Texas Administrative Code
Title 26 - HEALTH AND HUMAN SERVICES
Part 1 - HEALTH AND HUMAN SERVICES COMMISSION
Chapter 553 - LICENSING STANDARDS FOR ASSISTED LIVING FACILITIES
Subchapter D - FACILITY CONSTRUCTION
Division 5 - EXISTING SMALL TYPE B ASSISTED LIVING FACILITIES
Section 553.123 - Means of Escape Requirements for an Existing Small Type B Assisted Living Facility
Current through Reg. 49, No. 38; September 20, 2024
(a) The provisions of NFPA 101, Chapter 7, Means of Egress, do not apply to an existing small Type B assisted living facility, unless explicitly referenced by this section or by NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies.
(b) An existing small Type B assisted living facility must meet the requirements of 33.2.2, Means of Escape, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies, except as described in this section.
(c) An existing small Type B assisted living facility must ensure doors meet the requirements of 33.2.2.5, Doors, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies, and the additional requirements of this section. A resident room door is not otherwise required to meet the requirements for doors in 33.2.3.6, Construction of Corridor Walls, in NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies.
(d) An existing small Type B assisted living facility providing spaces for use by residents on floors other than the ground floor must provide at least two separate approved stairs.