Current through Reg. 50, No. 13; March 28, 2025
(a) Scope. The requirements of this section
are applicable to both new and existing facilities unless stated
otherwise.
(b) Purpose.
(1) The concept of requirements for fire
safety with regard to the residents is based on evacuation capability as
published in NFPA 101. These standards are written with the premise that the
residents will be capable of self-evacuation without continuous staff
assistance. Residents that are not normally capable of self-evacuation nor
capable of negotiating stairs unassisted must not be housed above or below the
floor of exit discharge unless the facility meets the construction requirements
of NFPA 101, Chapter 18, New Health Care Occupancies, or Chapter 19, Existing
Health Care Occupancies, for large facilities, or the "impractical"
requirements for small facilities as found in NFPA 101, Chapter 32, New
Residential Board and Care Occupancies, or Chapter 33, Existing Residential
Board and Care Occupancies. Examples of residents who may not be capable of
self-evacuation are as follows:
(A) a person
with a physical disability of a nature that he or she is not capable of
maneuvering in a wheelchair, walker, or other assistive device
unaided;
(B) a person with an
intellectual disability who will not take or cannot understand instructions
from a staff member; or
(C) a
person that is taking medication before bedtime which will make it difficult
for a staff member to arouse the person quickly.
(2) The method of determining the evacuation
capability of residents under NFPA 101, Chapter 32, New Residential Board and
Care Occupancies or Chapter 33, Existing Residential Board and Care
Occupancies, is by rating each resident and each staff member to determine an
evacuation difficulty score (E-score). If the E-score is 1.5 or less, the
evacuation capability of the facility is prompt, greater than 1.5 to five is
slow, greater than five is impractical. The worksheets to be completed are
located in NFPA 101A, Chapter 6, Evacuation Capability Determination for Board
and Care Occupancies. Facilities with capacity for 16 residents or less must
meet the evacuation requirement for their designated Chapter 32, New
Residential Board and Care Occupancies or Chapter 33, Existing Residential
Board and Care Occupancies rating. The ratings and their requirements are:
(A) Impractical rating.
(i) The facility must have one fire drill per
shift each calendar quarter (minimum of 12 drills per year).
(ii) The facility must actually evacuate
residents once a year on each shift.
(iii) All facility staff, including relief
and substitute staff, must participate in drills as soon as possible after
beginning employment on their shift.
(iv) E-scores are not required for
certification under this rating.
(B) Slow rating.
(i) The facility must have one fire drill per
shift each calendar quarter (minimum of 12 drills per year).
(ii) The facility must actually evacuate
residents during all drills.
(iii)
Staff on each shift must participate in drills.
(iv) New, relief, and substitute staff must
participate in a drill within ten days of employment on their assigned
shift.
(v) E-scores must be
calculated as soon as possible, but within ten calendar days of
admission.
(vi) Initial E-scores
are based on four drills, as follows:
(I) two
conducted during the daytime; and
(II) two conducted during the nighttime,
after the first 30 minutes and within the first three hours of sleep.
(vii) After the initial E-scores
are obtained, a worksheet for rating residents must be completed for all newly
admitted residents to obtain an E-score. The evacuation capability is
calculated as described in clause (vi) of this subparagraph.
(viii) E-scores must be updated annually or
sooner if significant changes occur in any resident's evacuation capability.
These updated scores are based on the group's overall performance during fire
drills as they are conducted throughout the year. Scores do not have to be
calculated in accordance with the drills required for newly admitted residents
based on the requirements stated in clause (vi) of this subparagraph.
(C) Prompt rating.
(i) The facility must have one fire drill per
shift each calendar quarter (minimum of 12 drills per year).
(ii) The facility must actually evacuate
residents during all drills.
(iii)
Staff on each shift must participate in drills.
(iv) New, relief, and substitute staff must
participate in a drill within ten days of employment on their assigned
shift.
(v) E-scores must be
calculated as soon as possible, but within ten calendar days of
admission.
(vi) Initial E-scores
are based on four drills, as follows:
(I) two
conducted during the daytime; and
(II) two conducted during the nighttime,
after the first 30 minutes and within the first three hours of sleep.
(vii) After the initial E-scores
are obtained, a worksheet for rating residents must be completed for all newly
admitted residents to obtain an E-score. The evacuation capability is
calculated as described in clause (vi) of this subparagraph.
(viii) E-scores must be updated annually or
sooner if significant changes occur that would affect a resident's evacuation
capability. These updated scores are based on the group's overall performance
during fire drills as they are conducted throughout the year. Scores do not
have to be calculated in accordance with the drills required for newly admitted
residents based on the requirements stated in clause (vi) of this
subparagraph.
(3) The "E" score will determine which NFPA
101 features are to be installed and maintained in the facility. These features
include construction, fire alarm systems, smoke detector systems, interior
finish, sprinkler systems, separation of bedrooms, and egress from the
building.
(c)
Construction.
(1) New construction is any
construction work that began on or after July 5, 2016. The provisions of NFPA
101, Chapter 18, New Health Care Occupancies are applicable for large
facilities, and Chapter 32, New Residential Board and Care Occupancies for
small facilities.
(2) An existing
facility is one that was operating with a license as a facility for persons
with an intellectual disability or related conditions before November 1, 2016,
and has not subsequently become unlicensed. The provisions of NFPA 101, Chapter
19, Existing Health Care Occupancies are applicable for large facilities, and
Chapter 33, Existing Residential Board and Care Occupancies for small
facilities.
(3) Alterations or new
installations of building services equipment, such as mechanical and electrical
systems, generators, fire alarm, and detection systems must be accomplished in
conformance with the requirements for new construction as required by NFPA
101.
(4) Site approval, as required
by the local health officer, building department, or fire marshal having
jurisdiction, must be obtained. Any conditions considered to be a fire, safety,
or health hazard will be grounds for disapproval of the site by the Texas
Health and Human Services Commission (HHSC) unless applied in an arbitrary or
discriminating manner.
(5)
Facilities that renovate must provide documentation for the flame spread rate
of any new materials applied as an interior finish.
(6) Life safety features and equipment that
have been installed in existing buildings and are now in excess of that
required by NFPA 101 must continue to be maintained or must be removed at the
direction of HHSC.
(7) When an
existing licensed facility plans building additions or remodeling, which
includes construction of additional resident beds, then the ratio of bathing
units must be reevaluated to meet minimum standards and the square footage of
dining and living areas must be reevaluated by HHSC. Conversion of existing
living, dining, or activity areas to resident bedrooms must not reduce these
functions to an area less than required by minimum standards.
(8) Buildings must be of recognized permanent
type construction. They must be structurally sound with regard to actual or
expected dead, live, and wind loads according to applicable building
codes.
(9) Each building must be
classified as to the building construction type for fire resistance rating
purposes in accordance with NFPA 220 and NFPA 101.
(d) Applicable codes and standards. Except as
provided in paragraph (9) of this subsection, a facility must comply with NFPA
101, NFPA 99, and a Tentative Interim Amendment (TIA) issued by the NFPA for
NFPA 99 or NFPA 101, including the TIAs listed in paragraphs (1) and (2) of
this subsection. A facility must also comply with other NFPA publications
referenced in this chapter and a TIA issued for a publication referenced in
this chapter, unless otherwise approved or required by HHSC.
(1) The following TIAs have been issued for
NFPA 101:
(A) TIA 12-1 to NFPA 101, issued
August 11, 2011;
(B) TIA 12-2 to
NFPA 101, issued October 30, 2012;
(C) TIA 12-3 to NFPA 101, issued October 22,
2013; and
(D) TIA 12-4 to NFPA 101,
issued October 22, 2013.
(2) The following TIAs have been issued for
NFPA 99:
(A) TIA 12-2 to NFPA 99, issued
August 11, 2011;
(B) TIA 12-3 to
NFPA 99, issued August 9, 2012;
(C)
TIA 12-4 to NFPA 99, issued March 7, 2013;
(D) TIA 12-5 to NFPA 99, issued August 1,
2013; and
(E) TIA 12-6 to NFPA 99,
issued March 3, 2014.
(3)
If the municipality has a building code and a plumbing code, then those codes
must govern in those areas of construction. Where local codes or ordinances are
applicable, the most restrictive parts concerning the same subject item must
apply unless otherwise determined by the authority having jurisdiction for
local codes and HHSC.
(4) In the
absence of such governing municipal codes, nationally recognized codes must be
used, such as the Standard Building Code and the Standard Plumbing Code, both
of the Southern Building Code Congress International, Inc. Such nationally
recognized codes, when used, must all be publications of the same group or
organization to assure the intended continuity.
(5) Heating, ventilating, and
air-conditioning systems must be designed and installed in accordance with NFPA
90A and NFPA 90B, as applicable, and the American Society of Heating,
Refrigerating, and Air-Conditioning Engineers (ASHRAE), except as may be
modified in this subchapter.
(6)
Electrical and illumination system must be designed and installed in accordance
with NFPA 70 and the Lighting Handbook of the Illuminating Engineering Society
of North America (IES) except as may be modified in this subchapter.
(7) The facility must meet all applicable
provisions and requirements concerning accessibility for individuals with
disabilities in the following laws and regulations: the Americans with
Disabilities Act of 1990 (Title 42, United States Code, Chapter 126); 28 CFR
Part 35, Nondiscrimination on the Basis of Disability in State and Local
Government Services; Texas Government Code, Chapter 469, Elimination of
Architectural Barriers; and 16 TAC, Chapter 68, Elimination of Architectural
Barriers. Plans for new construction, substantial renovations, modifications,
and alterations must be submitted to the Texas Department of Licensing and
Regulation (Attention: Elimination of Architectural Barriers Program) for
accessibility approval under Chapter 469.
(8) A facility with a boiler must meet all
applicable provisions and requirements of Texas Health and Safety Code, Chapter
755, Boilers.
(9) A facility that
is required to comply with NFPA 101, Chapter 33, Existing Residential Board and
Care Occupancies, must be in compliance with Chapter 33.2.3.5.7.1 or
33.2.3.5.7.2 by July 5, 2019.
(e) General requirements.
(1) The facility must provide and maintain
furnishings and decorations that meet the needs of the residents.
(2) The building, grounds, and equipment must
be maintained in good repair, operational, sanitary, and free of
hazards.
(3) There must be at least
one telephone (other than a pay phone) in the facility, accessible to residents
for use in making calls to summon help in case of emergency.
(4) The facility must have:
(A) floors that are free of irregularities
and are substantially level (floor areas may be at different elevations with
connecting stairs or ramps);
(B)
floors that have a resilient, nonabrasive, and slip-resistant
surface;
(C) nonabrasive carpeting,
if the area used by residents is carpeted and serves residents who lie on the
floor or ambulate with parts of their bodies, other than feet, touching the
floor; and
(D) exposed floor
surfaces and floor coverings that promote mobility in areas used by residents
and promote maintenance of sanitary conditions.
(5) Walls and ceilings must be cleanable and
in good repair.
(6) Walls and
floors must be kept free of cracks. The joint between the walls and floors is
to be maintained so as to be free of spaces which might harbor insects,
rodents, or vermin.
(7) An adequate
supply of hot water must be provided. The hot water system for resident use
must be capable of being regulated to not exceed 110 degrees Fahrenheit at the
fixtures.
(8) Draperies, curtains
(including cubicle curtains), and other similar furnishings and decorations
must be flame resistant in accordance with NFPA 701. Documentation must be kept
on file in the facility.
(9)
Wastebaskets must be of noncombustible material.
(10) An initial pressure test of facility gas
lines from the meter must be provided. Additional pressure tests will be
required when the facility has major renovations or additions where the gas
service is interrupted. All gas heating systems must be checked for proper
operation and safety prior to the heating season. Any unsatisfactory conditions
must be corrected promptly.
(11)
The IES recommendations must be followed to achieve proper illumination
characteristics and lighting levels throughout the facility. Minimum
illumination must be 10 footcandles in resident rooms during the day and 20
footcandles in corridors, staff stations, dining rooms, lobbies, toilets,
bathing facilities, laundries, stairways, and elevators during the day.
Illumination requirements for these areas apply to lighting throughout the
space and must be measured at approximately 30 inches above the floor anywhere
in the room. Minimum illumination for medication preparation or storage areas,
kitchens, and staff station desks must be 50 footcandles during the day.
Illumination requirements for these areas apply to the task performed and must
be measured on the tasks.
(12) In
addition to the required illumination (normal and emergency), the facility must
keep on hand and readily available to night staff, no less than one working
flashlight.
(13) Combustible attic
areas larger than 3,000 square feet must be divided into compartments not
exceeding 3,000 square feet or the attic area must be sprinkled. The separating
barrier must be at least one layer of 1/2-inch gypsum board on one side of
support members.