Current through Reg. 49, No. 38; September 20, 2024
(a) Fire alarm and
smoke detection system. A new large Type A assisted living facility must
provide a manual fire alarm system meeting the requirements of 9.6, Fire
Detection, Alarm, and Communication Systems, in NFPA 101, Chapter 9, Building
Service and Fire Protection Equipment, as modified by this section.
(1) General. A new large Type A assisted
living facility must ensure the operation of any alarm initiating device
automatically activates the manual fire alarm system evacuation alarm for the
entire building.
(2) Smoke
detectors.
(A) A new large Type A assisted
living facility must install smoke detectors in resident bedrooms, corridors,
hallways, living rooms, dining rooms, offices, kitchens, laundries, attached
garages used for car parking, and public or common areas, except as permitted
in subparagraphs (B) - (D) of this paragraph.
(B) A new large Type A assisted living
facility may install heat detectors in lieu of smoke detectors in kitchens,
laundries, and attached garages used for car parking.
(C) A new large Type A assisted living
facility located in a building constructed to meet the requirements of NFPA
101, Chapter 18, New Health Care Occupancies, may install a smoke detection
system meeting the requirements of 19.3.4.5.1, Corridors, in NFPA 101, Chapter
18, New Health Care Occupancies, in lieu of the requirements found in
subparagraphs (A) and (B) of this paragraph.
(D) A new large Type A assisted living
facility comprised of buildings containing living units with independent
cooking equipment must additionally have:
(i)
a smoke detector installed all in resident bedrooms, corridors, hallways,
living rooms, dining rooms, offices, kitchens and laundries within the living
unit, that sounds an alarm only within the living unit; and
(ii) a heat detector installed in the kitchen
within the living unit that activates the general alarm.
(E) A new large Type A assisted living
facility is not required to install smoke alarms, as required by 32.3.4.7,
Smoke Alarms, in NFPA 101, Chapter 32, New Residential Board and Care
Occupancies, in addition to the smoke detectors required by subparagraphs (A) -
(D) of this paragraph.
(3) Alarm control panel.
(A) A new large Type A assisted living
facility must provide a fire alarm control unit, or a fire alarm annunciator
providing annunciation of all fire alarm, supervisory, and trouble signals by
audible and visible indicators, in a location visible to staff at or near the
staff area that is attended 24 hours a day.
(B) A new large Type A assisted living
facility is not required to ensure a fire alarm control unit or fire alarm
annunciator is visible to staff if the fire alarm is monitored by devices
carried by all staff.
(C) A new
large Type A assisted living facility must ensure a fire alarm panel indicates
each floor and smoke compartment, as applicable, as a separate zone. Each zone
must provide an alarm and trouble indication. When all alarm initiating devices
are addressable and the status of each device is identified on the fire alarm
panel, zone indication is not required.
(4) Fire alarm power source.
(A) A new large Type A assisted living
facility must ensure a fire alarm system is powered by a permanently-wired,
dedicated branch circuit that is powered from a commercial power source in
accordance with NFPA 70.
(B) A new
large Type A assisted living facility must provide a secondary, emergency power
source meeting the requirements of NFPA 72.
(5) Emergency forces notification. A new
large Type A assisted living must ensure a fire alarm system provides emergency
forces notification according to the requirements of 32.3.3.4.6, Emergency
Forces Notification, in NFPA 101, Chapter 32, New Residential Board and Care
Occupancies.
(b) Fire
sprinkler system. A new large Type A assisted living facility must provide a
fire sprinkler system meeting the requirements of NFPA 13 in accordance with
32.3.3.5, in NFPA 101, Chapter 32, New Residential Board and Care
Occupancies.
(c) Portable Fire
Extinguishers. A new large Type A assisted living facility must provide and
maintain portable fire extinguishers according to the requirements of
32.3.3.5.7, Portable Fire Extinguishers, in NFPA 101, Chapter 32, New
Residential Board and Care Occupancies, and the additional requirements of this
subsection.
(1) A new large Type A assisted
living facility must ensure all requirements of NFPA 10 are followed for all
extinguisher types, including requirements for location, spacing, mounting
heights, monthly inspections by staff, yearly inspections by a licensed agent,
any necessary servicing, and hydrostatic testing as recommended by the
manufacturer.
(2) A new large Type
A assisted living facility must ensure portable fire extinguishers are located
in resident corridors so the travel distance from any point in the facility to
an extinguisher is no more than 75 feet.
(3) A new large Type A assisted living
facility must ensure the actual size of any portable fire extinguisher meets
the requirements of NFPA 10 for maximum floor area per unit covered, but an
extinguisher must be no smaller than the following.
(A) A water-type portable fire extinguisher
must have a rating of at least 1-A according to NFPA 10.
(B) All other portable fire extinguishers
must have a rating of at least 2-A:10-B:C according to NFPA 10.
(C) A facility must provide at least one
approved 20-B:C portable fire extinguisher in each laundry, kitchen and walk-in
mechanical room.
(4) A
new large Type A assisted living facility must ensure portable fire
extinguishers are installed on hangers or brackets supplied with the
extinguisher or is mounted in an approved cabinet.
(5) A new large Type A assisted living
facility must ensure a portable fire extinguisher is protected from impact or
dislodgement.
(6) A new large Type
A assisted living facility must ensure a portable fire extinguisher is
installed at an appropriate height.
(A) A
portable fire extinguisher having a gross weight of up to 40 pounds must be
installed so the top of the extinguisher is not more than five feet above the
floor.
(B) A portable fire
extinguisher having a gross weight greater than 40 pounds must be installed so
the top of the extinguisher is not more than three and a half feet above the
floor.
(C) A portable fire
extinguisher must be installed so the clearance between the bottom of the
extinguisher and the floor is at least four inches.
(7) A portable extinguisher provided in a
hazardous room must be located as close as possible to the exit access door
leading from the room and on the latch or knob side of the door.