Texas Administrative Code
Title 26 - HEALTH AND HUMAN SERVICES
Part 1 - HEALTH AND HUMAN SERVICES COMMISSION
Chapter 554 - NURSING FACILITY REQUIREMENTS FOR LICENSURE AND MEDICAID CERTIFICATION
Subchapter D - FACILITY CONSTRUCTION
Division 2 - FACILITIES LICENSED BEFORE SEPTEMBER 11, 2003
Section 554.316 - Subdivision of Building Spaces-Smoke Barriers
Current through Reg. 49, No. 38; September 20, 2024
(a) Subdivision of building spaces must be as required by NFPA 101.
(b) The facility must maintain the integrity of smoke barrier walls, including those parts of walls in attics and other concealed spaces.
(c) The facility must maintain the integrity of smoke dampers in air ducts.
(d) Ducts with smoke dampers must have maintenance panels for inspection. The maintenance panels must be removable without tools. Means of access must also be provided in the ceiling or side wall to facilitate smoke damper inspection readily and without obstruction. Location of dampers must be identified on the wall or ceiling of the occupied area below.