Texas Administrative Code
Title 30 - ENVIRONMENTAL QUALITY
Part 1 - TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
Chapter 117 - CONTROL OF AIR POLLUTION FROM NITROGEN COMPOUNDS
Subchapter C - COMBUSTION CONTROL AT MAJOR UTILITY ELECTRIC GENERATION SOURCES IN OZONE NONATTAINMENT AREAS
Division 3 - HOUSTON-GALVESTON-BRAZORIA OZONE NONATTAINMENT AREA UTILITY ELECTRIC GENERATION SOURCES
Section 117.1240 - Continuous Demonstration of Compliance
Current through Reg. 50, No. 13; March 28, 2025
(a) Nitrogen oxides (NOX) monitoring. The owner or operator of each unit subject to this division (relating to Houston-Galveston-Brazoria Ozone Nonattainment Area Utility Electric Generation Sources), shall install, calibrate, maintain, and operate a continuous emissions monitoring system (CEMS), predictive emissions monitoring system (PEMS), or other system specified in this section to measure NOX on an individual basis. Each NOX monitor (CEMS or PEMS) is subject to the relative accuracy test audit relative accuracy requirements of 40 Code of Federal Regulations (CFR) Part 75, Appendix B, Figure 2, except the concentration options (parts per million by volume (ppmv) and pounds per million British thermal units) therein do not apply. Each NOX monitor must meet either the relative accuracy percent requirement of 40 CFR Part 75, Appendix B, Figure 2, or an alternative relative accuracy requirement of ± 2.0 ppmv from the reference method mean value.
(b) Carbon monoxide (CO) monitoring. The owner or operator shall monitor CO exhaust emissions from each unit subject to this division using one or more of the methods in § 117.8120 of this title (relating to Carbon Monoxide (CO) Monitoring).
(c) Ammonia monitoring requirements. The owner or operator of units that are subject to the ammonia emission specification in § 117.1210(b)(2) of this title (relating to Emission Specifications for Attainment Demonstration) shall comply with the ammonia monitoring requirements of § 117.8130 of this title (relating to Ammonia Monitoring).
(d) CEMS requirements.
(e) Acid rain peaking units. The owner or operator of each peaking unit as defined in 40 CFR §72.2, may:
(f) Auxiliary steam boilers. The owner or operator of each auxiliary steam boiler as defined in § 117.10 of this title (relating to Definitions) shall:
(g) PEMS requirements. The owner or operator of any PEMS used to meet a pollutant monitoring requirement of this section shall comply with the following. The required PEMS and fuel flow meters must be used to demonstrate continuous compliance with the requirements of this division.
(h) Stationary gas turbine monitoring for NO X RACT. The owner or operator of each stationary gas turbine subject to the emission specifications of § 117.1205 of this title, instead of monitoring emissions in accordance with the monitoring requirements of 40 CFR Part 75, may comply with the following monitoring requirements:
(i) Totalizing fuel flow meters. The owner or operator of units listed in this subsection shall install, calibrate, maintain, and operate totalizing fuel flow meters to individually and continuously measure the gas and liquid fuel usage. A computer that collects, sums, and stores electronic data from continuous fuel flow meters is an acceptable totalizer. In lieu of installing a totalizing fuel flow meter on a unit, an owner or operator may opt to assume fuel consumption at maximum design fuel flow rates during hours of the unit's operation. The units are:
(j) Run time meters. The owner or operator of any stationary gas turbine using the exemption of § 117.1203(a)(3) or (b) of this title shall record the operating time with an elapsed run time meter approved by the executive director.
(k) Loss of exemption. The owner or operator of any unit claimed exempt from the emission specifications of this division using the low annual capacity factor exemptions of § 117.1203(a)(2) or (3) of this title, shall notify the executive director within seven days if the applicable limit is exceeded.
(l) Data used for compliance.
(m) Enforcement of NOX RACT limits. If compliance with § 117.1205 of this title is selected, no unit subject to § 117.1205 of this title may be operated at an emission rate higher than that allowed by the emission specifications of § 117.1205 of this title. If compliance with § 117.1215 of this title (relating to Alternative System-Wide Emission Specifications) is selected, no unit subject to § 117.1215 of this title may be operated at an emission rate higher than that approved by the executive director in accordance with § 117.1252(b) of this title (relating to Final Control Plan Procedures for Reasonably Available Control Technology).
(n) Testing requirements. The owner or operator of units subject to § 117.1210(a) of this title must test the units as specified in § 117.1235 of this title in accordance with the schedule specified in § 117.9120(2) of this title (relating to Compliance Schedule for Houston-Galveston-Brazoria Ozone Nonattainment Area Utility Electric Generation Sources).
(o) Emission allowances. The owner or operator of units subject to § 117.1210(a) of this title shall comply with the following.