(a) A rotating biological contactor (RBC) system designed for five-day biochemical oxygen demand (BOD5) removal and nitrification of domestic wastewater in a single system must include four stages and have a maximum overall organic loading rate of 1.6 pounds of BOD5 per day per 1,000 square feet of media.
(b) A nitrifying RBC must be designed to allow chemical addition if the influent pH is below 7.0 standard units.
(c) The engineering report must justify the nitrification rate of a system using calculations.
(d) A nitrifying RBC system may be subject to the requirements of § 217.7(b)(2) of this title (relating to Types of Plans and Specifications Approvals).
Disclaimer: These regulations may not be the most recent version. Texas may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.