(1) Piping systems.
(A) Water supply piping systems. Water
service pipe to point of entrance to the building shall be brass pipe, copper
tube (not less than type M when buried directly), copper pipe, cast iron water
pipe, galvanized steel pipe, or approved plastic pipe. Domestic water
distribution system piping within buildings shall be brass pipe, copper pipe,
copper tube, or galvanized steel pipe. Piping systems shall be designed to
supply water at sufficient pressure to operate all fixtures and equipment
during maximum demand.
(i) Valves. Each water
service main, branch main, riser, and branch to a group of fixtures shall be
equipped with accessible and readily identifiable shutoff valves. Stop valves
shall be provided at each fixture.
(ii) Backflow preventers. Backflow preventers
(vacuum breakers) shall be installed on hose bibs, laboratory sinks, janitor
sinks, bedpan flushing attachments, and all other fixtures to which hoses or
tubing can be attached. Connections to high hazard sources, e.g., X-ray film
processors, shall be from a cold water hose bib through a reduced pressure
principle type backflow preventer (RPBFP).
(iii) Flushing valves. Flush valves installed
on plumbing fixtures shall be of a quiet operating type, equipped with
silencers.
(iv) Capacity of water
heating equipment. Water heating equipment shall have sufficient capacity to
supply water for all clinical needs based on accepted engineering practices
using actual number and type of fixtures and for heating, when
applicable.
(v) Domestic hot water
system. Hot water distribution system serving all patient care areas shall be
under constant recirculation to provide continuous hot water at each hot water
outlet.
(vi) Water temperature
measurements. Water temperatures shall be measured at hot water point of use or
at the inlet to processing equipment. Hot water temperature at point of use for
patients, staff, and visitors shall be in the range of 105 to 120 degrees
Fahrenheit.
(vii) Water storage
tanks. Domestic water storage tank(s) shall be fabricated of
corrosion-resistant metal or lined with noncorrosive material. When potable
water storage tanks (hot and cold) are used, the water shall be used and
replenished. Water shall not be stored in tanks for future use unless the water
is tested weekly for contaminates/bacteria.
(viii) Purified water supply system. Purified
water distribution system piping shall be task specific and include, but not
necessarily be limited to, polypropylene (PP), polyvinylidene fluoride (PVDF)
or polyvinyl chloride (PVC) pipe. Final installed purified water system piping
assemblies shall be UL approved and fully comply with applicable American
Society for Testing and Materials (ASTM) Fire Resistant/Smoke Density
requirements. The applicable documents are available from ASTM International,
100 Barr Harbor Drive, Post Office Box C700, West Conshohocken, Pennsylvania
19428-2959.
(ix) Dead-end piping.
Dead-end piping (risers with no flow, branches with no fixture) shall not be
installed. In any renovation work, dead-end piping shall be removed. Empty
risers, mains and branches installed for future use are permitted.
(B) Fire sprinkler systems. When
provided, fire sprinkler systems shall comply with the requirements of NFPA
101, §9.7, Automatic Sprinklers and Other Extinguishing Equipment, and the
requirements of this subparagraph. All fire sprinkler systems shall be
designed, installed, and maintained in accordance with the requirements of NFPA
13, Standard for the Installation of Sprinkler Systems, 2002 Edition, and shall
be certified as required by § 135.55(c)(1)(C) of this title (relating to
Construction, Inspections, and Approval of Project).
(C) Piped nonflammable medical gas and
clinical vacuum systems. When provided, piped nonflammable medical gas and
clinical vacuum system installations shall be designed, installed, and
certified in accordance with the requirements of NFPA 99, §5.1 for Level 1
Piped Systems and the requirements of this subparagraph.
(i) Outlets. Nonflammable medical gas and
clinical vacuum outlets shall be provided in accordance with Table 3 of §
135.56(c) of this title.
(ii)
Installer qualifications. All installations of the medical gas piping systems
including source tanks and related piping shall be done only by, or under the
direct supervision of, a holder of a master plumber license or a journeyman
plumber license with a medical gas piping installation endorsement issued by
the Texas State Board of Plumbing Examiners.
(iii) Installer tests. Prior to closing of
walls, the installer shall perform an initial pressure test, a blowdown test, a
secondary pressure test, a cross-connection test, and a purge of the piping
system as required by NFPA 99.
(iv)
Qualifications for conducting verification tests and inspections. Verification
testing shall be performed and inspected by a party, other than the installer,
installing contractor, or material vendor. Testing shall be conducted by a
medical gas system verifier registered with an acceptable organization by this
department and is technically competent and experienced in the field of medical
gas and vacuum pipeline testing and meets the requirements of The American
Society of Safety Engineers (ASSE) Personnel Standard 6030, Professional
Qualifications Standard for Medical Gas Systems. The document published by ASSE
Personnel Standard 6030, Professional Qualifications Standard for Medical Gas
Systems as referenced in this rule may be obtained by writing or calling The
American Society of Safety Engineers (ASSE) at ASSE International Office, 901
Canterbury, Suite A, Westlake, Ohio 44145, telephone (440) 885-3040.
(v) Verification tests. Upon completion of
the installer inspections and tests and after closing of walls, verification
tests of the medical gas piping systems, the warning system, and the gas supply
source shall be conducted. The verification tests shall include a
cross-connection test, valve test, flow test, piping purge test, piping purity
test, final tie-in test, operational pressure tests, and medical gas
concentration test.
(vi)
Verification test requirements. Verification tests of the medical gas piping
system and the warning system shall be performed on all new piped medical gas
systems, additions, renovations, or repaired portions of an existing system.
All systems that are breached and components that are added, renovated, or
replaced shall be inspected and appropriately tested. The breached portions of
the systems subject to inspection and testing shall be all of the new and
existing components in the immediate zone or area located upstream of the point
or area of intrusion and downstream to the end of the system or a properly
installed isolation valve.
(vii)
Warning system verification tests. Verification tests of piped medical gas
systems shall include tests of the source alarms and monitoring safeguards,
master alarm systems, and the area alarm systems.
(viii) Source equipment verification tests.
Source equipment verification tests shall include medical gas supply sources
(bulk and manifold) and the compressed air source systems (compressors, dryers,
filters, and regulators).
(ix) ASC
responsibility. Before new piped medical gas systems, additions, renovations,
or repaired portions of an existing system are put into use, ASC medical
personnel shall be responsible for ensuring that the gas delivered at the
outlet is the gas shown on the outlet label and that the proper connecting
fittings are checked against their labels.
(x) Written certification. Upon successful
completion of all verification tests, written certification for affected piped
medical gas systems and piped medical vacuum systems including the supply
sources and warning systems shall be provided by a party technically competent
and experienced in the field of medical gas pipeline testing stating that the
provisions of NFPA 99 have been adhered to and systems integrity has been
achieved. The written certification shall be submitted directly to the ASC and
the installer. A copy shall be available at final department construction
inspection.
(xi) Documentation of
medical gas and clinical vacuum outlets. Documentation of the installed,
modified, extended or repaired medical gas piping system shall be submitted to
the department by the same party certifying the piped medical gas systems. The
number and type of medical gas outlets (e.g., oxygen, vacuum, medical air,
nitrogen, nitrous oxide) shall be documented and arranged tabularly by room
numbers and room types.
(D) Medical gas storage facilities. Main
storage of medical gases may be outside or inside the ASC in accordance with
NFPA 99, §5.1. Provision shall be made for additional separate storage of
reserve gas cylinders necessary to complete at least one day's
procedures.
(E) Multiple gas
outlets on one medical gas outlet. Y-connections, "twinning", or other similar
devices shall not be used on any medical gas outlet.
(F) Waste anesthetic gas disposal (WAGD)
systems. Each space routinely used for administering inhalation anesthesia
shall be provided with a WAGD system as required by NFPA 99,
§5.1.3.7.