Section 553.133 - Means of Egress Requirements for an Existing Large Type A Assisted Living Facility

Current through Reg. 49, No. 38; September 20, 2024

(a) An existing large Type A assisted living facility must meet the requirements of 33.3.2, Means of Egress, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies, except as described in this section.

(b) The provisions of 33.3.2.11.2, Lockups, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies, are not permitted.

(c) An existing large Type A assisted living facility must ensure doors meet the requirements of 33.3.2.2.2, Doors, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies, and the additional requirements of this section.

(1) A resident room door in an existing large Type A assisted living facility must latch in its frame to resist the passage of smoke.

(2) In an existing large Type A assisted living facility comprised of buildings that contain living units with independent cooking equipment within the living unit, a door between the living unit and a corridor or hallway must:
(A) be self-closing or automatic-closing; and

(B) latch in its frame to resist the passage of smoke.

(3) A resident room door or living unit door must not be arranged to prevent the occupant from closing the door.

(d) An existing large Type A assisted living facility providing spaces for use by residents on floors other than the ground floor must provide at least two separate approved stairs and must ensure stairs used as a means of egress meet the requirements of 33.3.2.2.3, Stairs, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies.

(e) An existing large Type A assisted living facility must ensure means of egress are marked according to the requirements of 33.3.2.10, Marking of Means of Egress, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies.

(f) An existing large Type A assisted living facility containing more than 25 sleeping rooms must provide emergency lighting, according to the requirements of 33.3.2.9, Emergency Lighting, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies, unless each sleeping room has a direct exit to the outside at the finished ground level.

Disclaimer: These regulations may not be the most recent version. Texas may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.