Current through Reg. 49, No. 38; September 20, 2024
(a) Fire alarm and
smoke detection system. A new large Type B assisted living facility must
provide a fire alarm system meeting the requirements of 18.3.4, Detection,
Alarm, and Communications Systems, in NFPA 101, Chapter 18, New Health Care
Occupancies, as modified by this section.
(1)
General. A new large Type B assisted living facility must ensure the operation
of any alarm initiating device automatically activates the manual fire alarm
system evacuation alarm for the entire building.
(2) Smoke detectors.
(A) A new large Type B assisted living
facility must install smoke detectors meeting the requirements of 18.3.4.5.1,
Corridors, in NFPA 101, Chapter 18, New Health Care Occupancies.
(B) A new large Type B assisted living
facility comprised of buildings containing living units with independent
cooking equipment within the living unit, must additionally have:
(i) a smoke detector installed in all
resident bedrooms, corridors, hallways, living rooms, dining rooms, offices,
kitchens and laundries within the living unit, that sounds an alarm only within
the living unit; and
(ii) a heat
detector installed in the kitchen within the living unit that activates the
general alarm.
(3) Alarm control panel.
(A) A new large Type B assisted living
facility must provide a fire alarm control unit, or a fire alarm annunciator
providing annunciation of all fire alarm, supervisory, and trouble signals by
audible and visible indicators, in a location visible to staff at or near the
staff area that is attended 24 hours a day.
(B) A new large Type B assisted living
facility is not required to ensure a fire alarm control unit or fire alarm
annunciator is visible to staff if the fire alarm is monitored by devices
carried by all staff.
(C) A new
large Type B assisted living facility must ensure a fire alarm panel indicates
each floor and smoke compartment, as applicable, as a separate zone. Each zone
must provide an alarm and trouble indication. When all alarm initiating devices
are addressable and the status of each device is identified on the fire alarm
panel, zone indication is not required.
(4) Fire alarm power source.
(A) A new large Type B assisted living
facility must ensure a fire alarm system is powered by a permanently-wired,
dedicated branch circuit that is powered from a commercial power source in
accordance with NFPA 70.
(B) A new
large Type B assisted living facility must provide a secondary, emergency power
source meeting the requirements of NFPA 72.
(5) Emergency forces notification. A new
large Type B assisted living facility must ensure a fire alarm system
automatically notifies emergency forces according to the requirements of
18.3.4.3.2, Emergency Forces Notification, in NFPA 101, Chapter 18, New Health
Care Occupancies
(b) Fire
sprinkler system. A new large Type B assisted living facility must provide a
fire sprinkler system meeting the requirements of NFPA 13 in accordance with
18.3.5, in NFPA 101, Chapter 18, New Health Care Occupancies.
(c) Portable Fire Extinguishers. A new large
Type B assisted living facility must provide and maintain portable fire
extinguishers according to the requirements of NFPA 10.
(1) A new large Type B assisted living
facility must ensure all requirements of NFPA 10 are followed for all
extinguisher types, including requirements for location, spacing, mounting
heights, monthly inspections by staff, yearly inspections by a licensed agent,
any necessary servicing, and hydrostatic testing as recommended by the
manufacturer.
(2) A new large Type
B assisted living facility must ensure portable fire extinguishers are located
in resident corridors so the travel distance from any point in the facility to
an extinguisher is no more than 75 feet.
(3) A new large Type B assisted living
facility must ensure the actual size of any portable fire extinguisher meets
the requirements of NFPA 10 for maximum floor area per unit covered, but an
extinguisher must be no smaller than the following.
(A) A water-type portable fire extinguisher
must have a rating of at least 1-A according to NFPA 10.
(B) All other portable fire extinguishers
must have a rating of at least 2-A:10-B:C according to NFPA 10.
(C) A facility must provide at least one
approved 20-B:C portable fire extinguisher in each laundry, kitchen, and
walk-in mechanical room.
(4) A new large Type B assisted living
facility must ensure portable fire extinguishers are installed on hangers or
brackets supplied with the extinguisher or mounted in an approved
cabinet.
(5) A new large Type B
assisted living facility must ensure a portable fire extinguisher is protected
from impact or dislodgement.
(6) A
new large Type B assisted living facility must ensure a portable fire
extinguisher is installed at an appropriate height.
(A) A portable fire extinguisher having a
gross weight of up to 40 pounds must be installed so the top of the
extinguisher is not more than five feet above the floor.
(B) A portable fire extinguisher having a
gross weight greater than 40 pounds must be installed so the top of the
extinguisher is not more than three and a half feet above the floor.
(C) A portable fire extinguisher must be
installed so the clearance between the bottom of the extinguisher and the floor
is at least four inches.
(7) A portable extinguisher provided in a
hazardous room must be located as close as possible to the exit access door
leading from the room and on the latch or knob side of the door.