieu of the swing check type.
Butterfly valves, tilting disc check valves, or other valves with a pivoted
disc in the flow line are not allowed. The design shall consider surge effects
and provide protection where necessary. Surge relief shall be contained in the
system.
(3) Valve position
indicators. Gate valves should be rising-stem valves. If other than rising-stem
gate valves and check valves with external levers are used, the valves shall
include a position indicator to show their open and closed positions.
(4) Lift station piping. Flanged pipe and
fitting or welded pipe shall be used for exposed piping inside of lift
stations. A flexible or flanged connection shall be installed in the piping to
each pump so that the pump may be removed easily for repairs. Provisions shall
be made in the design to permit flexure where pipes pass through walls of the
station. Piping should normally be sized so that the maximum suction velocity
does not exceed five feet per second and the maximum discharge velocity does
not exceed eight feet per second.
(5) Force main pipe selection. Force mains
shall be a minimum of four inches in diameter, unless justified, as with the
use of grinder pumps. In no case shall the velocity be less than two feet per
second with only the smallest pump operating, unless special facilities are
provided for cleaning the line at specified intervals or it can be shown that a
flushing velocity of five feet per second or greater will occur one or more
times per day. Pipe specified for force mains shall be of a type having an
expected life at least as long as that of the lift station and shall be
suitable for the material being pumped and the operating pressures to which it
will be subjected. All pipe shall be identified in the technical specifications
with appropriate American Society for Testing and Materials (ASTM), American
National Standards Institute (ANSI), or American Water Works Association (AWWA)
specifications numbers for both quality control (dimensions, tolerances, etc.)
and installation (bedding, backfill, etc.). All pipe and fittings shall have a
minimum working pressure rating of 150 pounds per square inch.
(6) Force main tests. Final plans and
specifications shall describe and require pressure testing for all installed
force mains. Minimum test pressure shall be 1.5 times the maximum design
pressure.
(7) Air release valves.
Air release valves or combination air release/vacuum valves suitable for sewage
service shall be provided at all peaks in elevation. The final engineering
drawings must depict all proposed force mains in both plan and
profile.
(e) Emergency
provisions. Lift stations shall be designed such that there is not a
substantial hazard of stream pollution from overflow or surcharge onto public
or private property with sewage from the lift station. Options for a reliable
power source may include the following.
(1)
Power supply. The commission will determine the reliability of the existing
commercial power service. Such determinations shall be based on power outage
records obtained from the appropriate power company and presented to the
commission. When requesting outage records for submittal to the commission, it
is important to note that the records be in writing, bear the signature of an
authorized utility employee, identify the location of the wastewater facilities
being served, list the total number of outages that have occurred during the
past 24 months, and indicate the duration of each recorded outage. The facility
will be deemed reliable if the demonstrated wastewater retention capacity, in
the station's wet well, spill retention facility, and incoming gravity sewer
lines, is sufficient to insure that no discharge of untreated wastewater will
occur for a length of time equal to the longest electrical outage recorded in
the past 24 months. If records for the service area cannot be obtained, a 120
minute worst case outage duration will be assumed. Provisions for a minimum
wastewater retention period of 20 minutes should be considered even in those
cases where power company records indicate no actual outages of more than 20
minutes occurred during the past 24 months.
(2) Alternative power supply. If the existing
power supply is found to be unreliable, an emergency power supply or detention
facility shall be provided. Options include:
(A) electrical service from two separate
commercial power companies, provided automatic switchover capabilities are in
effect;
(B) electrical service from
two independent feeder lines or substations of the same electric utility,
provided automatic switchover capabilities are in effect;
(C) on-site automatic starting electrical
generators;
(D) reliance on
portable generators or pumps. Proposals for the utilization of portable units
shall be accompanied by a detailed report showing conclusively the ability of
such a system to function satisfactorily. Portable units will be approved only
in those cases where the station is equipped with an auto-dialer, telemetry
device, or other acceptable operator notification device, operators
knowledgeable in acquisition and startup of the portable units are on 24-hour
call, the station is accessible in all weather conditions, reasonable
assurances exist as to the timely availability and accessibility of the proper
portable equipment, and the station is equipped with properly designed and
tested quick connection facilities. This option is usually acceptable only for
smaller lift stations.
(3) Restoration of lift station. Provisions
should be made to restore the lift station to service within four hours of
outage.
(4) Spill containment
structures. A spill containment structure should be considered together with
in-system retention in determining a total wastewater retention time. Because
separate spill retention facilities are not suitable for all locations,
engineers should check with the commission prior to designing such structures.
The design shall provide:
(A) a minimum
storage volume of average design flow from the contributing area and the
longest power outage during the most recent consecutive 24-month period or, if
power records are not available, an assumed 24-hour outage;
(B) an impermeable liner (such as concrete or
synthetic fabric (20 mil thickness)) and should have an energy dissipator at
the point of overflow from the lift station to prevent scour;
(C) a fence with a controlled access;
and
(D) a plan for routine cleaning
and inspection.
(5)
Alarm system. An audiovisual alarm system (red flashing light and horn) shall
be provided for all lift stations. These alarm systems should be telemetered to
a facility where 24-hour attendance is available. The alarm system shall be
activated in case of power outage, pump failure, or a specified high water
level.