Texas Administrative Code
Title 30 - ENVIRONMENTAL QUALITY
Part 1 - TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
Chapter 217 - DESIGN CRITERIA FOR DOMESTIC WASTEWATER SYSTEMS
Subchapter G - FIXED FILM AND FILTRATION UNITS
Section 217.188 - Submerged Biological Contactor
Universal Citation: 30 TX Admin Code § 217.188
Current through Reg. 50, No. 13; March 28, 2025
(a) A submerged biological contactor (SBC) must be air driven and does not require a cover. An SBC is any biological contactor where more than 60% of the surface is below the water level at design flow.
(b) An SBC system requires the same pretreatment as a rotating biological contactor system and must meet the criteria in § 217.185 of this title (relating to Rotating Biological Contactors), except as described in paragraphs (1) and (2) of this subsection.
(1) Each SBC unit must include two air headers - one to provide rotation of the unit, and one to provide dissolved oxygen for biological activity.
(2) Submerged bearings must be sealed to prevent intrusion of wastewater.
(c) If an SBC has any moving parts that require lubrication, an SBC must have lubrication access above the water level.
Disclaimer: These regulations may not be the most recent version. Texas may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.