Texas Administrative Code
Title 30 - ENVIRONMENTAL QUALITY
Part 1 - TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
Chapter 113 - STANDARDS OF PERFORMANCE FOR HAZARDOUS AIR POLLUTANTS AND FOR DESIGNATED FACILITIES AND POLLUTANTS
Subchapter D - DESIGNATED FACILITIES AND POLLUTANTS
Division 3 - EMISSION GUIDELINES AND COMPLIANCE TIMES FOR SMALL MUNICIPAL WASTE COMBUSTION UNITS CONSTRUCTED ON OR BEFORE AUGUST 30, 1999
Section 113.2149 - What is the minimum amount of monitoring data I must collect with my continuous parameter monitoring systems and is the data collection requirement enforceable?
Current through Reg. 50, No. 13; March 28, 2025
(a) Where continuous parameter monitoring systems are used, obtain 1-hour arithmetic averages for three parameters:
(b) Obtain at least two data points per hour in order to calculate a valid 1-hour arithmetic average.
(c) Obtain valid 1-hour averages for at least 75 percent of the operating hours per day for 90 percent of the operating days per calendar quarter. An operating day is any day the unit combusts any municipal solid waste or refuse-derived fuel.
(d) If you do not obtain the minimum data required in subsections (a) through (c) of this section, you are in violation of the data collection requirement, and you must notify the executive director according to § 113.2161(5) of this title (relating to What must I include in my annual report?).