Current through Reg. 49, No. 38; September 20, 2024
(a) Resident bedrooms. Each resident bedroom
must meet the following requirements:
(1) The
maximum room capacity must be two residents.
(2) Minimum bedroom area, excluding toilet
rooms, closets, lockers, wardrobes, alcoves, or vestibules, must be 100 square
feet in single occupancy rooms and 80 square feet per bed in multi-bed
rooms.
(3) The minimum allowable
room dimension is ten feet. The room must be designed to provide at least 36
inches between beds and 24 inches between any bed and the adjacent
wall.
(4) Each room must have at
least one operable outside window arranged and located so that it can be easily
opened from the inside without the use of tools or keys. The maximum allowable
sill height must not exceed 36 inches above the floor. All operable windows
must have insect screens. The minimum area of window in each bedroom must equal
at least 16 square feet or 8.0% of the gross floor area of the room, whichever
is larger. Operable window sections may be restricted to not more than six nor
less than four inches for security or safety reasons.
(5) Each room must have general lighting,
wall-mounted bed reading lights, and night lighting. The night light must be
switched just inside the entrance to each resident room with a silent type
switch, must be a recessed wall mounted fixture just inside the entry door to
the room and must not be obstructed by the door or furniture, unless otherwise
approved by HHSC. The light providing general illumination must be switchable
at the door of the resident room for use of staff and residents. A durable
non-glare reading light with an opaque front panel securely anchored to the
wall, integrally wired, must be provided above each resident bed. The switch
for this reading light must be within reach of a resident in the bed.
(6) The minimum number of power receptacles
at a resident bed location shall be determined based on the risk assessment
required by NFPA 99 and § 554.300(i) of this subchapter (relating to
General Requirements), as follows:
(A) All
receptacles must be listed and identified as "hospital grade";
(B) Four of the required receptacles must be
provided beside the head of each bed;
(C) No fewer than eight receptacles must be
provided within the patient care vicinity, as defined in NFPA 99;
(D) If the failure of patient-care-related
electrical equipment is likely to cause major injury or death to a resident, no
fewer than fourteen receptacles must be provided within the patient care
vicinity.
(E) Additional
receptacles, beyond the minimum quantities above, must be provided to ensure
the electrical needs of all residents living in the bedroom are met, including
power for TV, radio, razors, hairdryers, clocks, or as required by NFPA 99 and
NFPA 70.
(7) Each
resident bedroom must have direct access to a bathroom without entering the
general corridor area. The bathroom must serve no more than one resident room
and must include, at least, a lavatory and toilet.
(8) Each resident must have a bed with a
comfortable mattress, a bedside stand with at least two enclosed storage
spaces, a dresser, and closet or wardrobe space providing privacy for clothing
and personal belongings. Private clothes storage space must provide at least 22
inches of lineal hanging space per bed and have closable doors. Chairs and
space must be provided for use by residents and visitors.
(9) Each room must open onto an exit corridor
and must be arranged for convenient resident access to dining, living, and
bathing areas. To ensure a direct view from nurses' stations, resident room
doors must not be recessed into the corridor wall more than four feet. Alcoves
must meet applicable accessibility standards for a front approach to the door,
and handrails must be provided in the alcove. If an alcove exceeds four feet in
depth, it is a corridor and must meet all requirements for corridors, including
direct view from a nurses' station, minimum width of the corridor, and
provisions for handrails.
(10)
Visual privacy, such as cubicle curtains, must be available for each resident
in multi-bed bedrooms. Design for privacy must not restrict resident access to
the entry, lavatory, or toilet, nor may it restrict bed evacuation or obstruct
sprinkler flow coverage.
(11) At
least one noncombustible wastebasket must be provided in each
bedroom.
(12) See the requirements
in § 554.361(d)(4) of this subchapter (relating to Electrical Requirements
for New Facilities) for nurse call systems.
(13) Bedrooms must be identified with a
raised or recessed unique number placed on or near the door. Refer to TAS for
information about signs.
(14) Locks
on bedroom doors are permitted when they meet definite resident needs.
(A) Situations in which locks may be
necessary include the following:
(i) married
couples whose rights of privacy could be infringed upon unless bedroom door
locks are permitted; and
(ii)
residents for whom the attending physician wants bedroom door locks to enhance
the residents' sense of security.
(B) In situations such as those listed in
subparagraph (A) of this paragraph, the following guidelines must be met:
(i) bedroom door locks must be of the type
which the occupant can unlock at will from inside the room;
(ii) all bedroom door locks must be of the
type which can be unlocked from the corridor side;
(iii) attendants must carry keys which will
permit ready access to the locked bedrooms when entrance becomes
necessary;
(iv) locking of bedroom
doors by residents for privacy or security will not be permitted except when
specifically included in the attending physician's written orders or authorized
by the nursing facility administrator.
(15) Vacant bedrooms must not be used for
hazardous activities or hazardous storage, unless specifically approved by HHSC
in writing.
(b) Nursing
service areas. A nursing service area includes a nurses' station and other
areas described in this subsection and must be located in or readily available
to each nursing unit. The size and disposition of each service area will depend
upon the number and types of beds to be served. Each service area may be
arranged and located to serve more than one nursing unit, but at least one
service area must be provided on each nursing floor. The maximum allowable
distance from a resident room door to a nurses' station is 150 feet. The
following requirements are applicable to services areas:
(1) Nurses' stations must be provided with
space for nurses' charting, doctors' charting, and storage for administrative
supplies. Nurses' stations must be located to provide a direct view of resident
corridors. A nurses' station has a direct view of a resident corridor if a
person can see down the corridor from a point within 24 inches of the outside
of the nurses' station counter or wall. When a nurses' station does not provide
a direct view of a resident corridor, an auxiliary station complying with the
following guidelines must be provided.
(A)
The auxiliary station must be staffed by nursing personnel during all shifts.
(i) More than one auxiliary station may be
assigned to a designated nurses' station, regardless of the distance between
stations.
(ii) The nurse call
system for resident corridors monitored by the auxiliary station must report to
the auxiliary station.
(iii) Each
auxiliary station must meet the emergency electrical requirements for a nurse's
station, including electrical receptacles and emergency lighting.
(iv) If a required auxiliary station does not
already exist and the facility must establish a new auxiliary station, all
applicable standards, particularly those pertaining to the physical plant and
NFPA 101, must be observed.
(B) In addition to the required normal and
emergency illumination, the facility must keep on hand and readily available to
night staff no less than one working flashlight at each nurses'
station.
(2) Lounge and
toilet room must be provided for nursing staff.
(3) Lockers or security compartments must be
provided for the safekeeping of personal effects of staff. These must be
located convenient to the duty station of personnel or in a central
location.
(4) A clean utility room
must contain a work counter, sink with high-neck faucet with lever controls,
and storage facilities and must be part of a system for storage and
distribution of clean and sterile supply materials.
(5) A soiled utility room must contain a
water closet or equivalent flushing rim fixture, a sink large enough to
submerge a bedpan with spray hose and high-neck faucet with lever controls,
work counter, waste receptacle, and linen receptacle. A soiled utility room
must be part of a system for collection and cleaning or disposal of soiled
utensils or materials. A separate hand-washing sink must be provided if the
bedpan disinfecting sink cannot normally be used for hand-washing.
(6) Provision must be made for convenient and
prompt 24-hour distribution of medication to residents. The medication
preparation room must be under the nursing staff's visual control and contain a
work counter, refrigerator, sink with hot and cold water, and locked storage
for biologicals and drugs and must have a minimum area of 50 square feet. The
minimum dimension allowed is five feet six inches. An appropriate air supply
must be provided to maintain adequate temperature and ventilation for safe
storage of medications. For purposes of storage of unrefrigerated medications,
the room temperature must be maintained between 59 degrees and 86 degrees
Fahrenheit.
(7) Provision must be
made for separate closets or room for clean linens. Corridors must not be used
for folding or cart storage. Storage rooms must be located and distributed in
the building for efficient access to bedrooms.
(8) A soiled linen rooms must meet the
requirements in subsection (l)(2)(A) of this section.
(9) A nourishment station is required and
must contain a sink equipped for hand-washing, equipment for serving
nourishment between scheduled meals, refrigerator, and storage cabinets. Ice
for residents' service and treatment must be provided only by icemaker units.
This station may be furnished in a clean utility room.
(10) An equipment storage room must be
provided for equipment such as intravenous stands, inhalators, air mattresses,
and walkers.
(11) Parking spaces
for stretchers and wheelchairs must be located out of the path of normal
traffic.
(c) Residents'
bathing and toilet facilities. The following requirements are applicable to
bathing and toilet facilities:
(1) Bathtubs
or showers must be provided at the rate of one for each 20 beds which are not
otherwise served by bathing facilities within residents' rooms. At least one
bathing unit must be provided in each nursing unit. Each tub or shower must be
in an individual room or enclosure which provides space for the private use of
the bathing fixture, for drying and dressing, including an accessible dressing
bench, and for a wheelchair and an attendant. Each general-use bathing room
must be provided with at least one water closet in a stall, room, or area for
privacy, and one lavatory. A bathing room must be located conveniently to the
bedroom area it serves and must not be more than 100 feet from the farthest
bedroom.
(2) At least 50% of
bathrooms and toilet rooms, fixtures, and accessories must be designed and
provided to meet criteria under the Americans with Disabilities Act for
individuals with disabilities, unless otherwise approved by HHSC.
(3) All rooms containing bathtubs, sitz
baths, showers, and water closets, used by residents must be equipped with
doors and hardware that permits access from the outside in any
emergency.
(4) Bathing areas must
be provided with safe and effective auxiliary or supplementary heating. Bathing
areas must be free of drafts and must have adequate exhaust ducted to the
outside to minimize excess moisture retention and resulting mold and mildew
problems.
(5) Tubs and showers must
be provided with slip-proof bottoms.
(6) Lavatories and hand-washing facilities
must be securely anchored to withstand an applied downward load of not less
than 250 pounds on the front of the fixtures.
(7) Provision must be made for sanitary hand
drying and toothbrush storage at lavatories. There must be paper towel
dispensers or separate towel racks and separate toothbrush holders.
(8) Mirrors must be arranged for convenient
use by residents in wheelchairs as well as by residents in a standing position,
and the minimum size must be 15 inches in width by 30 inches in height, or tilt
type.
(9) Rooms with toilets must
be provided with effective forced air exhaust ducted to the exterior to remove
odors. Ducted manifold systems are recommended.
(10) Floors, walls, and ceilings must have
nonabsorbent surfaces, be smooth, and be easily cleanable.
(d) Disposal facilities. A policy and
procedure for the safe and sanitary disposal of special waste must be provided.
Space and facilities must be provided for the sanitary storage of waste by
incineration, mechanical destruction, compaction, containerization, removal, or
by a combination of these techniques.
(e) Resident living areas. The following
requirements are applicable to resident living areas:
(1) Social-diversional spaces such as living
rooms, dayrooms, lounges, and sunrooms, must be provided on a sliding scale as
follows:
Attached
Graphic
(2) If a
required way of exit, or a service way, is through a living or dining area, a
pathway equal to the corridor width must be deducted for calculation purposes
and discounted from that area. These exit pathways must be kept clear of
obstructions.
(3) Each resident
living room and dining room must have at least one outside window. The window
area must be equal to at least 8.0% of the total room floor area. Sky-lighting
may be used to fulfill one-half of the 8.0% minimum area.
(4) Open or enclosed seating space must be
provided within view of the main nurses' station that will allow furniture or
wheelchair parking that does not obstruct the corridor way of egress.
(f) Dining space. Dining space
must be adequate for the number of residents served, but no less than ten
square feet per resident bed.
(g)
Dietary facilities. The following requirements are applicable to dietary
facilities:
(1) A main or dietary kitchen
must be as follows:
(A) A kitchen will be
evaluated on the basis of its performance in the sanitary and efficient
preparation and serving of meals to residents. Consideration will be given to
planning for the type of meals served, the overall building design, the food
service equipment, the arrangement, and the work flow involved in the
preparation and delivery of food. Plans must include a large-scale detailed
kitchen layout designed by a registered or licensed dietitian or architect
having knowledge in the design of food service operations.
(B) Kitchens must be designed so that room
temperature at summertime peak load will not exceed a temperature of 85 degrees
Fahrenheit measured at the five-foot level. The amount of supply air must take
into account the large quantities of air that may be exhausted at the range
hood and dishwashing area.
(C)
Operational equipment must be provided as planned and scheduled by the facility
consultants for preparing and serving meals and for refrigerating and freezing
of perishable foods, as well as equipment in, or adjacent to, the kitchen or
dining area for producing ice.
(D)
Facilities for washing and sanitizing dishes and cooking utensils must be
provided. These facilities must be designed based on the number of meals served
and the method of serving, that is, use of permanent or disposable dishes. The
kitchen must contain a multi-compartment sink large enough to immerse pots and
pans. A mechanical dishwasher is required for washing and sanitizing dishes.
Separation of soiled and clean dish areas must be maintained, including air
flow.
(E) A vegetable preparation
sink must be provided, and it must be separate from the pot sinks.
(F) A supply of hot and cold water must be
provided. Hot water for sanitizing purposes must be 180 degrees Fahrenheit or
the manufacturer's suggested temperature for chemical sanitizers. For
mechanical dishwashers, the temperature measurement is at the
manifold.
(G) A kitchen must be
provided with a hand-washing lavatory in the food preparation area with hot and
cold water, soap, paper towel dispenser, and waste receptacle. The dish room
area must have ready access to a hand-washing lavatory.
(H) Staff rest room facilities with lavatory
must be directly accessible to kitchen staff without traversing resident use
areas. A facility must provide a vestibule so the rest room door does not open
directly into the kitchen.
(I)
Janitorial facilities must be provided exclusively for the kitchen and must be
located in the kitchen area.
(J)
Nonabsorbent smooth finishes or surfaces must be used on kitchen floors, walls,
and ceilings. These surfaces must be capable of being routinely cleaned and
sanitized to maintain a healthful environment. Counter and cabinet surfaces,
inside and outside, must also have smooth, cleanable, relatively nonporous
finishes.
(K) Operable windows must
have insect screens provided.
(L)
Doors between kitchen and dining or serving areas must have a safety glass view
panel.
(M) A garbage can or cart
washing area with drain and hot water must be provided.
(N) Floor drains must be provided in the
kitchen and dishwashing areas.
(O)
Vapor removal from cooking equipment must be designed and installed in
accordance with NFPA 101.
(P)
Grease traps must be provided in compliance with local plumbing code or other
nationally recognized plumbing code.
(2) Food storage areas must be as follows:
(A) Food storage areas must provide for
storage of a seven-day minimum supply of nonperishable foods at all
times.
(B) Shelves must be
adjustable wire type. Walls and floors must have a nonabsorbent finish to
provide a cleanable surface. No foods may be stored on the floor; dollies,
racks, or pallets may be used to elevate foods not stored on
shelving.
(C) Dry food storage must
have an effective venting system to provide for positive air
circulation.
(D) The maximum room
temperature for food storage must not exceed 85 degrees Fahrenheit at any time.
The measurement must be taken at the highest food storage level but not less
than five feet from the floor.
(E)
Food storage areas may be located apart from the food preparation area as long
as there is space adjacent to the kitchen for necessary daily usage.
(3) An auxiliary serving kitchen
not contiguous to a food preparation or serving area must be as follows:
(A) If a service area other than the kitchen
is used to dispense food, it must be designated as a food service area and must
have equipment for maintaining required food temperatures while
serving.
(B) Separate food service
areas must have hand-washing facilities as a part of the food service
area.
(C) Finishes of all surfaces,
except ceilings, must be the same as those required for dietary kitchens or
comparable areas. See paragraph (1)(J) of this subsection.
(h) Administrative and public
areas.
(1) The following elements must be
provided in the public area:
(A) The entrance
must be at grade level, sheltered from the weather, and able to accommodate
wheelchairs. A drive-under canopy must be provided for the protection of
residents or visitors entering or leaving a vehicle. The drive-under canopy may
be a secondary entrance.
(B) The
lobby, which may also be designed to satisfy a portion of the minimum area
required for resident living room space, must include:
(i) storage space for wheelchairs if more
than one is kept available;
(ii) a
reception or information area, which may be adjacent to the lobby if the
location is obvious;
(iii) waiting
space;
(iv) public toilet
facilities for individuals with disabilities, which may be adjacent to the
lobby;
(v) at least one public
access telephone, installed to meet standards under the Americans with
Disabilities Act; and
(vi) a
drinking fountain, which may be provided in a common public area and at least
one of which must be installed to meet standards under the Americans with
Disabilities Act.
(2) The following must be provided in the
administrative area:
(A) General or
individual offices must be provided for business transactions, medical and
financial records, administrative and professional staff, and for private
interviews relating to social service, credit, and admissions.
(B) A multipurpose room must be provided for
conferences, meetings, and health education purposes including facilities for
showing visual aids.
(C) Storage
and work area for office equipment and supplies must be provided and accessible
to the staff using such items.
(3) Toilet facilities for the disabled must
be available in the building.
(i) Physical therapy facilities.
(1) Physical therapy facilities must be
provided if required by the treatment program. The facilities stated in
subparagraph (B) of this paragraph and paragraph (2)(C) - (E) of this
subsection may be planned and arranged for shared use by occupational therapy
residents and staff if the treatment program reflects this sharing concept.
Physical therapy facilities must include the following:
(A) Provision for privacy at each individual
treatment area; hand-washing facilities, one lavatory or sink may serve more
than one cubicle; and facilities for the collection of soiled linen and other
material that may be used in the therapy.
(B) Residents' dressing areas with accessible
benches, showers, lockers, and toilet rooms if the therapy is such that these
would be needed at the area.
(2) Physical therapy facilities may also
include the following:
(A) treatment areas
with space and equipment for the therapies provided;
(B) an exercise area;
(C) storage for clean linen, supplies, and
equipment used in therapy;
(D)
service sink located near therapy area; and
(E) wheelchair and stretcher
storage.
(j)
Occupational therapy facilities. Occupational therapy facilities must be
provided if required by the treatment program.
(1) An activities area with a sink or
lavatory and facilities for collection of waste products prior to disposal must
be provided.
(2) Storage for
supplies and equipment used in the therapy must be provided.
(k) Personal grooming area, such
as a barber or beauty shop. A separate room with appropriate equipment must be
provided for hair care and grooming needs of residents in facilities with over
60 beds.
(l) Laundry and linen
services.
(1) On-site processing must be as
follows:
(A) Because of the high incidence of
fires in laundries, it is highly recommended that the laundry be in a separate
building 20 feet or more from the main building. If the laundry is located
within the main building it must be separated by minimum one-hour fire
resistance-rated construction to structure above, and sprinklered, and must be
located in a remote area away from resident sleeping areas. Access doors must
be from the exterior or interior nonresident use area, such as a service
corridor, that is separated from the resident area.
(B) If linen is to be processed on the site,
the following must be provided:
(i) A soiled
linen receiving, holding, and sorting room with a rinse sink. This area must
have a floor drain and forced exhaust to the exterior which must operate at all
times there is soiled linen being held in the area.
(ii) A laundry processing room with equipment
which can process seven days' worth of laundry within a regularly scheduled
work week. Hand-washing facilities must be provided. The washer area must have:
(I) a floor drain;
(II) storage for laundry supplies;
(III) a clean linen inspection and mending
room or area and a folding area;
(IV) a clean linen storage, issuing, or
holding room or area;
(V) a
janitors' closet containing a floor receptor or service sink and storage space
for housekeeping equipment and supplies; and
(VI) sanitizing and washing facilities and a
storage area for carts.
(C) Soiled and clean operations must be
planned to maintain sanitary flow of functions as well as air flow. If carts
containing soiled linens from resident rooms are not taken directly to the
laundry area, intermediate holding rooms must be provided and located
convenient to resident bedroom areas.
(D) Laundry areas must have adequate air
supply and ventilation for staff comfort without having to rely on opening a
door that is part of the fire wall separation.
(E) Provisions must be made to exhaust heat
from dryers and to separate dryer make-up air from the habitable work areas of
the laundry.
(2) For
off-site linen processing, the following must be provided on the premises:
(A) a soiled linen holding room with adequate
forced exhaust ducted to the exterior;
(B) clean linen receiving, holding,
inspection, sorting or folding, and storage rooms; and
(C) sanitizing facilities and storage area
for carts.
(3)
Resident-use laundry, if provided, must be limited to not more than one
residential type washer and dryer per laundry room. This room must be
classified as a hazardous area according to NFPA 101.
(m) General storage. The following
requirements are applicable to general storage facilities:
(1) A general storage room must be provided
as needed to accommodate the facility's needs. It is recommended that a general
storage area provide at least two square feet per resident bed. This area would
be for items such as extra beds, mattresses, appliances, and other furnishing
and supplies.
(2) Storage space
with provisions for locking and security control must be provided for
residents' personal effects which are not kept in their rooms.
(n) Janitors' closet. In addition
to the janitors' closet called for in certain departments, a sufficient number
of janitors' closets must be provided throughout the facility to maintain a
clean and sanitary environment. These must contain a floor receptor or service
sink and storage space for housekeeping equipment and supplies.
(o) Maintenance, engineering service, and
equipment areas. Space and facilities for adequate preventive maintenance and
repair service must be provided. The following spaces are needed and it is
suggested that these be part of a separate laundry building or area:
(1) A storage area for building and equipment
maintenance supplies, tools, and parts must be provided.
(2) A space for storage of yard maintenance
equipment and supplies, including flammable liquids bulk storage, must be
provided separate from the resident-occupied facility.
(3) A maintenance and repair workshop of at
least 120 square feet and equipment to support usual functions is
recommended.
(4) A suitable office
or desk space for the maintenance staff is recommended. This space may be
located within the repair shop area with space for catalogs, files, and
records.
(p) Oxygen. The
storage and use of oxygen and oxygen equipment must meet applicable NFPA
standards for gas equipment, including NFPA 99. Piped medical gas and vacuum
systems must comply with § 554.360(e) of this subchapter (relating to
Mechanical Requirements for New Facilities).