Current through Reg. 49, No. 38; September 20, 2024
(a) Fire alarm and
smoke detection system. An existing small Type A assisted living facility must
provide a manual fire alarm system meeting the requirements of section 9.6,
Fire Detection, Alarm, and Communication Systems, in NFPA 101, Chapter 9,
Building Service and Fire Protection Equipment, as modified by this section.
(1) General. An existing small Type A
assisted living facility must ensure the operation of any alarm initiating
device automatically activates an audible or a visual alarm at the
site.
(2) Smoke detectors.
(A) An existing small Type A assisted living
facility must install smoke detectors in resident bedrooms, corridors,
hallways, living rooms, dining rooms, offices, kitchens, laundries, attached
garages used for car parking, and public or common areas, except as permitted
in subparagraphs (B) and (C) of this paragraph.
(B) An existing small Type A assisted living
facility may install heat detectors in lieu of smoke detectors in kitchens,
laundries, and attached garages used for car parking.
(C) An existing small Type A assisted living
facility located in a building constructed to meet the requirements of NFPA
101, Chapter 19, Existing Health Care Occupancies, may install a smoke
detection system meeting the requirements of 19.3.4.5.1, Corridors, in NFPA
101, Chapter 19, Existing Health Care Occupancies, in lieu of the requirements
in subparagraph (A) of this paragraph.
(3) Alarm control panel.
(A) An existing small Type A assisted living
facility must provide a fire alarm control unit, or a fire alarm annunciator
providing annunciation of all fire alarm, supervisory, and trouble signals by
audible and visible indicators, in a location visible to staff at or near the
staff area that is attended 24 hours a day.
(B) An existing small Type A assisted living
facility is not required to ensure a fire alarm control unit or fire alarm
annunciator is visible to staff if the fire alarm is monitored by devices
carried by all staff.
(4)
Fire alarm power source.
(A) An existing
small Type A assisted living facility must ensure a fire alarm system is
powered by a permanently-wired, dedicated branch circuit that is powered from a
commercial power source in accordance with NFPA 70.
(B) An existing small Type A assisted living
facility must provide a secondary, emergency power source meeting the
requirements of NFPA 72.
(b) Fire sprinkler system.
(1) An existing small Type A assisted living
facility may provide one of the following fire sprinkler systems according to
the requirements of 33.2.3.5, Extinguishment Requirements, in NFPA 101, Chapter
33, Existing Residential Board and Care Occupancies.
(A) A fire sprinkler system meeting the
requirements of NFPA 13 in accordance with 33.2.3.5.3.3;
(B) A fire sprinkler system meeting the
requirements of NFPA 13R in accordance with 33.2.3.5.3.4; or
(C) A fire sprinkler system meeting the
requirements of NFPA 13D in accordance with 33.2.3.5.3.2.
(2) An existing small Type A assisted living
facility must provide supervision of any fire sprinkler system where required
by 33.2.3.5, Extinguishment Requirements, in NFPA 101, Chapter 33, Existing
Residential Board and Care Occupancies.
(c) Protection of attics. An existing small
Type A assisted living facility equipped with a fire sprinkler system must
ensure an attic is protected according to the requirements of 33.2.3.5.7, in
NFPA 101, Chapter 33, Existing Residential Board and Care Occupancies, not
later than August 31, 2024.
(d)
Portable fire extinguishers. An existing small Type A assisted living facility
must provide and maintain portable fire extinguishers according to the
requirements of NFPA 10.
(1) An existing small
Type A assisted living facility must ensure all requirements of NFPA 10 are
followed for all extinguisher types, including requirements for location,
spacing, mounting heights, monthly inspections by staff, yearly inspections by
a licensed agent, any necessary servicing, and hydrostatic testing as
recommended by the manufacturer.
(2) An existing small Type A assisted living
facility must ensure portable fire extinguishers are located so the travel
distance from any point in the facility to an extinguisher is no more than 75
feet.
(3) An existing small Type A
assisted living facility must ensure the actual size of any portable fire
extinguisher meets the requirements of NFPA 10 for maximum floor area per unit
covered, but an extinguisher must be no smaller than the following.
(A) A water-type portable fire extinguisher
must have a rating of at least 1-A according to NFPA 10.
(B) All other portable fire extinguishers
must have a rating of at least 2-A:5-B:C according to NFPA 10.
(4) An existing small Type A
assisted living facility must ensure portable fire extinguishers are installed
on hangers or brackets supplied with the extinguisher or mounted in an approved
cabinet.
(5) An existing small Type
A assisted living facility must ensure a portable fire extinguisher is
protected from impact or dislodgement.
(6) An existing small Type A assisted living
facility must ensure a portable fire extinguisher is installed at an
appropriate height.
(A) A portable fire
extinguisher having a gross weight of up to 40 pounds must be installed so the
top of the extinguisher is not more than five feet above the floor.
(B) A portable fire extinguisher having a
gross weight greater than 40 pounds must be installed so the top of the
extinguisher is not more than three and a half feet above the floor.
(C) A portable fire extinguisher must be
installed so the clearance between the bottom of the extinguisher and the floor
is at least four inches.
(7) A portable extinguisher provided in a
hazardous room must be located as close as possible to the door leading from
the room and on the latch or knob side of the door.