Texas Administrative Code
Title 26 - HEALTH AND HUMAN SERVICES
Part 1 - HEALTH AND HUMAN SERVICES COMMISSION
Chapter 511 - LIMITED SERVICES RURAL HOSPITALS
Subchapter G - PHYSICAL PLANT AND CONSTRUCTION REQUIREMENTS
Section 511.165 - Building with Multiple Occupancies
Universal Citation: 26 TX Admin Code § 511.165
Current through Reg. 50, No. 13; March 28, 2025
(a) Multiple hospitals located within one building.
(1)
Identifiable location. Each hospital shall conform with all the requirements
contained in Chapter 18 of the National Fire Protection Association 101, Life
Safety Code, 2012 edition (NFPA 101), relating to New Health Care Occupancies.
(A) The guest hospital shall be in one
separately contiguous location.
(B)
In no case may a person leave the guest hospital, traverse the host hospital,
and then reenter the guest hospital to access the remaining portion of the
guest hospital.
(C) A connecting
stair within the host hospital may be used to connect the vertical contiguous
areas of the guest hospital.
(D) A
guest hospital may not occupy two or more noncontiguous areas of a host
hospital that contain intervening space of the host hospital even if on the
same floor.
(E) Construction of the
host hospital building shall conform to the requirements of NFPA 101 Chapter
18, and the building shall be fully sprinklered.
(2) Separate facilities. Each limited
services rural hospital (LSRH) shall provide the following separate facilities:
(A) a nursing unit in accordance with the
requirements of §
511.163(q) of
this subchapter (relating to Spatial Requirements);
(B) an administration office with an adjacent
waiting room or waiting area;
(C) a
medical records room that conforms with the requirements of §
511.163(m) of
this subchapter;
(D) a pharmacy
suite that complies with §
511.163(s) of
this subchapter;
(E) employee
locker facilities that comply with requirements of §
511.163(f)(1) of
this subchapter;
(F) a housekeeping
room that complies with the requirements of §
511.162(d)(2)(A)(xxviii)
of this subchapter (relating to Construction
Requirements);
(G) emergency
facilities as required by §
511.163(e)(1)(A)
of this subchapter;
(H) imaging and
other diagnostic services and facilities, in accordance with §
511.46 of this chapter (relating
to Radiologic Services) and §
511.163(j) of
this subchapter respectively;
(I)
laboratory services and a laboratory suite that comply with §
511.163(k) of
this subchapter, and §
511.45 of this chapter (relating
to Laboratory Services) of this chapter respectively;
(J) where surgical services are provided, a
surgical suite in accordance with §
511.163(x) of
this subchapter;
(K) dietary
services and dietary suite, including staff dining facilities, which comply
with §
511.53 of this chapter (relating
to Dietary Services) and §
511.163(d) of
this subchapter respectively;
(L)
external signage at the building entrance that identifies each hospital;
and
(M) internal signage that
provides directions to each hospital.
(3) Means of egress. Means of egress from the
host or guest hospital shall not be through a psychiatric hospital or a crisis
stabilization unit or other area subject to locking. Means of egress may
traverse through a hospital that conforms with the requirements of §
511.161 of this subchapter
(relating to Requirements for Buildings in Which Existing Licensed Hospitals
are Located) or §
511.162 of this subchapter. Stairs
must have guardrails from the floor of the guest hospital to the level of exit
discharge in accordance with NFPA 101 §7.2.2.4.5.
(4) Additional services and facilities.
Additional services and facilities when required in each licensed hospital may
be provided by contractual agreement with the other hospital when the services
and facilities comply with the specific requirements of Subchapter C of this
chapter (relating to Operational Requirements) and §
511.163 of this subchapter. Some
services may be provided by contractual agreement with a commercial contractor;
however, the following minimal facilities shall be provided on site by the host
hospital and be located in one of the hospitals. If the host hospital fails to
provide the facilities and services, the guest hospital shall describe to the
Texas Health and Human Services Commission (HHSC) how it plans to provide
services:
(A) cart cleaning and sanitizing
services and facilities that comply with §
511.163(b) of
this subchapter;
(B) general
storage services and facilities that comply with §
511.163(h) of
this subchapter;
(C) housekeeping
rooms as required in §
511.162(d)(2)(A)(xxviii)
of this subchapter;
(D) parking facilities, in accordance with
§
511.162(c)(2) of
this subchapter;
(E) physical
therapy, occupational therapy services and facilities, or both in accordance
with §
511.57 of this chapter (relating
to Therapy Services), and §
511.163(u) of
this subchapter respectively;
(F)
patient activity facilities shall comply with the requirements for the specific
service in accordance with §
511.163 of this subchapter as
follows: mental health and chemical dependency nursing units
§511.163(n)(1) and rehabilitation therapy suite §
511.163(u)(1)(A)(i) and
(ii) of this subchapter;
(G) respiratory care services and respiratory
therapy suite that comply with §
511.70 of this chapter (relating
to Respiratory Care Services) and §
511.163(v) of
this subchapter respectively;
(H)
body-holding room that complies with §
511.163(o)(1)(D)
of this subchapter;
(I) central
sterile supply that complies with §
511.163(c) of
this subchapter respectively;
(J)
waste and waste disposal services and waste processing and storage units shall
comply with §
511.71 of this chapter (relating
to Waste and Waste Disposal); and
(K) emergency water storage requirement in
Texas Administrative Code Title 25 §133.162(d)(4)(A)(i)(VIII) shall be
required for the LSRH and the hospital and be located in either the LSRH or
other hospital.
(5)
Building systems and equipment.
(A) The
following systems shall be provided separately in each hospital at a 24-hour
staffed location.
(i) Nurses calling systems
shall be provided separately in each hospital in accordance with
§511.162(d)(5)(L) and Table 7 in §
511.169(g) of
this subchapter (relating to Tables).
(ii) Medical gas alarms shall be provided in
each hospital.
(iii) Fire alarm
annunciator panels shall be provided in each hospital so that each hospital can
monitor the other.
(iv) An
emergency generator annunciator panel shall be provided in each
hospital.
(B) Where
applicable, the following systems may serve more than one hospital provided the
systems meet the new construction requirements of §
511.162 of this subchapter.
(i) Air conditioning, heating, and
ventilating systems.
(ii) Drainage
systems.
(iii) Elevators.
(iv) Fire sprinkler systems. The guest
hospital may not be constructed in a host hospital when the host hospital is
not fully sprinklered. The host and guest hospitals shall be fully
sprinklered.
(v) Medical piping
systems.
(vi) Stand pipe
systems.
(vii) Steam
systems.
(viii) Water supply
systems, hot and cold (including emergency water storage).
(ix) Electrical service and equipment.
(I) Where applicable, the building electrical
service, lighting, essential electrical system, and fire alarm system may be a
part of or extension of those in the existing hospital, provided the existing
systems meet these requirements. The host hospital shall be responsible for
maintenance, testing and upkeep of the essential electrical system. Power and
lighting distribution panels shall be within each hospital served and comply
with the requirements of §
511.162(d)(5)(E)
of this subchapter. Electrical installation details shall conform with all
requirements contained in §
511.162(d)(5)(A)
of this subchapter.
(II) When the
existing essential electrical system is nonconforming, the following options
are available:
(-a-) a separate conforming
essential electrical system shall be provided in the guest hospital;
or
(-b-) separate transfer switches
connected to the existing on-site generator(s) shall be provided when adequate
capacity is available and the host hospital existing nonconforming system shall
be corrected. Corrections shall be made in accordance with a plan of correction
approved by HHSC.
(b) LSRHs located in buildings with licensed health care facilities other than hospitals.
(1) Before an LSRH is licensed in a building
containing other licensed health care facilities, all the requirements of this
chapter and the following requirements shall be met.
(A) Construction of the building shall
conform to the requirements of NFPA 101 Chapter 18 and the building shall be
fully sprinklered.
(B) The LSRH
shall be in one identifiable contiguous location and shall be separated
(vertically and horizontally) with two-hour fire rated noncombustible
construction from the other licensed health care facility and comply with the
requirements of this chapter.
(i) In no case
may a person leave the LSRH, traverse other licensed health care facilities,
and then reenter the LSRH to access the remaining portion of the
hospital.
(ii) A connecting stair
and elevator within the building shall be provided to connect the vertical
contiguous areas of the LSRH.
(iii)
An LSRH may not occupy two or more noncontiguous areas of other licensed health
care facilities that contain intervening space of the other licensed health
care facilities even if on the same floor.
(iv) Access to the LSRH shall be directly
from a main lobby or an elevator lobby, if on an upper floor. The required
means of egress from the LSRH may be through the other licensed health care
facility except not through a psychiatric hospital or a crisis stabilization
unit or other area subject to locking.
(I)
Each licensed facility shall be identified with external signage at the
building entrance.
(II) Internal
signage shall provide direction to the LSRH.
(v) The LSRH shall have services and
facilities separate from the other licensed health care facility. The required
facilities shall be located within the proposed LSRH proper.
(vi) Common use of facilities using
time-sharing concepts may be permitted on a case-by-case basis when the other
health care facilities comply with the requirements contained in NFPA 101
Chapter 18 and §
511.163 of this subchapter, and
provided this chapter and the other health care facility licensing regulations
allow.
(C) The equipment
and systems required in each new LSRH may be provided exclusively for the LSRH
or by contractual agreement with a licensed health care facility. The equipment
and systems shall comply with §
511.162 of this subchapter.
(i) The following equipment and systems shall
be provided for the exclusive use of the LSRH, except where noted otherwise.
(I) Where the LSRH is served by the
building's normal electrical system, the breaker serving the LSRH shall
originate in the main switchboard and shall be labeled, "Hospital Service -
Contact Hospital Representative Prior to Opening Breaker".
(II) The LSRH distribution panel board shall
be within the LSRH.
(III) An
electrical room for the distribution of type I essential electrical system
shall be provided separate from the building electrical room. The LSRH staff
shall have access at all times to the essential electrical system room and the
building's electrical room. The LSRH shall be responsible for maintenance,
testing, and upkeep of the essential electrical system. When the existing
essential electrical system owned and operated by the other licensed health
care facility is nonconforming, the following options are available:
(-a-) a separate conforming essential
electrical system shall be provided in the new LSRH; or
(-b-) separate transfer switches connected to
the existing on-site generator shall be provided when adequate capacity is
available and the other health care facility existing nonconforming system
shall be corrected. Corrections shall be made in accordance with a plan of
correction approved by HHSC.
(IV) An emergency generator may be shared
when adequate capacity is available. Separate transfer switches shall be
provided to serve the LSRH and other licensed health care facilities. The LSRH
shall be the owner of the generator, have access to the generator at all times,
and shall be responsible for maintenance, testing and upkeep of the
generator.
(V) The LSRH shall meet
the emergency water storage requirement under 25 TAC §
133.162(d)(4)(A)(i)(VIII)
and the storage shall be located within the
LSRH.
(VI) When the other licensed
health care facilities have a fire alarm control center or a main building
alarm panel at the main lobby entrance, the LSRH shall have an annunciator
panel at a 24-hour staffed location. The LSRH staff shall have access at all
times to the main building fire alarm system panels and shall be responsible
for verifying the maintenance and upkeep of such system.
(VII) Fireman's test valve for the fire
sprinkler system.
(VIII) Air
conditioning, heating, and ventilating systems.
(IX) The medical gas supply sources may be
shared provided the LSRH is owner of the medical gas system source and is
responsible for maintenance, testing and upkeep of the supply sources. The LSRH
and other occupancies shall have separate main supply shutoff valves. The LSRH
shall be provided with an alarm panel within the LSRH that monitors the medical
gas system supply source serving the other licensed health care
facilities.
(X) Medical vacuum and
medical air.
(XI) Nurses calling
systems.
(ii) Where
applicable, the following systems may be a part or extension of those in the
existing licensed health care facility, provided the existing systems meet the
requirements of this chapter for new construction.
(I) Drainage systems.
(II) The LSRH shall be served by the number
and size of elevators cabs in accordance with §
511.164 of this subchapter
(relating to Elevators, Escalators, and Conveyors). The elevators cab lighting,
control, communication, and signal systems shall be connected to the life
safety panel of the essential electrical system.
(III) The new LSRH may not be constructed in
the other health care facility when the other health care facility is not fully
sprinklered. The new LSRH and the other health care facility shall be fully
sprinklered.
(IV) Stand pipe
systems.
(V) The LSRH is
responsible for providing all backup systems (such as boilers) as required in
this chapter.
(VI) Domestic water
supply systems, hot and cold.
(VII)
Mechanical chilled and hot water systems.
(2) When an LSRH and a psychiatric
hospital share one building, the building systems and equipment may be shared
in accordance with subsection (a)(5)(B) of this section, or be provided
separately.
(c) LSRHs in buildings with non-health care occupancies.
(1) General. Before an LSRH is licensed in a
building also containing occupancies other than health care occupancies, all
requirements of this chapter and the following requirements shall be met.
(A) Construction of the building shall
conform to the requirements of NFPA 101 Chapter 18, and the building shall be
fully sprinklered.
(B) The LSRH
shall be in one identifiable contiguous location and shall be separated
(vertically and horizontally) with two-hour fire rated noncombustible
construction from the other occupancies.
(i)
In no case may a person leave the LSRH, traverse other occupancies, and then
reenter the LSRH to access the remaining portion of the LSRH.
(ii) A connecting stair and elevator within
the building shall be provided to connect the vertical contiguous areas of the
LSRH.
(iii) An LSRH may not occupy
two or more noncontiguous areas of other occupancies that contain intervening
space of the other occupancies even if on the same floor.
(C) Access to the LSRH shall be through a
dedicated LSRH lobby or from the building's main lobby. The building's main
lobby shall be part of the LSRH and shall comply with the requirements of
§
511.162 of this subchapter.
(i) External signage shall be provided at the
building entrance that identifies the LSRH.
(ii) Internal signage shall be provided to
give directions to the LSRH.
(D) The required means of egress from the
LSRH shall be independent of and shall not traverse through the other
occupancies.
(E) Stairs shall have
guardrails and handrails from the floor of the LSRH to the level of exit
discharge in accordance with NFPA 101 §7.2.2.4.5.
(2) Services and facilities. Services and
facilities shall be provided exclusively for the LSRH in accordance with
Subchapters C and F of this chapter (relating to Operational Requirements and
Fire Prevention and Safety respectively) and this subchapter. Required services
and facilities shall not be shared with the other occupancies except as noted
in paragraph (3) of this subsection.
(3) Building equipment and facilities. The
equipment and systems shall comply with §
511.162 of this subchapter.
(A) The following equipment and systems shall
be provided for the exclusive use of the LSRH except where noted otherwise.
(i) An electrical room for the distribution
of type I essential electrical system shall be provided separate from the
building electrical room. LSRH staff shall have access at all times to the
essential electrical system room and the building's electrical room or rooms.
The LSRH is responsible for maintenance, testing and upkeep of the essential
electrical system.
(ii) An
emergency generator may be shared when adequate capacity is available. Separate
transfer switches shall be provided to serve the LSRH and other building
occupancies. The LSRH shall be the owner of the generator, have access to the
generator at all times, and shall be responsible for maintenance, testing and
upkeep of the generator.
(iii)
Emergency water storage located within the LSRH.
(iv) When the building has a fire alarm
control center or a main building alarm panel at the main lobby entrance, the
LSRH shall have an annunciator panel at a 24-hour staffed location. The LSRH
staff shall have access at all times to the main building fire alarm system
panels and shall be responsible for verifying the maintenance and upkeep of
such system.
(v) Fireman's test
valve for the fire sprinkler system.
(vi) The medical gas supply sources may be
shared provided the LSRH is owner of the medical gas system supply source and
is responsible for maintenance, testing, and upkeep of the supply sources. The
LSRH and other occupancies shall have separate main supply shutoff valves. The
LSRH shall be provided with an alarm panel within the LSRH that monitors the
medical gas system serving the other occupancies.
(vii) Medical vacuum and medical
air.
(viii) Air handling units of
other occupancies may not be used for the LSRH. The LSRH air handling units may
share the supply source for other occupancies but shall not return air from the
other occupancies back to the air handling unit.
(ix) Nurses calling systems.
(B) Where applicable, the
following systems may be a part or extension of those in the existing building
occupancies provided the existing systems meet the requirements of this chapter
for new construction.
(i) Where the LSRH is
served by the building's normal electrical system, the breaker serving the LSRH
shall originate in the main switchboard and shall be labeled, "Hospital Service
- Contact Hospital Representative Prior to Opening Breaker."
(ii) The LSRH's distribution panelboard shall
be within the LSRH.
(iii) Drainage
systems.
(iv) The LSRH shall be
served by the number and size of elevators cabs in accordance with §
511.164 of this subchapter. The
elevators cab lighting, control, communication, and signal systems shall be
connected to the life safety panel of the essential electrical
system.
(v) The LSRH may not be
constructed in the other type of building occupancies when the other types of
occupancies are not fully sprinklered. The LSRH and the other occupancies shall
be fully sprinklered.
(vi) Stand
pipe systems.
(vii) Fire pump,
where applicable; LSRH staff shall have access at all times to the location of
the fire pump to verify compliance and maintenance.
(viii) The LSRH is responsible for providing
all backup systems (such as boilers) that are required in this
chapter.
(ix) Domestic water supply
systems, hot and cold.
Disclaimer: These regulations may not be the most recent version. Texas may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.