Texas Administrative Code
Title 26 - HEALTH AND HUMAN SERVICES
Part 1 - HEALTH AND HUMAN SERVICES COMMISSION
Chapter 559 - DAY ACTIVITY AND HEALTH SERVICES REQUIREMENTS
Subchapter C - FACILITY CONSTRUCTION PROCEDURES
Section 559.42 - Safety
Universal Citation: 26 TX Admin Code § 559.42
Current through Reg. 49, No. 52; December 27, 2024
(a) Environmental safety.
(1) The physical plant safety
requirements are designed to provide safety to the clients, participants, or
adult individuals receiving day care.
(2) The facility must conform to all
applicable state laws and local ordinances pertaining to occupancy. When these
laws, codes, and ordinances are more stringent than the standards in this
section, the more stringent requirements govern. If state laws or local codes
or ordinances conflict with the requirements of these standards, DADS'
Regulatory Services Licensing and Credentialing Section will be so informed so
that these conflicts may be legally resolved.
(3) The facility must meet the provisions and
requirements concerning accessibility for individuals with disabilities in the
following laws and regulations: the Americans with Disabilities Act (ADA) of
1990 (Title 42, United States Code, Chapter 126); Title 28, Code of Federal
Regulations, Part 35; Texas Government Code, Chapter 469, Elimination of
Architectural Barriers; and 16 TAC, Chapter 68, Elimination of Architectural
Barriers. Plans for new construction, substantial renovations, modifications,
and alterations must be submitted to the Texas Department of Licensing and
Regulation (Attn: Elimination of Architectural Barriers Program) for
accessibility approval under Texas Government Code, Chapter 469. At least 50%
of the client restrooms must be in accordance with ADA. Exception: Facilities
licensed for 45 or fewer persons may provide one unisex restroom in accordance
with accessibility requirements.
(4) DADS' jurisdiction extends beyond the
licensed facility when the licensed area is only a part of a building or floor
that is not fire-separated in accordance with the Life Safety Code, NFPA 101,
2000 edition, §16.1.2, New Day-Care Centers, or Life Safety Code, NFPA
101, 2000 edition, §17.1.2, Existing Day-Care Centers with Mixed
Occupancies.
(b) Life Safety Code, NFPA 101, 2000 edition.
(1) The
principles of the Life Safety Code, NFPA 101, 2000 edition, under Chapter 16
for new day-care centers or Chapter 17 for existing day-care centers, and
operating features under §16.7 or §17.7, must be used in establishing
life safety requirements for adult day care facilities, with the interpretation
and exceptions as listed in paragraphs (2) and (3) of this subsection. Chapter
16 of the Life Safety Code, NFPA 101, 2000 edition, is applicable to new
construction, conversions of existing unlicensed buildings, remodeling, and
additions conducted after April 1, 2007. Chapter 17 of the Life Safety Code,
NFPA 101, 2000 edition, is applicable to existing adult day-care facilities
licensed before April 1, 2007. Life safety features and equipment installed in
existing buildings that are now in excess of what is required by the Life
Safety Code, NFPA 101, 2000 edition, must continue to be maintained or may be
completely removed if prior written approval is obtained from DADS.
(2) Interpretations of the Life Safety Code,
NFPA 101, 2000 edition, chapters 16 and 17, are as follows:
(A) The principles of chapters 16 and 17
apply to any size facility requiring licensing with four or more clients or
participants.
(B) The principles of
§16.1.4.2 and §17.1.4.2 relating to a building or portion thereof
used less than 24 hours per day to house more than three adults requiring care,
maintenance, and supervision by other than a relative apply to all facilities
requiring licensing. A client must be ambulatory or semi-ambulatory and must
not be bedridden. A client must not exhibit behavior that is harmful to the
client or others.
(C) The manual
fire alarm system and automatic smoke detection system must be installed in
accordance with NFPA 72 National Fire Alarm Code series and state fire marshal
licensing requirements.
(D) The
facility must have a program to inspect, test, and maintain the fire alarm
system and must execute the program at least once every six months.
(i) The facility must contract with a company
that is registered by the State Fire Marshal's Office to execute the
program.
(ii) The person who
performs a service under the contract must be licensed by the State Fire
Marshal's Office to perform the service and must complete, sign, and date an
inspection form similar to the inspection and testing form in NFPA 72 for a
service provided under the contract.
(iii) The facility must ensure fire alarm
system components that require visual inspection are visually inspected in
accordance with NFPA 72.
(iv) The
facility must ensure fire alarm system components that require testing are
tested in accordance with the NFPA 72.
(v) The facility must ensure fire alarm
system components that require maintenance are maintained in accordance with
NFPA 72.
(vi) The facility must
ensure smoke dampers are inspected and tested in accordance with NFPA 101, 2000
edition.
(vii) The facility must
maintain onsite documentation of compliance with this subsection and have
available for examination by DADS, operation and maintenance manuals, and a
written sequence of operation.
(E) If the facility has a complete NFPA 13
system, the facility must have a program to inspect, test, and maintain the
sprinkler system and must execute the program at least once every six months.
(i) The facility must contract with a company
that is registered by the State Fire Marshal's Office to execute the
program.
(ii) The person who
performs a service under the contract must be licensed by the State Fire
Marshal's Office to perform the service and must complete, sign, and date an
inspection form similar to the inspection and testing form in NFPA 25 for a
service provided under the contract.
(iii) The facility must ensure sprinkler
system components that require visual inspection are visually inspected in
accordance with NFPA 13 and 25.
(iv) The facility must ensure sprinkler
system components that required testing are tested in accordance with the NFPA
13 and 25.
(v) The facility must
ensure sprinkler system components that require maintenance are maintained in
accordance with NFPA 13 and 25.
(vi) The facility must ensure that individual
sprinkler heads are inspected and maintained in accordance with NFPA 13 and
25.
(vii) The facility must
maintain onsite documentation of compliance with this subsection and have
available for examination by DADS as built drawings, operation and maintenance
manuals, and a written sequence of operation.
(F) All facilities must follow the Life
Safety Code, NFPA 101, 2000 edition, chapters 16 or 17, including the
following:
(i) If a center is located in a
building containing mixed occupancies, the occupancies must be separated by
one-hour fire barriers.
(ii) Each
floor occupied by clients must have access to two remote exits in accordance
with Chapter 7, Means of Egress.
(I) Doors in
the means of egress must be equipped with hardware that opens with a single
motion.
(II) Doors must swing in
the direction of egress for occupant loads greater than 50 occupants.
(iii) Every room or space normally
subject to client occupancy, other than bathrooms or any room with attended
individual clients, must have at least one outside window for emergency rescue
or ventilation. Such window must be able to be opened from the inside without
the use of tools and provide a clear opening of not less than 20 inches in
width, 24 inches in height, and 5.7 sq. ft. (821 sq. in.) in area (minimum
width of 20 inches by 41.2 inches high and minimum height of 24 inches by 34.2
inches wide). The bottom of the opening must be not more than 44 inches (112
cm.) above the floor. In rooms located greater than three stories above grade,
the openable clear height, width, and area of the window may be modified to the
dimensions necessary for ventilation. Exceptions are:
(I) buildings protected throughout by an
approved, supervised automatic sprinkler system in accordance with
§9.7;
(II) rooms or spaces
with a door leading directly to the outside of the building; or
(III) in existing facilities, rooms smaller
than 250 square feet.
(iv) Interior finish in stairways, corridors,
and lobbies must be Class A. All other walls and ceilings must be Class A or
Class B interior finish in accordance with Life Safety Code, NFPA 101, 2000
edition, §10.2.3. Flame spread is the rate of fire travel along the
surface of a material. (This is different from other requirements for
time-rated "burn through" resistance ratings such as one-hour rated.) Flame
spread ratings are Class A (0-25), Class B (26-75), and Class C
(76-200).
(v) Floor finish
materials within corridors and exits must be Class I or Class II in accordance
with §10.2.7 in new construction or new installations of flooring.
Replacement or newly installed floor finish materials must be Class I or II.
Existing floor finish materials in good condition may remain in use in
accordance with §10.2.
(vi) A
smoke detection system must be installed in accordance with §9.6 with
placement of detectors in each story in front of the doors to the stairways and
in the corridors of all floors occupied by the day-care occupancy. Detectors
also must be installed in lounges, recreation areas, dining areas, and sleeping
rooms in the center
(vii) Fire
department notification must be accomplished in accordance with §9.6.4,
except in day-care centers with not more than 100 clients.
(3) Exceptions to the Life Safety
Code, NFPA 101, 2000 edition, chapters 16 or 17, are as follows.
(A) All required smoke detectors must be
powered by the facility electrical system and be interconnected with the fire
alarm system.
(B) Reference to
apartment buildings in §16.1.2 or §17.1.2 must be deleted. Any floor
above or below the floor of exit discharge that is used by semi-ambulatory
clients, or those whose disability prevents them from taking appropriate action
for self-preservation in emergencies, must be provided with smoke
compartmentation.
(C) Emergency
lighting is not required for means of egress if the facility operation is
during daylight hours and if natural light, direct or borrowed, is provided so
that the means of egress is usable in emergencies.
(D) Special protective electrical receptacle
covers are not required.
(E) NFPA
96, Standard for Ventilation Control and Fire Protection of Commercial Cooking
Operations, is not applicable if the facility has residential-type cooking
equipment.
(F) Public corridors
must not be used for return or supply air systems.
(G) Residential-type heating units or heating
units designed for attic installations must not be considered to be units
requiring furnace room construction as specified under §16.3.2.1 or
§17.3.2.1.
(H) New additions
or remodeling must be as required for new construction in accordance with
paragraph (4) of this subsection.
(I) Sprinkler system for a janitor's closet
as specified under §16.3.2.1 or §17.3.2.1 is not required unless the
building has a complete NFPA 13 system.
(4) For new construction, DADS requires
conformance to the following codes, except that DADS may accept other
nationally recognized codes that are locally enforced.
(A) If the municipality has a building code
and a plumbing code, then those codes govern in those areas of construction.
Where local codes or ordinances are applicable, the most restrictive parts
concerning the same subject item apply unless otherwise determined by the
authority having jurisdiction for local codes and the licensing
agency.
(B) In the absence of local
municipal codes or ordinances, nationally recognized codes must be used, such
as the International Building Code and the compatible International Codes
published by the International Code Council. These nationally recognized codes,
when used, must all be publications of the same group or organization to assure
the intended continuity.
(C)
Heating, ventilating, and air-conditioning (HVAC) systems must be designed and
installed in accordance with NFPA 90A and NFPA 90B, as applicable, and the
American Society of Heating, Refrigerating, and Air-Conditioning Engineers
(ASHRAE), except as may be modified in this subchapter. Buildings required to
meet NFPA 90A must have automatic shutdown upon initiation of the fire alarm
system, in accordance with NFPA 90A, §4.4.
(D) Electrical and illumination systems must
be designed and installed in accordance with NFPA 70 and the Lighting
Handbook of the Illuminating Engineering Society (IES) of North
America, except as may be modified in this subchapter.
(i) Minimum illumination must be 20 foot
candles in the toilets, bathing, and general use areas, such as living areas,
dining areas, corridors, and lobbies.
(ii) Minimum illumination must be 50 foot
candles in the kitchen, medication or food preparation areas, and activity
areas for handicrafts or reading.
(5) An existing building either occupied as
an adult day care facility at the time of initial inspection by DADS, or
converted to occupancy as an adult day care facility, must meet all local
requirements pertaining to the building for that occupancy. DADS may require
the facility sponsor or licensee to submit evidence that local requirements are
satisfied.
(6) Adult day care
facilities must be of recognized permanent type construction as distinguished
from movable buildings or construction. Buildings must be structurally sound
with regard to actual or expected dead, live, and wind loads. DADS may require
submission of evidence to this effect. Foundations must be permanent,
structurally sound for local soil conditions, and in good repair. A letter from
a registered professional engineer may be required as validation of a permanent
and structurally sound foundation.
(7) The walking surface in a facility and at
the exit discharge must be consistent, nominally level, and without abrupt
changes in elevation, trip hazards, or gaps. Floor surfaces may be on different
elevations if connected with ramps or steps in accordance with the Life Safety
Code, NFPA 101, 2000 edition, means of egress chapter.
(8) DADS will consider a written request from
the facility for a waiver of requirements which, if strictly applied, would
clearly be impractical in DADS' judgment for existing buildings and structures
that have been converted to adult day care occupancy. Any of these
modifications will be allowed only to the extent that reasonable life safety
against the hazards of fire, explosion, structural, or other building failure
and panic are provided and maintained.
(c) Personal safety.
(1) Fire safety.
(A) The facility must maintain an onsite copy
of the annual fire marshal inspection report by the local fire
marshal.
(B) Storage items must be
neatly arranged and placed in the facility to minimize fire hazard. Gasoline,
volatile materials, paint, and similar products must not be stored in the
building housing clients unless approved by the local fire marshal.
Accumulations of extraneous material and refuse are not permitted in the
facility.
(C) The building must be
kept in good repair.
(D) The
facility's electrical, mechanical, heating, and cooling systems must be
maintained in a safe manner and in working order. DADS may require the facility
sponsor or licensee to submit evidence to this effect, consisting of a report
from the fire marshal or city or county building official having jurisdiction
or a report from a registered professional engineer.
(E) Electrical appliances, devices, and lamps
used in the facility must be used in a manner that prevents overloaded
circuits.
(F) If the facility uses
extension cords in excess of six feet, they must be shielded or
protected.
(G) Smoking regulations
must be established and enforced by the facility and conspicuously posted in
the facility.
(i) All smoking must be
supervised.
(ii) The facility must
prohibit smoking in any room, ward, or compartment where flammable liquids,
combustible gas, or oxygen are used or stored and in any other hazardous
location. The facility must post a "No Smoking" sign in these areas.
(iii) Ashtrays of noncombustible material and
safe design must be provided in all areas where smoking is permitted.
(iv) Metal containers of substantial gauge or
any UL- or FM-approved containers with self- closing cover devices into which
ashtrays can be emptied must be provided in all areas where smoking is
permitted.
(H) The
facility must have an emergency fire lane for access of fire apparatus if
required by local authorities.
(I)
An initial pressure test of facility gas lines from the meter must be provided.
Additional pressure tests are required when the facility has major renovations
or additions during which the gas service is interrupted. Testing must be
performed by a person licensed with the State Board of Plumbing
Examiners.
(J) The facility must
have all gas heating systems checked for proper operation and safety before the
heating season by a person licensed by the Texas Department of Licensing and
Regulation to perform maintenance work on gas-fired equipment. Any
unsatisfactory conditions must be corrected promptly.
(K) Curtains or draperies in public spaces
and individual rooms in which smoking is allowed must be flame
retardant.
(L) Portable fire
extinguishers of appropriate type and placed in the appropriate location must
be provided by the facility in accordance with NFPA 10.
(M) The facility must inspect and maintain
portable fire extinguishers.
(i) Portable
fire extinguishers must be visually inspected monthly by facility staff.
Facility staff conducting the monthly visual inspection must assure portable
fire extinguishers are protected from damage, kept on their mounting brackets
or in cabinets at all times, and kept in proper condition and working
order.
(ii) Portable fire
extinguishers must be inspected and maintained at least once every 12 months in
accordance with NFPA 10 by a person licensed by the State Fire Marshal's
office, to include hydrostatic testing as recommended by the
manufacturer.
(iii) A record of all
fire extinguisher inspections and maintenance performed must be kept onsite by
the facility.
(N)
Garbage, waste, or trash containers provided for kitchens, janitor closets,
laundries, mechanical or boiler rooms, general storage, and similar places must
be made of metal or any UL- or FM-approved material, having a close fitting
cover. Disposable plastic liners may be used in these containers for
sanitation.
(2) General
requirements.
(A) All exterior site
conditions must be designed, constructed, and maintained in the interest of
clients' safety. Newly constructed ramps must not exceed 1:12 slope. Ramps,
walks, and steps must be of slip-resistive texture and be smooth and uniform,
without irregularities. Guard rails, fences, and hand rails must be provided as
required.
(B) All stairways must
have substantial hand rails properly secured.
(C) Tubs or showers for client use must have
non-slip bottoms or floor surfaces, either built in or applied to the
surface.
(D) Elevators for client
use must be in safe operating condition.
(E) An adequate supply of hot water must be
provided. The hot water system connected to all client-use fixtures must
deliver warm water no hotter than 120 degrees Fahrenheit at the fixture. Hot
water for other sanitary usages must be provided at the temperatures required
for the appliance or fixture served, or for the operation involved.
(F) There must be no occupancies or
activities adversely affecting the safety of the clients in the buildings or on
the premises of the facility.
(G)
Licensure capacity will be calculated at 40 square feet per client. This space
may not include the kitchen/food service area, rest rooms, bath areas, office,
corridors, stairways, storage areas, and outdoor space. Facilities licensed
before October 1, 2000, will be allowed to meet the requirements in effect
before October 1, 2000, of 35/50 square feet for ambulatory and semi-
ambulatory clients. If a facility licensed before October 1, 2000, chooses to
increase its capacity, changes ownership, or relocates, the facility will be
required to meet the current standards for usable space, outdoor area, and
rooms for privacy.
(H) An office
area must be provided in a central location to record and maintain files for
each client.
(I) An area for rest,
other than the treatment and/or exam room, must be provided with a sufficient
number of reclining lounge chairs or beds to accommodate the needs of
clients.
(J) The facility must
provide a separate room or rooms with beds and with walls from floor to ceiling
for those clients who prefer privacy. Facilities licensed on or after May 1,
1999, must ensure that the room(s) with beds provide space for a minimum 5% of
the licensed capacity. The usable space in the room(s) must provide not less
than 80 square feet per bed for a one-bed room and not less than 60 square feet
per bed for multiple-bed rooms. A bedroom shall be not less than eight feet in
its smallest dimension, unless otherwise approved by DADS.
(K) The facility must have at least one room
available as a treatment or examination room for use by the nursing staff or
the client's physician. The client may not be treated or examined in an area
other than the treatment room.
(L)
The facility must have a safe, secure, and suitable outdoor recreation or
relaxation area for clients. This area must be connected to, be a part of, be
controlled by, and be directly accessible from the facility. This area must be
enclosed by a wall or a fence or located in a courtyard and supervised by staff
to prevent wandering and large enough to conduct outdoor activities. A chain-
link fence must provide protection on top to prevent injury from wire points.
This area must be suitably furnished. A minimum of 20% of the required outdoor
space must be shaded. The required outdoor space for facilities licensed on or
after May 1, 1999 is:
(i) 400 square feet for
facilities up to 59 clients;
(ii)
600 square feet for facilities up to 99 clients; and
(iii) 800 square feet for facilities with 100
or more clients.
Disclaimer: These regulations may not be the most recent version. Texas may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.