Texas Administrative Code
Title 30 - ENVIRONMENTAL QUALITY
Part 1 - TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
Chapter 115 - CONTROL OF AIR POLLUTION FROM VOLATILE ORGANIC COMPOUNDS
Subchapter C - VOLATILE ORGANIC COMPOUND TRANSFER OPERATIONS
Division 4 - CONTROL OF VEHICLE REFUELING EMISSIONS (STAGE II) AT MOTOR VEHICLE FUEL DISPENSING FACILITIES
Section 115.244 - Inspection Requirements

Universal Citation: 30 TX Admin Code § 115.244

Current through Reg. 50, No. 13; March 28, 2025

The owner or operator of any gasoline dispensing facility subject to the control requirements of this division shall conduct daily inspections of the Stage II vapor recovery system for the defects specified in § 115.242(d)(3) and (4) of this title (relating to Control Requirements) as follows.

(1) For all systems, the daily inspections must include the applicable portions of § 115.242(d)(3)(A) - (F), (H), and (K), and (4) of this title.

(2) For assist systems that use a processor, indicating mechanisms designed by the Stage II vapor recovery equipment manufacturer to verify proper operation must be inspected daily. Examples of these indicating mechanisms include flame detection sensors, remote (from the processor) visual or audible displays indicating system operation, or other means as described in the applicable Executive Order for the system.

(3) For all systems, the components listed in § 115.242(d)(3)(J) of this title must be inspected at least monthly.

(4) For all systems, the components listed in § 115.242(d)(3)(G) of this title must be inspected at least annually.

Disclaimer: These regulations may not be the most recent version. Texas may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.