Texas Administrative Code
Title 26 - HEALTH AND HUMAN SERVICES
Part 1 - HEALTH AND HUMAN SERVICES COMMISSION
Chapter 553 - LICENSING STANDARDS FOR ASSISTED LIVING FACILITIES
Subchapter D - FACILITY CONSTRUCTION
Division 7 - EXISTING LARGE TYPE B ASSISTED LIVING FACILITIES
Section 553.141 - Construction Requirements for an Existing Large Type B Assisted Living Facility
Current through Reg. 49, No. 38; September 20, 2024
(a) Structurally sound. An existing large Type B assisted living facility must ensure any building is structurally sound regarding actual or expected dead, live, and wind loads according to applicable building codes.
(b) Separation of occupancies. An existing large Type B assisted living facility must be separated from other occupancies by a fire barrier having at least a 2-hour fire resistance rating constructed according to the requirements of NFPA 101 and its referenced standards, unless otherwise permitted by paragraphs (1) or (2) of this subsection.
(c) Construction type. An existing large Type B assisted living facility must ensure a building housing the facility meets the requirements of 19.1.6, Minimum Construction Requirements, in NFPA 101, Chapter 19, Existing Health Care Occupancies.
(d) Interior finish. An existing Large Type B assisted living facility must ensure interior wall, ceiling and floor finish materials meet the requirements of 19.3.3, Interior Finish, in NFPA 101, Chapter 19, Existing Health Care Occupancies.
(e) Vertical openings. An existing large Type B assisted living facility must ensure vertical openings are protected according to the requirements of 19.3.1, Protection of Vertical Openings, in NFPA 101, Chapter 19, Existing Health Care Occupancies.