Current through Reg. 49, No. 38; September 20, 2024
(a) Fire alarm and
smoke detection system. An existing large Type A assisted living facility must
provide a manual fire alarm system meeting the requirements of 9.6, Fire
Detection, Alarm, and Communication Systems, in NFPA 101, Chapter 9, Building
Service and Fire Protection Equipment, as modified by this section.
(1) General. An existing large Type A
assisted living facility must ensure the operation of any alarm initiating
device automatically activates an audible or a visual alarm at the
site.
(2) Smoke detectors.
(A) An existing large Type A assisted living
facility must install smoke detectors in resident bedrooms, corridors,
hallways, living rooms, dining rooms, offices, kitchens, laundries, attached
garages used for car parking, and public or common areas, except as permitted
in subparagraphs (B) - (D) of this paragraph.
(B) An existing large Type A assisted living
facility may install heat detectors in lieu of smoke detectors in kitchens,
laundries, and attached garages used for car parking.
(C) An existing large Type A assisted living
facility located in a building constructed to meet the requirements of NFPA
101, Chapter 19, Existing Health Care Occupancies, may install a smoke
detection system meeting the requirements of 19.3.4.5.1, Corridors, in NFPA
101, Chapter 19, Existing Health Care Occupancies, in lieu of the requirements
found in subparagraphs (A) and (B) of this paragraph.
(D) An existing large Type A assisted living
facility comprised of buildings containing living units with independent
cooking equipment must additionally have:
(i)
a smoke detector installed all in resident bedrooms, corridors, hallways,
living rooms, dining rooms, offices, kitchens and laundries within the living
unit, that sounds an alarm only within the living unit; and
(ii) a heat detector installed in the kitchen
within the living unit that activates the general alarm.
(3) Alarm control panel.
(A) An existing large Type A assisted living
facility must provide a fire alarm control unit, or a fire alarm annunciator
providing annunciation of all fire alarm, supervisory, and trouble signals by
audible and visible indicators, in a location visible to staff at or near the
staff area that is attended 24 hours a day.
(B) An existing large Type A assisted living
facility is not required to ensure a fire alarm control unit or fire alarm
annunciator is visible to staff if the fire alarm is monitored by devices
carried by all staff.
(C) An
existing large Type A assisted living facility must ensure a fire alarm panel
indicates each floor and smoke compartment, as applicable, as a separate zone.
Each zone must provide an alarm and trouble indication. When all alarm
initiating devices are addressable and the status of each device is identified
on the fire alarm panel, zone indication is not required.
(4) Fire alarm power source.
(A) An existing large Type A assisted living
facility must ensure a fire alarm system is powered by a permanently-wired,
dedicated branch circuit that is powered from a commercial power source in
accordance with NFPA 70.
(B) An
existing large Type A assisted living facility must provide a secondary,
emergency power source meeting the requirements of NFPA 72.
(5) Emergency forces notification.
An existing large Type A assisted living facility not equipped with a fire
alarm system that automatically notifies emergency forces must immediately
notify the fire department by telephone or other means.
(b) Fire sprinkler system.
(1) An existing large Type A assisted living
facility may provide a fire sprinkler system meeting the requirements of NFPA
13 in accordance with 33.3.3.5.1, in NFPA 101, Chapter 33, Existing Residential
Board and Care Occupancies.
(2) An
existing large Type A assisted living facility located in a building that is
four or fewer stories in height may provide a fire sprinkler system meeting the
requirements of NFPA 13R in accordance with 33.3.3.5.1.1, in NFPA 101, Chapter
33, Existing Residential Board and Care Occupancies.
(3) An existing large Type A assisted living
facility located in a high-rise building must be protected throughout by an
approved, supervised automatic fire sprinkler system meeting the requirements
of NFPA 13 according to 33.3.3.5.3, in NFPA 101, Chapter 33, Existing
Residential Board and Care Occupancies.
(c) Protection of attics. An existing large
Type A assisted living facility equipped with a fire sprinkler system must
ensure an attic is protected according to the requirements of 33.3.3.5.4, in
NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies, not
later than August 31, 2024.
(d)
Portable fire extinguishers. An existing large Type A assisted living facility
must provide and maintain portable fire extinguishers according to the
requirements of NFPA 10.
(1) An existing large
Type A assisted living facility must ensure all requirements of NFPA 10 are
followed for all extinguisher types, including requirements for location,
spacing, mounting heights, monthly inspections by staff, yearly inspections by
a licensed agent, any necessary servicing, and hydrostatic testing as
recommended by the manufacturer.
(2) An existing large Type A assisted living
facility must ensure portable fire extinguishers are located in resident
corridors so the travel distance from any point in the facility to an
extinguisher is no more than 75 feet.
(3) An existing large Type A assisted living
facility must ensure the actual size of any portable fire extinguisher meets
the requirements of NFPA 10 for maximum floor area per unit covered, but an
extinguisher must be no smaller than the following.
(A) A water-type portable fire extinguisher
must have a rating of at least 1-A according to NFPA 10.
(B) All other portable fire extinguishers
must have a rating of at least 2-A:5-B:C according to NFPA 10.
(C) A facility must provide at least one
approved 20-B:C portable fire extinguisher in each laundry, kitchen and walk-in
mechanical room.
(4) An
existing large Type A assisted living facility must ensure portable fire
extinguishers are installed on hangers or brackets supplied with the
extinguisher or mounted in an approved cabinet.
(5) An existing large Type A assisted living
facility must ensure a portable fire extinguisher is protected from impact or
dislodgement.
(6) An existing large
Type A assisted living facility must ensure a portable fire extinguisher is
installed at an appropriate height.
(A) A
portable fire extinguisher having a gross weight of up to 40 pounds must be
installed so the top of the extinguisher is not more than five feet above the
floor.
(B) A portable fire
extinguisher having a gross weight greater than 40 pounds must be installed so
the top of the extinguisher is not more than three and a half feet above the
floor.
(C) A portable fire
extinguisher must be installed so the clearance between the bottom of the
extinguisher and the floor is at least four inches.
(7) A portable extinguisher provided in a
hazardous room must be located as close as possible to the exit access door
leading from the room and on the latch or knob side of the door.