Current through Reg. 49, No. 38; September 20, 2024
(a) Resident bedrooms. Each resident bedroom
must meet the following requirements:
(1) The
maximum room capacity must be four residents.
(2) No more than 25% of the total licensed
beds may be in bedrooms with more than two beds each.
(3) Minimum bedroom area, excluding toilet
rooms, closets, lockers, wardrobes, alcoves, or vestibules, must be 100 square
feet in single occupancy rooms and 80 square feet per bed in multi-bed
rooms.
(4) The minimum allowable
room dimension is ten feet. The room must be designed to provide at least 36
inches between beds and 24 inches between any bed and the adjacent
wall.
(5) Each room must have at
least one operable outside window arranged and located so that it can be easily
opened from the inside without the use of tools or keys. The maximum allowable
sill height must not exceed 36 inches above the floor. All operable windows
must have insect screens. The minimum area of a window in each bedroom must
equal at least 16 square feet or 8.0% of the room area, whichever is larger.
Operable window sections may be restricted to not more than six nor less than
four inches for security or safety reasons.
(6) Each room must have general lighting,
wall-mounted bed reading lights, and night lighting. The night light must be
switched just inside the entrance to each resident room with a silent type
switch unless otherwise approved by HHSC. The light providing general
illumination must be switchable at the door of the resident room for use of
staff and residents. A durable non-glare reading light with an opaque front
panel securely anchored to the wall, integrally wired, must be provided for
each resident bed. The switch must be within reach of a resident in the
bed.
(7) Two duplex or a fourplex
grounding type receptacles must be provided beside the head of each bed. Other
walls must have duplex receptacles to accommodate items such as TV, radio,
razors, hairdryers, clocks, and as required by NFPA 70.
(8) Each resident must have access to a
toilet room without entering the general corridor area. One toilet room must
serve no more than two resident rooms. The toilet room must contain a water
closet and a lavatory. The lavatory may be omitted from a toilet room which
serves two bedrooms if each resident room contains a lavatory.
(9) Each resident must have a bed with a
comfortable mattress, a bedside stand with at least two enclosed storage
spaces, a dresser, and closet or wardrobe space providing privacy for clothing
and personal belongings. Clothes storage space must provide at least 22 inches
of lineal hanging space per bed and have closable doors. Chairs and space must
be provided for use by residents and visitors.
(10) Each room must open onto an exit
corridor and must be arranged for convenient resident access to dining, living,
and bathing areas.
(11) Visual
privacy such as cubicle curtains must be available for each resident in
multi-bed rooms. Design for privacy must not restrict resident access to entry,
lavatory, or toilet, nor may it restrict bed evacuation or obstruct sprinkler
flow coverage.
(12) At least one
noncombustible wastebasket must be provided in each bedroom.
(13) See the requirements in §
554.341(d)(4) of this subchapter (relating to Electrical Requirements) for
nurse call systems.
(14) Bedrooms
must be identified with a raised or recessed unique number placed on or near
the door. Refer to § 554.333(g) of this subchapter (relating to General
Considerations).
(15) Locks on
bedroom doors are permitted when they meet definite resident needs.
(A) Situations in which locking may be
necessary include the following:
(i) married
couples whose rights of privacy could be infringed upon unless bedroom door
locks are permitted; and
(ii)
residents for whom the attending physician wants bedroom door locks to enhance
the residents' sense of security.
(B) In situations such as those listed in
subparagraph (A) of this paragraph, the following guidelines must be met:
(i) bedroom door locks must be of the type
which the occupant can unlock at will from inside the room;
(ii) all bedroom door locks must be of the
type which can be unlocked from the corridor side;
(iii) attendants must carry keys which will
permit ready access to the locked bedrooms when entrance becomes necessary;
and
(iv) locking of bedroom doors
by residents for privacy or security will not be permitted except when
specifically included in the attending physician's written orders or authorized
by the nursing facility administrator.
(16) Vacant bedrooms must not be used for
hazardous activities or hazardous storage, unless specifically approved by HHSC
in writing.
(b) Nursing
service areas. The service areas described in this subsection must be located
in or readily available to each nursing unit. The size and disposition of each
service area will depend upon the number and types of beds to be served. Each
service area may be arranged and located to serve more than one nursing unit,
but at least one service area must be provided on each nursing floor. The
maximum allowable distance from a resident room door to a nurses' station is
150 feet. The following requirements are applicable to services areas:
(1) Nurses' stations must be provided with
space for nurses' charting, doctors' charting, and storage for administrative
supplies. Nurses' stations must be located to provide a direct view of resident
corridors. A direct view of resident corridors is acceptable if a person can
see down the corridors from a point within 24 inches of the outside of the
nurses' station counter or wall. When a nurses' station does not provide a
direct view of resident corridors, an auxiliary station complying with the
following guidelines must be provided.
(A)
The auxiliary station must be staffed by nursing personnel during all shifts.
(i) More than one auxiliary station may be
assigned to a designated nurses' station, regardless of the distance between
stations.
(ii) The nurse call
system for resident corridors monitored by the auxiliary station must report to
the auxiliary station.
(iii) Each
auxiliary station must meet the emergency electrical requirements for a nurses'
station, including electrical receptacles and emergency lighting.
(iv) If a required auxiliary station does not
already exist and the facility must establish a new auxiliary station, all
applicable standards, particularly those pertaining to the physical plant and
NFPA 101, must be observed.
(B) In addition to the required normal and
emergency illumination, the facility must keep on hand and readily available to
night staff no less than one working flashlight at each nurses'
station.
(2) Lounge and
toilet room must be provided for nursing staff.
(3) Lockers or security compartments must be
provided for the safekeeping of personal effects of staff. These must be
located convenient to the duty station of personnel or in a central
location.
(4) Clean utility room
must contain a work counter, sink with high-neck faucet with lever controls,
and storage facilities and must be part of a system for storage and
distribution of clean and sterile supply materials.
(5) Soiled utility room must contain a water
closet or equivalent flushing rim fixture, a sink large enough to submerge a
bedpan with spray hose and high-neck faucet with lever controls, work counter,
waste receptacle, and linen receptacle. These utility rooms must be part of a
system for collection and cleaning or disposal of soiled utensils or materials.
A separate hand-wash sink must be provided if the bedpan disinfecting sink
cannot normally be used for hand-washing.
(6) Provision must be made for convenient and
prompt 24-hour distribution of medication to residents. The medication
preparation room must be under the nursing staff's visual control and contain a
work counter, refrigerator, sink with hot and cold water, and locked storage
for biologicals and drugs and must have a minimum area of 50 square feet. The
minimum dimension allowed is five feet six inches. An appropriate air supply
must be provided to maintain adequate temperature and ventilation for safe
storage of medications. For purposes of storage of unrefrigerated medications,
the room temperature must be maintained between 59 degrees and 86 degrees
Fahrenheit.
(7) Provision must be
made for separate closets or room for clean linens. Corridors must not be used
for folding or cart storage. Storage rooms must be located and distributed in
the building for efficient access to bedrooms.
(8) Soiled linen rooms must be provided as
required in subsection (l) of this section.
(9) Nourishment stations are usually required
in all but the smaller facilities and must contain a sink equipped for
hand-washing, equipment for serving nourishment between scheduled meals,
refrigerator, and storage cabinets. Ice for residents' service and treatment
must be provided only by icemaker units. This station may be furnished in a
clean utility room.
(10) An
equipment storage room must be provided for equipment such as intravenous
stands, inhalators, air mattresses, and walkers.
(11) Parking spaces for stretchers and
wheelchairs must be located out of the path of normal traffic.
(c) Residents' bathing and toilet
facilities. The following requirements are applicable to bathing and toilet
facilities:
(1) Bathtubs or showers must be
provided at the rate of one for each 20 beds which are not otherwise served by
bathing facilities within residents' rooms. At least one bathing unit must be
provided in each nursing unit. Each tub or shower must be in an individual room
or enclosure which provides space for the private use of the bathing fixture,
for drying and dressing, and for a wheelchair and an attendant. Each
general-use bathing room must be provided with at least one water closet, in a
stall, room, or area for privacy, and one lavatory. A bathing room must be
located conveniently to the bedroom area it serves and must not be more than
100 feet from the farthest bedroom. See requirements in subsection (a)(8) of
this section for resident toilets at bedrooms.
(2) At least 50% of bathrooms and toilet
rooms, fixtures, and accessories must be designed and provided to meet criteria
under the Americans with Disabilities Act for individuals with disabilities
unless otherwise approved by HHSC.
(3) All rooms containing bathtubs, sitz
baths, showers, and water closets, subject to occupancy by residents, must be
equipped with swinging doors and hardware which will permit access from the
outside in any emergency.
(4)
Bathing areas must be provided with safe and effective auxiliary or
supplementary heating. Bathing areas must be free of drafts and must have
adequate exhaust ducted to the outside to minimize excess moisture retention
and resulting mold and mildew problems.
(5) Tubs and showers must be provided with
slip-proof bottoms.
(6) Lavatories
and hand-washing facilities must be securely anchored to withstand an applied
downward load of not less than 250 pounds on the front of the
fixtures.
(7) Provision must be
made for sanitary hand drying and toothbrush storage at lavatories. There must
be paper towel dispensers or separate towel racks and separate toothbrush
holders.
(8) Mirrors must be
arranged for convenient use by residents in wheelchairs as well as by residents
in a standing position, and the minimum size must be 15 inches in width by 30
inches in height, or tilt type.
(9)
Rooms with toilets must be provided with effective forced air exhaust ducted to
the exterior to help remove odors. Ducted manifold systems are recommended for
some multiple-type installations.
(10) Floors, walls, and ceilings must have
nonabsorbent surfaces, be smooth, and easily cleanable.
(d) Disposal facilities. A policy and
procedure for the safe and sanitary disposal of special waste must be provided.
Space and facilities must be provided for the sanitary storage of waste by
incineration, mechanical destruction, compaction, containerization, removal, or
by a combination of these techniques.
(e) Resident living areas. The following
requirements are applicable to resident living areas:
(1) Social-diversional spaces such as living
rooms, dayrooms, lounges, sunrooms, must be provided on a sliding scale as
follows:
Attached
Graphic
(2) Where
a required way of exit or a service way is through a living or dining area, a
pathway equal to the corridor width will normally be deducted for calculation
purposes and discounted from that area. These exit pathways must be kept clear
of obstructions.
(3) Each resident
living room and dining room must have at least one outside window. The window
area must be equal to at least 8.0% of the total room floor area. Sky-lighting
may be used to fulfill one-half of the 8.0% minimum area.
(4) Open or enclosed seating space must be
provided within view of the main nurse station that will allow furniture or
wheelchair parking that does not obstruct the corridor way of egress.
(f) Dining space. Dining space
must be adequate for the number of residents served, but not less than ten
square feet per resident bed.
(g)
Dietary facilities. The following requirements are applicable to dietary
facilities:
(1) Main or dietary kitchens must
be as follows:
(A) Kitchens will be evaluated
on the basis of their performance in the sanitary and efficient preparation and
serving of meals to residents. Consideration will be given to planning for the
type of meals served, the overall building design, the food service equipment,
arrangement, and the work flow involved in the preparation and delivery of
food. Plans must include a large-scale detailed kitchen layout designed by a
registered or licensed dietitian or architect having knowledge in the design of
food service operations.
(B)
Kitchens must be designed so that room temperature at summertime peak load will
not exceed a temperature of 85 degrees Fahrenheit measured over the room at the
five-foot level. The amount of supply air must take into account the large
quantities of air that may be exhausted at the range hood and dishwashing
area.
(C) Operational equipment
must be provided as planned and scheduled by the facility consultants for
preparing and serving meals and for refrigerating and freezing of perishable
foods, as well as equipment in, or adjacent to, the kitchen or dining area for
producing ice.
(D) Facilities for
washing and sanitizing dishes and cooking utensils must be provided. These
facilities must be designed based on the number of meals served and the method
of serving, that is, use of permanent or disposable dishes. As a minimum, the
kitchen must contain a multi-compartment sink large enough to immerse pots and
pans. In all facilities, a mechanical dishwasher is required for washing and
sanitizing dishes. Separation of soiled and clean dish areas must be
maintained, including air flow.
(E)
A vegetable preparation sink must be provided, and it must be separate from the
pot sinks.
(F) A supply of hot and
cold water must be provided. Hot water for sanitizing purposes must be 180
degrees Fahrenheit or the manufacturer's suggested temperature for chemical
sanitizers. For mechanical dishwashers the temperature measurement is at the
manifold.
(G) A kitchen must be
provided with a hand-washing lavatory in the food preparation area with hot and
cold water, soap, paper towel dispenser, and waste receptacle. The dish room
area must have ready access to a hand-washing lavatory.
(H) Staff rest room facilities with lavatory
must be directly accessible to kitchen staff without traversing resident use
areas. The rest room door must not open directly into the kitchen, that is,
provide a vestibule.
(I) Janitorial
facilities must be provided exclusively for the kitchen and must be located in
the kitchen area.
(J) Nonabsorbent
smooth finishes or surfaces must be used on kitchen floors, walls, and
ceilings. These surfaces must be capable of being routinely cleaned and
sanitized to maintain a healthful environment. Counter and cabinet surfaces,
inside and outside, must also have smooth, cleanable, relatively nonporous
finishes.
(K) Operable windows must
have insect screens provided.
(L)
Doors between kitchen and dining or serving areas must have a safety glass view
panel.
(M) A garbage can or cart
washing area with drain and hot water must be provided.
(N) Floor drains must be provided in the
kitchen and dishwashing areas.
(O)
Vapor removal from cooking equipment must be designed and installed in
accordance with NFPA 96.
(P) Grease
traps must be provided in compliance with local plumbing code or other
nationally recognized plumbing code.
(2) Food storage areas must be as follows:
(A) Food storage areas must provide for
storage of a seven-day minimum supply of nonperishable foods at all
times.
(B) Shelves must be
adjustable wire type. Walls and floors must have a nonabsorbent finish to
provide a cleanable surface. No foods may be stored on the floor; dollies,
racks, or pallets may be used to elevate foods not stored on
shelving.
(C) Dry foods storage
must have an effective venting system to provide for positive air
circulation.
(D) The maximum room
temperature for food storage must not exceed 85 degrees F at any time. The
measurement must be taken at the highest food storage level but not less than
five feet from the floor.
(E) Food
storage areas may be located apart from the food preparation area as long as
there is space adjacent to the kitchen for necessary daily usage.
(3) Auxiliary serving kitchens not
contiguous to food preparation or serving area must be as follows:
(A) Where service areas other than the
kitchen are used to dispense foods, these must be designated as food service
areas and must have equipment for maintaining required food temperatures while
serving.
(B) Separate food service
areas must have hand-washing facilities as a part of the food service
area.
(C) Finishes of all surfaces,
except ceilings, must be the same as those required for dietary kitchens or
comparable areas. See paragraph (1)(J) of this subsection.
(h) Administrative and public
areas.
(1) The following elements must be
provided in the public area:
(A) The entrance
must be at grade level, sheltered from the weather, and able to accommodate
wheelchairs. A drive-under canopy must be provided for the protection of
residents or visitors entering or leaving a vehicle. The latter may be a
secondary entrance.
(B) The lobby
must include:
(i) storage space for
wheelchairs if more than one is kept available;
(ii) a reception or information area, which
may be adjacent to the lobby if location is obvious;
(iii) waiting space;
(iv) public toilet facilities for individuals
with disabilities, which may be adjacent to lobby;
(v) at least one public access telephone,
installed to meet standards under the Americans with Disabilities Act;
and
(vi) drinking fountains. These
may be provided in a common public area and at least one must be installed to
meet standards under the Americans with Disabilities Act; and
(C) A lobby may also be
use-designed to satisfy a portion of the minimum area required for resident
living room space.
(2)
The following must be provided in the administrative area:
(A) General or individual offices for
business transactions, medical and financial records, administrative and
professional staff, and for private interviews relating to social service,
credit, and admissions.
(B) A
multipurpose room for conferences, meetings, and health education purposes
including facilities for showing visual aids.
(C) Storage and work area for office
equipment and supplies must be provided and accessible to the staff using such
items.
(3) Toilet
facilities for the disabled must be available in the building.
(i) Physical therapy facilities.
(1) Physical therapy facilities must be
provided if required by the treatment program. The facilities stated in
subparagraph (B) of this paragraph and paragraph (2)(C) - (E) of this
subsection may be planned and arranged for shared use by occupational therapy
residents and staff if the treatment program reflects this sharing concept.
Physical therapy facilities must include the following:
(A) Provision for privacy at each individual
treatment area.
(B) Hand-washing
facilities and one lavatory or sink may serve more than one cubicle.
(C) Facilities for the collection of soiled
linen and other material that may be used in the therapy.
(D) Residents' dressing areas, showers,
lockers, and toilet rooms, if the therapy is such that these would be needed at
the area.
(2) Physical
therapy facilities may also include the following:
(A) treatment areas with space and equipment
for the therapies provided;
(B) an
exercise area;
(C) storage for
clean linen, supplies, and equipment used in therapy;
(D) service sink located near therapy area;
and
(E) wheelchair and stretcher
storage.
(j)
Occupational therapy. Occupational therapy facilities must be provided if
required by the treatment program.
(1) An
activities area with a sink or lavatory and facilities for collection of waste
products prior to disposal must be provided.
(2) Storage for supplies and equipment used
in the therapy must be provided.
(k) Personal grooming area, such as a barber
or beauty shop. A separate room with appropriate equipment must be provided for
hair care and grooming needs of residents in facilities with over 60
beds.
(l) Laundry and linen
services.
(1) On-site processing must be as
follows:
(A) Because of the high incidence of
fires in laundries, it is highly recommended that the laundry be in a separate
building 20 feet or more from the main building. If the laundry is located
within the main building it must be separated by minimum one-hour fire
construction to structure above, and sprinklered, and must be located in a
remote area away from resident sleeping areas. Access doors must be from an
interior nonresident use area, such as a service corridor, that is separated
from the resident area, or from the exterior.
(B) If linen is to be processed on the site,
the following must be provided:
(i) A soiled
linen receiving, holding, and sorting room with a rinse sink. This area must
have a floor drain and forced exhaust to the exterior which must operate at all
times there is soiled linen being held in the area.
(ii) A laundry processing room with equipment
which can process seven days needs within a regularly scheduled work week.
Hand-washing facilities must be provided. The washer area must have:
(I) a floor drain;
(II) storage for laundry supplies;
(III) a clean linen inspection and mending
room or area and a folding area;
(IV) a clean linen storage, issuing, or
holding room or area;
(V) a
janitors' closet containing a floor receptor or service sink and storage space
for housekeeping equipment and supplies; and
(VI) sanitizing and washing facilities and a
storage area for carts.
(C) Soiled and clean operations must be
planned to maintain sanitary flow of functions as well as air flow. If carts
containing soiled linens from resident rooms are not taken directly to the
laundry area, intermediate holding rooms must be provided and located
convenient to resident bedroom areas.
(D) Laundry areas must have adequate air
supply and ventilation for staff comfort without having to rely on opening a
door that is part of the fire wall separation.
(E) Provisions must be made to exhaust heat
from dryers and to separate dryer make-up air from the habitable work areas of
the laundry.
(2) For
off-site linen processing, the following must be provided on the premises:
(A) a soiled linen holding room provided with
adequate forced exhaust ducted to the exterior;
(B) clean linen receiving, holding,
inspection, sorting or folding, and storage rooms; and
(C) sanitizing facilities and storage area
for carts.
(3)
Resident-use laundry, if provided, must be limited to not more than one
residential type washer and dryer per laundry room. This room must be
classified as a hazardous area according to NFPA 101.
(m) General storage. The following
requirements are applicable to general storage facilities:
(1) A general storage room must be provided
as needed to accommodate the facility's needs. It is recommended that a general
storage area provide at least two square feet per resident bed. This area would
be for items such as extra beds, mattresses, appliances, and other furnishing
and supplies.
(2) Storage space
with provisions for locking and security control should be provided for
residents' personal effects which are not kept in their rooms.
(n) Janitors' closet. In addition
to the janitors' closet called for in certain departments, a sufficient number
of janitors' closets must be provided throughout the facility to maintain a
clean and sanitary environment. These must contain a floor receptor or service
sink and storage space for housekeeping equipment and supplies.
(o) Maintenance, engineering service, and
equipment areas. Space and facilities for adequate preventive maintenance and
repair service must be provided. The following spaces are needed and it is
suggested that these be part of a separate laundry building or area:
(1) A storage area for building and equipment
maintenance supplies, tools, and parts must be provided.
(2) A space for storage of yard maintenance
equipment and supplies, including flammable liquids bulk storage, must be
provided separate from the resident-occupied facility.
(3) A maintenance and repair workshop of at
least 120 square feet and equipment to support usual functions is
recommended.
(4) A suitable office
or desk space for the maintenance staff is recommended, possibly located within
the repair shop area, with space for catalogs, files, and records.
(p) Oxygen. The storage and use of
oxygen and equipment must meet applicable NFPA standards for oxygen, including
NFPA 99.