Current through Reg. 49, No. 38; September 20, 2024
(a) Ambulatory surgical center (ASC)
location. Any proposed new ASC shall be easily accessible to the community and
to service vehicles such as delivery trucks, ambulances, and fire protection
apparatus. No building may be converted for use as an ASC which, because of its
location, physical condition, state of repair, or arrangement of facilities,
would be hazardous to the health and safety of the patients. An ASC may be a
distinct separate part of an existing hospital, it may occupy an entire
separate independent structure, or it may be located within another building
such as an office building or commercial building.
(1) Means of egress. An ASC shall have at
least two exits remotely located in accordance with National Fire Protection
Association (NFPA) 101, Life Safety Code, 2003 Edition (NFPA 101),
§20.2.4.1. When a required means of egress from the ASC is through another
portion of the building, that means of egress shall comply with the
requirements of NFPA 101 which are applicable to the occupancy of that other
building. Such means of egress shall be open, available, unlocked,
unrestricted, and lighted at all times during the ASC hours of operation. All
documents published by National Fire Protection Association (NFPA) as
referenced in this section may be obtained by writing or calling the NFPA at
the following address or telephone number: National Fire Protection
Association, 1 Batterymarch Park, Quincy, Massachusetts 02269-9101 or
800-344-3555.
(2) Hazardous
location.
(A) Underground and above ground
hazards. A new ASC or an addition(s) to an existing ASC shall not be
constructed within 150 feet of easement boundaries or setbacks of hazardous
underground locations including but not limited to liquid butane or propane,
liquid petroleum or natural gas transmission lines, high pressure lines, and
not within the easement of high voltage electrical lines.
(B) Fire hazards. A new ASC and an addition
to an existing ASC shall not be built within 300 feet of above ground or
underground storage tanks containing liquid petroleum or other flammable
liquids used in connection with a bulk plant, marine terminal, aircraft
refueling, bottling plant of a liquefied petroleum gas installation, or near
other hazardous or hazard producing plants.
(3) Undesirable locations.
(A) Nuisance producing sites. A new ASC shall
not be located near nuisance producing sites such as industrial sites, feed
lots, sanitary landfills, or manufacturing plants which produce excessive noise
or air pollution.
(B) Flood plains.
(i) New construction. When a new ASC is
constructed in a designated 100-year flood plain, the building finished floor
elevation shall be one foot above the set base flood plain elevation. The
building shall meet all local flood code ordinances and local flood control
requirements.
(ii) Previously
licensed ASC. To obtain a license as an ASC, a previously licensed ASC and an
existing building or a portion of an existing building located in a designated
100-year flood plain shall meet the requirement of subparagraph (B)(i) of this
paragraph.
(iii) Existing ASC. ASC
required functional components shall be constructed above the designated flood
plain in a new addition to an existing ASC located in a designated 100-year
flood plain. The new addition shall meet the requirement of subparagraph (B)(i)
of this paragraph.
(b) ASC site. The ASC site shall include
paved roads, walkways, and parking in accordance with the requirements set out
in this subsection.
(1) Paved roads and
walkways.
(A) Paved roads shall be provided
within lot lines for access from public roads to the main entrance and to
service entrances.
(B) Finished
surface walkways shall be provided for pedestrians. When public transportation
or walkways serve the site, finished surface walkways or paved roads shall
extend from the public conveyance to the building entrance.
(2) Parking and disability
requirements.
(A) Parking requirements.
Off-street parking shall be provided at the minimum ratio of two spaces for
each operating room, one space for each staff member, and one visitor's space
for each operating room.
(B) Design
for the handicapped. Special considerations benefiting handicapped staff,
visitors, and patients shall be provided. Each ASC shall comply with the
Americans with Disabilities Act (ADA) of 1990, Public Law 101 - 336, 42 United
States Code, Chapter 126, and Title 36 Code of Federal Regulations, Part 1191,
Appendix A, Accessibility Guidelines for Buildings and Facilities or 16 Texas
Administrative Code, §68.20(relating to Buildings and Facilities Subject
to Compliance with the Texas Accessibility Standards), Texas Accessibility
Standards (TAS), April 1, 1994 edition, issued by the Texas Department of
Licensing and Regulation, under the Texas Architectural Barriers Act, Texas
Government Code, Chapter 469.
(c) Building design and construction
requirements. Every building and every portion thereof shall be designed and
constructed to sustain all dead and live loads in accordance with accepted
engineering practices and standards and local governing building codes. Where
there is no local governing building code, the ASC shall be constructed in
accordance with the International Building Code, 2003 edition, published by the
International Code Council, 500 New Jersey Avenue, Northwest, 6th Floor,
Washington, District of Columbia 20001-2070, (888) 422-7233.
(1) General architectural requirements. All
new construction, including conversion of an existing building to an ASC or
establishing a separately licensed ASC within another existing building, shall
comply with NFPA 101, Chapter 20, New Ambulatory Health Care Occupancies, of
the National Fire Protection Association 101, Life Safety Code, 2003 Edition
(NFPA 101), and Subchapters B and C of this chapter (relating to Fire
Prevention and Safety Requirements, and Physical Plant and Construction
Requirements, respectively). Construction documents shall be submitted to the
department in accordance with §
135.54
of this title (relating to Preparation, Submittal, Review and Approval of
Plans, and Retention of Records).
(A)
Construction types for multiple building occupancy.
(i) When an ASC is part of a larger building
which complies with NFPA 101, §20.1.6, Minimum Construction Requirements
for (fire resistance) construction type, the designated ASC shall be separated
from the remainder of the building with a minimum of one-hour fire-rated
construction.
(ii) When an ASC is
located in a multistory building of two or more stories, the entire building
shall meet the construction requirements of NFPA 101, §20.1.6.3. An ASC
shall not be located in a multistory building which does not comply with the
minimum construction requirements of NFPA 101, §20.1.6.3.
(iii) When an ASC is part of a one-story
building that does not comply with the construction requirements of NFPA 101,
§20.1.6.2, the ASC shall be separated from the remainder of the building
with a two-hour fire-rated construction. The designated ASC portion shall have
the construction type upgraded to comply with NFPA 101,
§20.1.6.2.
(B)
Special design provisions. Special provisions shall be made in the design of a
facility if located in a region where local experience shows loss of life or
extensive damage to buildings resulting from hurricanes, tornadoes, or
floods.
(2) Physical
environment. A physical environment that protects the health, welfare, and
safety of patients, personnel, and the public shall be provided in each
facility. The physical premises of the facility and those areas of the
facility's physical structure that are used by the patients (including all
stairwells, corridors, and passageways) shall meet the local building and fire
safety codes and the requirements of this chapter.
(3) Other regulations. The more stringent
standard, code or requirement shall apply when a difference in requirements for
construction exists.
(4) Exceeding
minimum requirements. Nothing in this subchapter shall be construed to prohibit
a better type of building construction, more exits, or otherwise safer
conditions than the minimum requirements specified in this
subchapter.
(5) Equivalency.
Nothing in this subchapter is intended to prevent the use of systems, methods,
or devices of equivalent or superior quality, strength, fire resistance,
effectiveness, durability, and safety to those prescribed by this subchapter,
provided technical documentation which demonstrates equivalency is submitted to
the department for approval.
(6)
Freestanding buildings (not for patient use). Separate freestanding buildings
for nonpatient use such as the heating plant, boiler plant, laundry, repair
workshops, or general storage may be of unprotected noncombustible
construction, protected noncombustible construction, or fire-resistive
construction and be designed and constructed in accordance with other occupancy
classifications requirements listed in NFPA 101.
(d) Spatial requirements.
(1) Administration and public areas.
(A) Entrance. Entrances shall be located at
grade level, be accessible to individuals with disabilities, and be protected
against inclement weather from the point of passenger loading/unloading to the
building entrance. When an ASC is located on a floor above grade level,
elevators shall be accessible and shall meet the requirements of §
135.53
of this title (relating to Elevators, Escalators, and Conveyors).
(B) Waiting area. A waiting area or lobby
shall be provided within the ASC and include having the following rooms and
items:
(i) public toilet
facilities;
(ii) telephone(s) for
public use; and
(iii) access to
potable drinking water.
(C) Reception area. A designated reception
area with desk or counter shall be provided.
(D) Interview space(s). Space shall be
provided for private interviews or family members, relating to social services,
credit, or admission.
(E) General
or individual office(s). An office(s) shall be provided for business
transactions, records, and administrative and professional staff.
(F) Medical records area. The medical records
area shall have adequate space for reviewing, dictating, sorting, or recording
records. If electronic imaging devices are employed (i.e., microfilm, digital,
or optical disc), the medical records area shall have adequate space for
transcribing records in the electronic format. Medical record storage space
shall be located within a secure designated area under direct visual
supervision of administrative staff.
(G) General storage room.
(i) A minimum of 30 square feet per operating
room shall be provided exclusive of soiled holding, sterile supplies, clean
storage, drug storage, locker rooms, and surgical equipment storage. General
storage may be located in one or more rooms or closets, and shall be located
outside of the patient treatment areas.
(ii) General storage room(s) shall be
separated from adjacent areas by fire-rated construction in accordance with the
NFPA 101, §38.3.2.1 and §38.3.2.2.
(H) Wheelchair storage space or alcove.
Storage space for wheelchairs shall be provided and shall be out of the direct
line of traffic.
(2)
Engineering services and equipment areas. Equipment rooms with adequate space
shall be provided for mechanical and electrical equipment. These areas shall be
separate from public, patient, and staff areas.
(3) Examination room. An examination room is
not required, but when provided, the room shall have:
(A) a minimum clear floor area of at least 80
square feet exclusive of fixed or moveable cabinets, counters, or shelves;
and
(B) a work counter with space
for writing and a hand washing fixture with hands-free operable
controls.
(4) Janitor's
closet. In addition to the janitor's closet exclusive to the surgery suite, a
sufficient number of janitor's closets shall be provided throughout the
facility to maintain a clean and sanitary environment. The closet shall contain
a floor receptor or service sink and storage space for housekeeping supplies
and equipment.
(5) Laboratory.
(A) General. Laboratory services shall be
provided within the ASC or through a contract or other arrangement with a
hospital or accredited laboratory.
(B) Special requirements. When the laboratory
is located on site the following minimum items shall be provided:
(i) a room with work counter, utility sink,
and storage cabinets or closet(s); and
(ii) specimen collection facilities. For dip
stick urinalysis, urine collection rooms shall be equipped with a water closet
and lavatory. Blood collection facilities shall have space for a chair, work
counter, and a hand washing fixture with hands-free operable
controls.
(C) Code
compliance. An on-site laboratory shall comply with the following codes.
(i) Construction for fire protection in
laboratories employing quantities of flammable, combustible, or other hazardous
material shall be in accordance with the National Fire Protection Association
99, Health Care Facilities, 2002 Edition, (NFPA 99).
(ii) Laboratories shall comply with the
requirements of NFPA 99, Health Care Facilities, 2002 Edition, Chapter 11, as
applicable and the requirements of NFPA 45, Standards on Fire Protection for
Laboratories Using Chemicals, 2000 Edition, as applicable.
(6) Laundry and linen processing
area(s). Laundry and linen processing may be done within the center or off site
at a commercial laundry.
(A) On-site linen
processing. When on-site linen processing is provided, soiled and clean
processing operations shall be separated and arranged to provide a one-way
traffic pattern from soiled to clean areas. The following rooms and items shall
be provided:
(i) a soiled linen processing
room which includes areas for receiving, holding, sorting, and
washing;
(ii) a clean linen
processing room which includes areas for drying, sorting, folding, and holding
prior to distribution;
(iii) supply
storage cabinets in the soiled and clean linen processing rooms;
(iv) a hand washing fixture with hands-free
operable controls within the soiled linen processing room; and
(v) a storage room for clean linen located
within the surgical suite. Clean linen storage may be combined with the clean
work room.
(B) Off-site
linen processing. When linen is processed off site, the following rooms or
items shall be provided:
(i) a storage room
for clean linen located within the surgical suite. Clean linen storage may be
combined with the clean work room; and
(ii) a soiled linen holding room or area
located within the surgical suite. Soiled linen holding may be combined with
the soiled workroom.
(7) Medical waste processing. Space and
facilities shall be provided for the safe storage and disposal of waste as
appropriate for the material being handled and in compliance with all
applicable rules and regulations.
(8) Pharmacy. A pharmacy work room or alcove
shall be provided and located separate from patient and public areas and under
the direct supervision of staff. A work counter, refrigerator, medication
storage, and locked storage for biologicals and drugs shall be provided. A hand
washing fixture with hands-free operable controls shall be located in the
pharmacy room or alcove.
(9)
Postoperative recovery suite.
(A) General. A
postoperative recovery suite shall be distinct and separate from preoperative
areas. The postoperative recovery suite shall be arranged to provide a one-way
traffic pattern from the restricted surgical corridor to the postoperative
recovery suite, and then to the extended observation rooms or
discharge.
(B) Postanesthesia care
unit. A minimum of one patient station per operating room, plus one additional
station, shall be provided.
(i) In a
multiple-bed postoperative recovery area, the clearance between the side of a
bed/gurney and a wall/partition shall be a minimum of three feet. The clearance
between sides of beds/gurneys shall be a minimum of four feet six inches. The
minimum distance at the foot of the bed/gurney shall not be less than six feet
for single load area/room or nine feet for double load area/room. Four feet of
the passage space at the foot of the bed may be shared between two
beds/gurneys. The fixed and moveable cabinets and shelves shall not encroach
upon the bed/gurney clear floor space/area.
(ii) The minimum clear floor space in a
private postoperative recovery room shall be 100 square feet exclusive of
aisles and fixed and moveable cabinets and selves. A minimum of nine feet width
shall be provided for the head wall.
(C) Patient toilet. A toilet room with a
water closet and a hand washing fixture with hands-free operable controls shall
be provided. The toilet room may be shared with the preoperative patient
holding area, if located conveniently between both areas.
(D) Hand washing fixture. One hand washing
fixture with hands-free operable controls shall be provided for every four
recovery beds or fraction thereof in open wards. Fixtures shall be uniformly
distributed. One hand washing fixture shall be provided within each single-bed
recovery room.
(E) Extended
observation rooms. Separate supervised rooms or areas may be provided for
patients who are sufficiently stabilized to leave the postanesthesia care unit,
but require additional time in the facility for observation or comfort measures
prior to being discharged.
(i) When
individual rooms are provided for extended observation, the rooms shall have an
area of at least 60 square feet. When such rooms include a bed or recliner, a
minimum clearance of three feet at the foot and on each side of the bed or
recliner shall be provided.
(ii)
When an open or ward area for extended observation is provided, the minimum
clearance from the bed or recliner to the side wall shall not be less than
three feet; and a space of four feet shall be provided at the foot of each bed
or recliner. The minimum clearance between beds or recliners shall not be less
than three feet.
(iii) A toilet
room with a water closet and a hand washing fixture with hands-free operable
controls shall be provided. The toilet room may be shared with the
postoperative recovery area, if located conveniently between both
areas.
(10)
Preoperative patient holding room.
(A)
General. A preoperative holding area shall be provided and arranged in a
one-way traffic pattern so that patients entering from outside the surgical
suite can change, gown, and move directly into the restricted corridor of the
surgical suite. The holding area shall be separate from the postoperative
recovery suite and the restricted corridor.
(B) Patient station. A minimum of one patient
station per operating room shall be provided.
(i) When individual rooms are provided, the
minimum clear floor space in a private preoperative holding room shall be 80
square feet exclusive of aisles and fixed and moveable cabinets and shelves.
The rooms shall include a bed or recliner with a minimum clearance of three
feet at the foot and on each side of the bed or recliner.
(ii) In a multiple-bed preoperative holding
area, a minimum area of 60 square feet shall be provided for each patient
station. The minimum clearance from the gurney or bed to a sidewall shall not
be less than three feet. A space of four feet shall be provided at the foot of
the gurney or bed and the minimum clearance between gurneys or beds shall not
be less than four feet six inches.
(iii) Space shall be made available for
storing and securing patient's personal effects.
(iv) One hand washing fixture with hands-free
operable controls shall be provided for every four preoperative beds or
fraction thereof in open wards. Fixtures shall be uniformly distributed. One
hand washing fixture shall be provided within each single-bed preoperative
holding room.
(C)
Patient toilet. A toilet room with handicapped accessible water closet and hand
washing facilities shall be provided. The toilet room may be shared with the
postoperative recovery suite, if located conveniently between both
areas.
(D) Duty station. A hand
washing fixture with hands-free operable controls and a counter or shelf space
for writing shall be provided for staff use within or convenient to the
preoperative area. The staff hand washing fixture with hands-free operable
controls shall be separate from and in addition to patient toilet
accommodations.
(11)
Radiology.
(A) Special requirements. When
radiology services are provided on site, the following minimum facilities shall
be provided:
(i) film processing facilities,
if used;
(ii) viewing
capabilities;
(iii) storage
facilities for exposed film, if used, located in rooms or areas constructed in
accordance with the NFPA 101, §38.3.2.1 and §38.3.2.2; and
(iv) dressing area(s) shall be required,
depending on services provided, with convenient access to toilets, and may be
shared with patient changing/preoperative rooms.
(B) Fluoroscopy room. When fluoroscopy
services are provided on site in a dedicated fluoroscopy room, a toilet room
with a water closet and a hand washing fixture with hands-free operable
controls shall be directly accessible to the room.
(12) Soiled workroom. In addition to the
soiled workroom provided in the surgical suite, a separate soiled workroom(s)
shall be required when a treatment room is provided, except as allowed in
subparagraph (B) of this paragraph.
(A)
Special requirements. The workroom(s) shall contain a clinical sink or
equivalent flushing type fixture, work counter, designated space for waste and
linen receptacles, and a hand washing fixture with hands-free operable
controls.
(B) Shared functions. The
soiled workroom required in support of a treatment room may be combined with a
surgical suite soiled work room with two means of entry. A separate door into
the soiled workroom shall serve a treatment room located outside the surgical
suite.
(13) Surgical
staff clothing change area.
(A) Surgical staff
changing rooms. Appropriately sized areas shall be provided for male and female
personnel working within the surgical suite. These areas shall contain lockers,
showers, toilets, hand washing fixtures with hands-free operable controls, and
space to change into scrub suits and boots. Separate locker/changing rooms
shall be provided for male and female staff. The shower and toilet room(s) may
be unisex. These areas shall be arranged to provide a traffic pattern so that
personnel entering from outside the surgical suite can shower, change, and move
directly into the restricted areas of the surgical suite.
(B) Surgical staff lounge. When a surgical
staff lounge is provided, the lounge shall be located to permit the use without
leaving the surgical suite and may be accessed from the clothing changing
rooms. The surgical staff lounge shall not have direct access from outside the
surgical suite. When the lounge is remote from the clothing change rooms,
toilet facilities and a hand washing fixture with hands-free operable controls
accessible from the lounge shall be provided.
(14) Sterilizing facilities. A system for
sterilizing equipment and supplies shall be provided. Sterilizing procedures
may be done on site or off site, or disposables may be used to satisfy
functional needs.
(A) Off-site sterilizing.
When sterilizing is provided off site and disposables and prepackage surgical
supplies are used, the following rooms shall be provided near the operating
room.
(i) Soiled holding room. A room for
receiving contaminated/soiled material and equipment from the operating room
shall be provided. The room shall be physically separate from all other areas
of the suite. The room shall include a work counter(s) or a table(s), clinical
sink or equivalent flushing type fixture, equipment for initial disinfection
and preparation for transport to off-site sterilizing, and a hand washing
fixture with hands-free operable controls. The soiled holding room may be
combined with the surgical suite soiled workroom.
(ii) Clean workroom. A clean workroom shall
be provided for the exclusive use of the surgical suite. The workroom shall
contain a work counter with space for receiving, disassembling and organizing
clean supplies, storage cabinets or shelving, and a hand washing fixture with
hands-free operable controls.
(iii)
Sterilizer equipment. Sterilizer equipment shall be located in a separate room
convenient to the operating room(s), in an alcove adjacent to the restricted
corridor, or in the clean workroom.
(B) On-site sterilizing facilities. When
sterilizing facilities are provided on site they shall be located near the
operating room and provide the following rooms.
(i) Receiving/decontamination room. The
receiving/decontamination room shall be physically separate from all other
areas of the surgical suite. The room shall include a work counter(s) or
table(s), clinical sink or equivalent flushing type fixture, equipment for
initial washing/disinfection, and a hand washing fixture with hands-free
operable controls. Pass-through dutch doors, windows, and washer/sterilizer
decontaminators shall serve in delivering material to the clean workroom. The
receiving/decontamination room may be combined with the surgical suite soiled
workroom.
(ii) Clean/assembly
workroom. The clean/assembly workroom shall include a counter(s) or table(s)
with space for organizing, assembling, and packaging of medical/surgical
supplies and equipment, equipment for terminal sterilizing, and a hand washing
fixture with hands-free operable controls. Clean and soiled work areas shall be
physically separated.
(iii) Sterile
storage. A storage room for clean and sterile supplies shall be provided. The
storage room shall have adequate areas and counters for breakdown of
manufacturers' clean/sterile medical/surgical supplies. This room may be
combined with the clean assembly/workroom.
(iv) Cart storage room or alcove. The storage
space for distribution carts shall be adjacent to clean and sterile storage
area(s) and close to main distribution points.
(15) Surgical suite. The surgical suite shall
be arranged to preclude unrelated traffic through the suite. The surgical suite
shall contain at least one operating room and all surgical service areas
required under subparagraph (B) of this paragraph.
(A) Operating room. The operating room(s)
shall have a clear floor area of at least 240 square feet exclusive of fixed or
moveable cabinets, counters, or shelves. The minimum clear dimension between
built-in cabinets, counters, and shelves shall be 14 feet.
(B) Surgical service areas.
(i) Restricted corridor. The restricted
corridor shall serve as the primary passageway for staff and patients within
the surgical suite. The following rooms and areas shall have direct access to
the restricted corridor:
(I) preoperative
patient holding area;
(II)
operating room(s);
(III)
postoperative recovery suite;
(IV)
soiled workroom;
(V) clean
workroom;
(VI) janitor's
closet;
(VII) equipment
storage;
(VIII) sterilizing
facilities;
(IX) anesthesia
workroom when provided; and
(X)
area for emergency crash cart.
(ii) Soiled workroom. A soiled workroom shall
be provided for the exclusive use of the surgical suite staff. The workroom
shall contain a clinical sink or equivalent flushing type fixture, work
counter, designated space for waste and linen receptacles, and a hand washing
fixture with hands-free operable controls. The soiled workroom shall not have
direct connection with operating room(s) or other sterile activity
room(s).
(iii) Clean linen storage.
A storage room or alcove shall be provided for storing clean linen.
(iv) Scrub facilities. A scrub station shall
be located in the restricted corridor within five feet of the entrance of each
operating room. One scrub station with dual faucets with hands free operable
controls may serve two operating rooms if the scrub stations are located
adjacent to the entrance of both operating rooms. Scrub facilities shall be
arranged to minimize any incidental splatter on nearby personnel, medical
equipment, or supply carts. Viewing panels shall be provided for observation of
the surgical room interior. The scrub sinks shall be recessed out of the main
traffic areas. The scrub sink alcove shall be located within the restricted
areas of the surgical suite. Scrub sinks shall not be located inside the
sterile area.
(v) Janitor's closet.
A janitor's closet shall be provided for the exclusive use of the surgical
suite. The closet shall contain a floor receptor or service sink and storage
space for housekeeping supplies and equipment.
(vi) Equipment storage. A room, alcove, or
designated area shall be provided for storing equipment and supplies used in
the surgical suite. The storage room or area shall be a minimum of 50 square
feet per operating room.
(vii)
Medical gas storage room. When provided or required by NFPA 101, a medical gas
storage room shall comply with the requirements of NFPA 99, 2002, Chapter 5,
Gas and Vacuum Systems.
(viii) Area
for emergency crash cart. An area or alcove located out of traffic and
convenient to the operating room(s) shall be provided for an emergency crash
cart.
(ix) Stretcher storage area.
An area or alcove shall be located convenient for use and out of the direct
line of traffic for the storage of stretchers as required. Stored stretchers
shall not encroach on corridor widths.
(16) Treatment room.
(A) A treatment room is not required, but
when provided, it shall be used only for minor procedures.
(B) If inhalation anesthesia is administered
in the treatment room, the room shall comply with NFPA 99, §14.4.1
requirements for an anesthetizing location.
(C) The treatment room shall have a clear
floor area of at least 120 square feet exclusive of fixed or moveable cabinets,
counters, or shelves.
(D) The
treatment room shall contain an examination table, a counter for writing, and a
hand washing fixture with hands-free operable controls.
(e) General detail and finish
requirements. Details and finishes in new construction projects, including
additions and alterations, shall be in compliance with this subsection, with
NFPA 101, Chapter 20, and with local building codes.
(1) General detail requirements.
(A) Fire safety. Fire safety features,
including smoke compartmentation, means of egress, automatic extinguishing
systems, inspections, smoking regulations, and other details relating to fire
prevention and fire protection shall comply with NFPA 101, Chapter 20. The Fire
Safety Evaluation System for Health Care Occupancies contained in the National
Fire Protection Association 101A, Alternative Approaches to Life Safety, 2001
Edition, Chapter 3, shall not be used in new building construction,
renovations, or additions to existing ASCs.
(B) Exits, corridors and doors.
(i) Number of exits. A facility shall provide
two exits remote from each other in accordance with NFPA 101, §20.2.4.1.
At least one exit door shall be accessible by an ambulance from the outside.
This door may also serve as an entry for loading or receiving goods.
(ii) Encroachment into the means of egress.
Items such as drinking fountains, telephone booths or stations, and vending
machines shall be so located as to not project into and restrict exit corridor
traffic or reduce the exit corridor width below the required minimum. Portable
equipment shall not be stored so as to project into and restrict exit corridor
traffic or reduce the exit corridor width below the required minimum.
(iii) Corridors.
(I) Public corridor. The minimum clear and
unobstructed width of a public corridor shall be at least four feet.
(II) Communicating corridor. The
communicating corridor shall be used to convey patients by stretcher, gurney,
or bed.
(III) The communicating
corridor shall link the preoperative holding area, operating room(s), and
postoperative recovery suite, and shall be continuous to at least one
exit.
(IV) The minimum clear and
unobstructed width of the communicating corridor shall be eight feet.
(iv) Door types. Doors at all
openings between corridors and rooms or spaces subject to occupancy shall be
swing type. Elevator doors are excluded from this requirement.
(v) Door swing. Doors, except doors to spaces
such as small closets which are not subject to occupancy, shall not swing into
corridors in a manner that might obstruct traffic flow or reduce the required
corridor width. Large walk-in type closets are considered as occupiable
spaces.
(vi) Patient access doors.
The minimum width of doors for patient access to examination and consultation
rooms shall be three feet. The minimum width of doors requiring access for beds
and gurneys (preoperative holding area, operating room, postoperative recovery
suite, treatment rooms) shall be three feet eight inches.
(vii) Emergency access. Rooms containing a
water closet, intended for patient use, shall be provided with at least one
door having hardware which will permit access from the outside in any
emergency. Door leaf width of such doors shall not be less than 36
inches.
(viii) Sliding doors.
Horizontal sliding doors serving an occupant load of fewer than 10 shall be
permitted. The area served by the door shall have no high hazard contents. The
door shall be readily operable from either side without special knowledge or
effort. The force required to operate the door in the direction of door travel
shall be not more than 30 pounds per foot to set the door in motion, and shall
be not more than 15 pounds per foot to close the door or open in the minimum
required width. The door assembly shall comply with any required fire
protection rating, and, where rated, shall be self-closing or automatic
closing. The sliding doors opening to the egress corridor doors shall have a
latch or other mechanism that ensures that the doors will not rebound into a
partially open position if forcefully closed. The sliding doors may have
breakaway provisions and shall be installed to resist passage of smoke. The
latching sliding panel shall have a minimum clear opening of 36 inches in the
fully open position. The fixed panels may have recessed tracks.
(ix) Fire doors. All fire doors shall be
listed by an independent testing laboratory and shall meet the construction
requirements for fire doors in National Fire Protection Association 80,
Standard for Fire Doors and Fire Windows, 1999 Edition. Reference to a labeled
door shall be construed to include labeled frame and hardware.
(C) Glazing. Glass doors, lights,
sidelights, borrowed lights, and windows located within 12 inches of a door
jamb or with a bottom-frame height of less than 18 inches and a top-frame
height of more than 36 inches above the finished floor which may be broken
accidentally by pedestrian traffic shall be glazed with safety glass or plastic
glazing material that will resist breaking and will not create dangerous
cutting edges when broken. Similar materials shall be used for wall openings in
activity areas such as recreation and exercise rooms, unless otherwise required
for fire safety. Safety glass, tempered or plastic glazing materials shall be
used for shower doors and bath enclosures, interior windows and doors. Plastic
and similar materials used for glazing shall comply with the flame spread
ratings of NFPA 101, §18.3.3.
(D) Grab bars. Grab bars shall be provided at
patient toilets and showers. The bars shall be one and one-half inches in
diameter, shall have either one and one-fourth or one and one-half inches
clearance to walls, and shall have sufficient strength and anchorage to sustain
a concentrated vertical or horizontal load of 250 pounds. Grab bars intended
for use by the disabled shall also comply with ADA requirements.
(E) Hand washing facilities. Location and
arrangement of fittings for hand washing facilities shall permit their proper
use and operation. Hand washing fixtures with hands-free controls shall be
provided in each examination room, treatment room, preoperative area,
postoperative recovery suite, extended observation room or area, soiled utility
room, fluoroscopy room, clean work room, and toilet room. Particular care shall
be given to the clearances required for blade-type operating handles.
Lavatories and hand washing facilities shall be securely anchored to withstand
an applied vertical load of not less than 250 pounds on the front of the
fixture. In addition to the specific areas noted, hand washing facilities shall
be conveniently located for staff use in rooms and areas noted under spatial
requirements in subsection (d) of this section and throughout the center where
patient care services are provided.
(F) Soap dispensers. A liquid or foam soap
dispenser shall be located at each hand washing facility.
(G) Hand drying. Provisions for hand drying
shall be included at all hand washing facilities. There shall be hot air dryers
or individual paper or cloth units enclosed in such a way as to provide
protection against dust or soil and ensure single-unit dispensing.
(H) Signage. A sign shall be posted at the
entrance to each toilet/restroom to identify the facility for public, staff, or
patient use.
(I) Ceiling heights.
The minimum ceiling height shall be eight feet six inches with the following
exceptions.
(i) Rooms containing
ceiling-mounted light fixtures or equipment. Operating rooms or other rooms
containing ceiling-mounted light fixtures or equipment shall have ceiling
heights of not less than nine feet. Additional ceiling height may be required
to accommodate special fixtures or equipment.
(ii) Minor rooms. Ceilings in storage rooms,
toilet rooms, and other minor rooms shall be not less than seven feet six
inches
(iii) Boiler rooms. Boiler
rooms shall have ceiling clearances not less than two feet six inches above the
main boiler header and connecting piping.
(iv) Overhead clearance. Suspended tracks,
rails, pipes, signs, lights, door closers, exit signs, and other fixtures that
protrude into the path of normal traffic shall not be less than six feet eight
inches above the finished floor.
(J) Areas producing impact noises. Recreation
rooms, exercise rooms, and similar spaces where impact noises may be generated
shall not be located directly over operating rooms or special procedure rooms
unless special provisions are made to minimize noise.
(K) Rooms with heat-producing equipment.
Rooms containing heat-producing equipment, such as mechanical and electrical
equipment and laundry rooms, shall be insulated and ventilated to prevent
floors of any occupied room located above it from exceeding a temperature
differential of 10 degrees Fahrenheit above the ambient room
temperature.
(L) Radiation
protection. Shielding shall be designed, tested, and approved by a medical
physicist licensed under the Medical Physics Practice Act, Occupations Code,
Chapter 602. The ASC shall obtain a certificate of registration issued by the
Radiation Safety Licensing Branch to use radiation machines.
(2) [Reserved.]
(f) General finishes requirements.
(1) Privacy screens, cubicle curtains, and
draperies.
(A) Cubicle curtains or privacy
screens shall be provided to assure patient privacy when required or requested
by a patient.
(B) Cubicle curtains,
draperies and other hanging fabrics shall be noncombustible or flame retardant
and shall pass both the small-scale and the large-scale tests of National Fire
Protection Association 701, Standard Methods of Fire Tests for Flame-Resistant
Textiles and Films, 1999 Edition. Copies of laboratory test reports for
installed materials shall be submitted to the department at the time of the
final construction inspection.
(2) Flame spread, smoke development and
noxious gases. Flame spread and smoke developed limitations of interior
finishes shall comply with Table 4 of §
135.56(d)
of this title (relating to Construction Tables) and NFPA 101, §10.2. The
use of materials known to produce large or concentrated amounts of noxious or
toxic gases shall not be used in exit accesses or in patient areas. Copies of
laboratory test reports for installed materials tested in accordance with
National Fire Protection Association 255, Standard Method of Test of Surface
Burning Characteristics of Building Materials, 2000 Edition, and National Fire
Protection Association 258, Standard Research Test Method for Determining Smoke
Generation of Solid Materials, 2001 Edition, shall be provided.
(3) Floor finishes.
(A) Flooring shall be easy to clean and have
wear resistance appropriate for the location involved. Floors that are subject
to traffic while wet (such as shower and bath areas, and similar work areas)
shall have a nonslip surface. In all areas frequently subject to wet cleaning
methods, floor materials shall not be physically affected by germicidal and
cleaning solutions. The following are acceptable floor finishes:
(i) painted concrete for mechanical,
electrical, communication rooms, and janitor's closets;
(ii) vinyl and vinyl composition tiles and
sheets tiles for offices, lobbies, administrative areas, storage, staff and
public toilet rooms, examination rooms, support spaces, and nontreatment
areas;
(iii) monolithic or seamless
flooring shall be provided for all operating rooms, special procedure rooms,
treatment rooms, patient toilet rooms, soiled workrooms, and sterilizing
facility(ies). Seamless flooring shall be impervious to water, coved and
installed integral with the base, tightly sealed to the wall, and without voids
that can harbor insects or retain dirt particles. The base shall not be less
then six inches in height. Welded joint flooring is acceptable;
(iv) marble, ceramic and quarry tile for
offices, lobbies, staff and public toilet rooms, administrative areas, wet
areas, and similar spaces;
(v)
carpet flooring for offices, lobbies, and administrative areas. Carpeting shall
not be installed in any preoperative holding, toilet rooms, treatment rooms,
examination rooms, and similar spaces; and
(vi) terrazzo for offices, lobbies,
administrative areas, and similar spaces.
(B) Threshold and expansion joint covers.
Thresholds at doorways shall not exceed 3/4 inch in height for exterior sliding
doors or 1/2 inch for other type doors. Raised thresholds and floor level
changes at accessible doorways shall be beveled with a slope no greater than
1:2. Expansion joint covers shall not exceed 1/2 inch in height and shall have
beveled edges with a slope no greater than 1:2.
(4) Wall finishes. Wall finishes shall be
smooth, washable, moisture resistant, and cleanable by standard housekeeping
practices. Wall finishes shall be in compliance with the requirements of NFPA
101, §38.3.3, relating to flame spread.
(A) Finishes at plumbing fixtures. Wall
finishes shall be water-resistant in the immediate area of plumbing
fixtures.
(B) Wet cleaning methods.
Wall finishes in areas subject to frequent wet cleaning methods shall be
impervious to water, tightly sealed, and without voids.
(5) Ceiling finishes. All occupied rooms and
spaces shall be provided with finished ceilings, unless otherwise noted.
Ceilings which are a part of a rated roof/ceiling assembly or a floor/ceiling
assembly shall be constructed of listed components and installed in accordance
with the listing. Three types of ceilings that are required in various areas of
the ASC are:
(A) ordinary ceilings. Ceilings
are required in all areas or rooms in the ASC unless otherwise noted. This
includes ceilings such as acoustical tiles installed in a metal grid which are
dry cleanable with equipment used in daily housekeeping activities such as
dusters and vacuum cleaners;
(B)
washable ceilings. When ceilings that dictate this type of cleaning or
protection for these spaces such as soil utility or soil workroom, the ceilings
shall be made of washable, smooth, moisture impervious materials such as
painted lay-in gypsum wallboard or vinyl faced acoustic tile in a metal grid;
and
(C) monolithic ceilings.
Ceilings which are monolithic from wall to wall (painted solid gypsum
wallboard), smooth and without fissures, open joints, or crevices and with a
washable and moisture impervious finish shall be provided in the operating
rooms, special procedure rooms, and sterilizing facilities.
(D) Nonceiling requirements. Finished
ceilings may be omitted in mechanical, electrical, communication rooms and
equipment spaces, shops, and similar spaces unless required for fire-resistive
purposes.
(6) Floor,
wall, and ceiling penetrations. Floor, wall, and ceiling penetrations by pipes,
ducts, and conduits, or any direct openings shall be tightly sealed to minimize
entry of dirt particles, rodents, and insects. Joints of structural elements
shall be similarly sealed.
(7)
Materials finishes. Materials known to produce noxious gases when burned shall
not be used for mattresses, upholstery, and wall finishes.
(g) General mechanical requirements. This
subsection contains requirements for mechanical systems; air conditioning,
heating and ventilating systems; steam and hot and cold water systems; and
thermal and acoustical insulation.
(1) Cost.
All mechanical systems shall be designed for overall efficiency and life cycle
costing, including operational costs. Recognized engineering practices shall be
followed to achieve the most economical and effective results except that in no
case shall patient care or safety be sacrificed for conservation.
(2) Equipment location. Mechanical equipment
may be located indoors or outdoors (when in a weatherproof enclosure), or in a
separate building(s).
(3) Vibration
isolation. Mechanical equipment shall be mounted on vibration isolators as
required to prevent unacceptable structure-borne vibration. Ducts, pipes, etc.
connected to mechanical equipment which is a source of vibration shall be
isolated from the equipment with vibration isolators.
(4) Performance and acceptance. Prior to
completion and acceptance of the facility, all mechanical systems shall be
tested, balanced, and operated to demonstrate to the design engineer or his
representative that the installation and performance of these systems conform
to the requirements of the plans and specifications.
(A) Material lists. Upon completion of the
contract, the owner shall obtain from the construction contractor parts lists
and procurement information with numbers and descriptions for each piece of
equipment.
(B) Instructions. Upon
completion of the contract, the owner shall obtain from the construction
contractor instructions in the operational use and maintenance of systems and
equipment as required.
(5) Heating, ventilating, and air
conditioning (HVAC) systems.
(A) All central
HVAC systems shall comply with and shall be installed in accordance with the
requirements of NFPA 90A, Standard for the Installation of Air Conditioning and
Ventilating Systems, 2002 Edition, or NFPA 90B, Standard for the Installation
of Warm Air Heating and Air-Conditioning Systems, 2002 Edition, as applicable
and the requirements contained in this paragraph. Air handling units serving
two or more rooms are considered to be central units.
(B) Noncentral air handling systems, i.e.,
individual room units that are used for heating and cooling purposes (e.g.,
fan-coil units, heat pump units, and packaged terminal air conditioning units)
shall be equipped with permanent (cleanable) or replaceable filters. The
filters shall have an average efficiency of 25 - 30% and an average arrestance
of 85% based on American Society of Heating, Refrigerating, and
Air-Conditioning Engineers (ASHRAE), Inc., Standard 52.2, 1999 edition, Method
of Testing General Ventilation Air Cleaning Devices for Removal Efficiency by
Particle Size. These units shall be used as air recirculating units only. All
outdoor air requirements shall be met by a separate central air handling system
with the proper filtration, as required in Table 1 of §
135.56(a)
of this title.
(C) General
ventilation requirements. All rooms and areas in the ASC shall have provision
for positive ventilation. Fans serving exhaust systems shall be located at the
discharge end and shall be conveniently accessible for service. Exhaust systems
may be combined, unless otherwise noted, for efficient use of recovery devices
required for energy conservation. The ventilation rates shown in Table 1 of
§
135.56(a)
of this title shall be used only as minimum requirements, since they do not
preclude the use of higher rates that may be appropriate.
(i) Cost reduction methods. To reduce utility
costs, facility design may utilize energy conserving procedures including
recovery devices, variable air volume, load shedding, systems shutdown, or
reduction of ventilation rates (when specifically permitted) in certain areas
when unoccupied. In no case shall patient care be jeopardized.
(ii) Economizer cycle. Mechanical systems
shall be arranged to take advantage of outside air conditions by using an
economizer cycle when appropriate to reduce heating and cooling systems loads.
Innovative design that provides for additional energy conservation while
meeting the intent of this section for acceptable patient care may be presented
to the department for consideration.
(iii) Areas requiring fully ducted systems.
Fully ducted supply, return and exhaust air for HVAC systems shall be provided
for all critical care areas, sensitive care areas, all patient care areas, all
areas requiring a sterile regimen, clean storage rooms, and where required for
fire safety purposes. Combination systems, utilizing both ducts and plenums for
movement of air in these areas, shall not be permitted. Ductwork access panels
shall be labeled.
(iv) Temperatures
and humidities. The designed capacity of the systems shall be capable of
providing the ranges of temperatures and humidities as shown in Table 1 of
§
135.56(a)
of this title.
(v) Thermometers and
humidity gauges. Each operating room, special procedure room, and postoperative
recovery suite shall have temperature and humidity indicating devices mounted
at eye level.
(vi) Outside air
intake locations.
(I) Outside air intakes
shall be located at least 25 feet from exhaust outlets of ventilating systems,
combustion equipment stacks, medical-surgical vacuum system outlets, plumbing
vents, or areas which may collect vehicular exhaust or other noxious fumes.
(Prevailing winds and proximity to other structures may require other
arrangements).
(II) Plumbing and
vacuum vents that terminate five feet above the level of the top of the air
intake may be located as close as 10 feet to the air intake.
(III) The bottom of outside air intakes
serving central systems shall be located as high as practical but at least six
feet above ground level, or if installed above the roof, three feet above the
roof level.
(vii)
Contaminated air exhaust outlets. Exhaust outlets from areas (laboratory hoods,
etc.) that exhaust contaminated air shall be above the roof and be arranged to
exhaust upward unless the air has been treated by an appropriate means where
sidewall exhaust will be allowed. Exhaust outlets from areas containing
ethylene oxide sterilizers and other contaminants, e.g., glutaraldehyde, shall
terminate not less than eight feet above the roof level (or be appropriately
labeled as "hazardous exhaust") and arranged to exhaust upward.
(viii) Directional air flow. Ventilation
systems shall be designed and balanced to provide pressure relationships
contained in Table 1 of §
135.56(a)
of this title. For reductions and shut down of ventilation systems when a room
is unoccupied, the provisions in Note 4 of Table 1 of §
135.56(a)
of this title shall be followed.
(ix) Air distribution devices. Design shall
consider turbulence and other factors of air movement to minimize airborne
particulate matter. Where extraordinary procedures require special designs, the
installation shall be reviewed on a case-by-case basis.
(I) All supply diffusers grilles shall be
located on the ceiling or on a wall near the ceiling.
(II) Air supply for the operating rooms and
special procedure rooms shall be from ceiling outlets near the center of the
work area to efficiently control air movement.
(III) A minimum of two return air inlets
located diagonally opposite from one another and near floor level shall be
provided. Bottoms of return air grilles in operating rooms and other
anesthetizing locations shall be located not more than 12 inches above the
finished floor nor less than six inches above the finished floor.
(x) Ventilation start-up
requirements. Air handling systems shall not be started or operated without the
filters installed in place. This includes the 90% and 99.97% efficiency filters
where required. This includes during construction operations. Ducts shall be
cleaned thoroughly and throughout by a National Air Duct Cleaners Association
(NADCA) certified air duct cleaning contractor when the air handling systems
have been operating without the required filters in place. When ducts are
determined to be dirty or dusty, the department shall require a written report
assuring cleanliness of duct and clean air quality.
(xi) Humidifier location. When duct
humidifiers are located upstream of the final filters, they shall be located at
least 15 feet from the filters. Duct work with duct-mounted humidifiers shall
be provided with a means of removing water accumulation. An adjustable
high-limit humidistat shall be located downstream of the humidifier to reduce
the potential of condensation inside the duct. All duct takeoffs shall be
sufficiently downstream of the humidifier to ensure complete moisture
absorption. Reservoir-type water spray or evaporative pan humidifiers shall not
be used.
(xii) Filtration
requirements. All air handling units shall be equipped with filters having
efficiencies equal to, or greater than, those specified in Table 2 of §
135.56(b)
of this title. Filter efficiencies shall be average dust spot efficiencies
tested in accordance with American Society of Heating, Refrigerating, and
Air-Conditioning Engineers (ASHRAE), Inc., Standard 52.2, 1999 edition, Method
of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by
Particle Size. All joints between filter segments, and between filter segments
and the enclosing ductwork, shall have gaskets and seals to provide a positive
seal against air leakage. Air handlers serving more than one room shall be
considered as central air handlers. All documents published by ASHRAE as
referenced in this section may be obtained by writing or calling the ASHRAE,
Inc. at the following address or telephone number: ASHRAE, 1791 Tullie Circle,
Northeast, Atlanta, Georgia 30329; telephone (404) 636-8400.
(I) Filtration requirements for air handling
units serving single rooms requiring asepsis control. Dedicated air handlers
serving only one room where asepsis control is required, such as, but not
limited to, operating rooms, special procedure rooms, and treatment rooms shall
be equipped with filters having efficiencies equal to, or greater than, those
specified for patient care areas in Table 2 of §
135.56(b)
of this title.
(II) Filtration
requirements for air handling units serving other single rooms. Dedicated air
handlers serving all other single rooms shall be equipped with nominal filters
installed at the return air system.
(III) Location of multiple filters. Where two
filter beds are required by Table 2 of §
135.56(b)
of this title, filter bed number one shall be located upstream of the air
conditioning equipment, and filter bed number two shall be downstream of the
supply air blowers, cooling and heating coils.
(IV) Location of single filters. Where only
one filter bed is required by Table 2 of §
135.56(b)
of this title, it shall be located upstream of the supply fan. Filter frames
shall be durable and constructed to provide an airtight fit with the enclosing
ductwork.
(V) Pressure monitoring
devices. A manometer or draft gauge shall be installed across each filter bed
having a required efficiency of 75% or more, including laboratory hoods
requiring high efficiency particulate air (HEPA) filters. The pressure
monitoring device shall be mounted below the ceiling line within the ASC such
that it can be observed by staff.
(D) Thermal and acoustical insulation for air
handling systems. Asbestos containing insulation materials shall not be used.
(i) Thermal duct insulation. Air ducts and
casings with outside surface temperature below the ambient dew point or
temperature above 80 degrees Fahrenheit shall be provided with thermal
insulation.
(ii) Insulation in air
plenums and ducts. When installed, linings in air ducts and equipment shall
meet the Erosion Test Method described in Underwriters Laboratories (UL),
Standard 181, relating to Factory-Made Duct Materials and Air Duct Connectors,
April 4, 1996 edition. This document may be obtained from the Underwriters
Laboratories, 333 Pfingsten Road, Northbrook, Illinois 60062-2096.
(iii) Insulation flame spread and smoke
developed ratings. Interior and exterior insulation, including finishes and
adhesives on the exterior surfaces of ducts and equipment, shall have a flame
spread rating of 25 or less and a smoke developed rating of 50 or less as
required by NFPA 90A, Chapters 4 and 5 and as determined by an independent
testing laboratory in accordance with NFPA 255, A Standard Method of Test of
Surface Burning Characteristics of Building Materials, 2000 Edition.
(iv) Linings and acoustical traps. Duct
lining and acoustical traps exposed to air movement shall not be used in ducts
serving critical care areas. This requirement shall not apply to mixing boxes
and acoustical traps that have approved nonabrasive coverings over such
linings.
(v) Frangible insulation.
Insulation of soft and spray-on types shall not be used where it is subject to
air currents or mechanical erosion or where loose particles may create a
maintenance problem or occupant discomfort.
(vi) Existing duct linings. Internal linings
shall not be used in ducts, terminal boxes, or other air system components
supplying operating rooms and the postoperative recovery suite, unless terminal
filters of at least 90% efficiency are installed downstream of
linings.
(E) Ventilation
for anesthetizing locations. When anesthesia is administered, ventilation for
anesthetizing locations, as defined in NFPA 99, §3-3, shall comply with
NFPA 99, §13.4.1.2 and any specific ventilation requirements of clauses
(i) - (iii) of this subparagraph.
(i) Smoke
removal systems for anesthetizing locations. Smoke removal systems shall be
provided in all windowless anesthetizing locations in accordance with NFPA 99,
§6.4.1.2. Supply and exhaust systems for windowless anesthetizing
locations shall be arranged to automatically exhaust smoke and products of
combustion, prevent recirculation of smoke originating within the surgical
suite, and prevent the circulation of smoke entering the system intakes,
without in either case interfering with the exhaust function of the
system.
(ii) Smoke removal systems
for surgical suites. Smoke removal systems shall be provided in all surgical
suites in accordance with NFPA 99, §6.4.1.3.
(iii) Smoke exhaust grilles. Exhaust grilles
for smoke evacuation systems shall be ceiling-mounted or wall-mounted within 12
inches of the ceiling.
(F) Location of return and exhaust air
devices. The bottoms of wall-mounted return and exhaust air openings shall be
at least four inches above the floor. Return air openings located less than six
inches above the floor shall be provided with nominal filters. All exhaust air
openings and return air openings located higher than six inches but less than
seven feet above the floor shall be protected with grilles or screens having
openings through which a one-half inch sphere will not pass.
(G) Ray protection. Ducts which penetrate
construction intended for X-ray or other ray protection shall not impair the
effectiveness of the protection.
(H) Fire damper requirements. Fire dampers
shall be located and installed in all ducts at the point of penetration of a
required two-hour or higher fire-rated wall or floor in accordance with the
requirements of NFPA 101, §18.5.2.
(I) Smoke damper requirements. Smoke dampers
shall be located and installed in accordance with the requirements of NFPA 101,
§20.3.7.3, and NFPA 90A, Chapter 5.
(i)
Protection of ducts penetrating fire and smoke partitions. Combination fire and
smoke leakage limiting dampers (Class II) shall be installed in accordance with
manufacturer's instructions for all ducts penetrating one and two-hour rated
fire and smoke partitions required by NFPA 101, §20.3.7, Subdivision of
Building Space (not required in ASCs meeting the provisions of NFPA 101,
§20.3.7.2, Exception Number 1).
(ii) Fail-safe installation. Combination
smoke and fire dampers shall close on activation of the fire alarm system by
smoke detectors installed and located as required by National Fire Protection
Association 72, National Fire Alarm Code, 2002 Edition (NFPA 72), Chapter 8;
NFPA 90A, Chapter 6; and NFPA 101, §20.3.5; the fire sprinkler system; and
upon loss of power. Smoke dampers shall not close by fan shutdown alone unless
it is a part of an engineered smoke removal system.
(iii) Interconnection of air handling fans
and smoke dampers. Air handling fans and smoke damper controls may be
interconnected so that closing of smoke dampers will not damage the
ducts.
(iv) Frangible devices. Use
of frangible devices for shutting smoke dampers is not permitted.
(J) Acceptable damper assemblies.
Only fire damper and smoke damper assemblies integral with sleeves and listed
for the intended purpose shall be acceptable.
(K) Duct access doors. Unobstructed access to
duct openings in accordance with NFPA 90A, §4.3, shall be provided in
ducts within reach and sight of every fire damper, smoke damper and smoke
detector. Each opening shall be protected by an internally insulated door which
shall be labeled externally to indicate the fire protection device located
within.
(L) Restarting controls.
Controls for restarting fans may be installed for convenient fire department
use to assist in evacuation of smoke after a fire is controlled, provided that
provisions are made to avoid possible damage to the system because of closed
dampers. To accomplish this, smoke dampers shall be equipped with remote
control devices.
(M) Make-up air.
If air supply requirements in Table 2 of §
135.56(b)
of this title do not provide sufficient air for use by exhaust hoods and safety
cabinets, filtered make-up air shall be ducted to maintain the required air
flow direction in that room. Make-up systems for hoods shall be arranged to
minimize short circuiting of air and to avoid reduction in air velocity at the
point of contaminant capture.
(h) Piping systems and plumbing fixture
requirements. All piping systems and plumbing fixtures shall be designed and
installed in accordance with the requirements of the National Standard Plumbing
Code Illustrated published by the National Association of
Plumbing-Heating-Cooling Contractors (PHCC), 2003 edition, and this paragraph.
The National Standard Plumbing Code may be obtained by writing or calling the
PHCC at the following address or telephone number: Plumbing-Heating-Cooling
Contractors, Post Office Box 6808, Falls Church, Virginia 22046; telephone
(800) 533-7694.
(1) Piping systems.
(A) Water supply piping systems. Water
service pipe to point of entrance to the building shall be brass pipe, copper
tube (not less than type M when buried directly), copper pipe, cast iron water
pipe, galvanized steel pipe, or approved plastic pipe. Domestic water
distribution system piping within buildings shall be brass pipe, copper pipe,
copper tube, or galvanized steel pipe. Piping systems shall be designed to
supply water at sufficient pressure to operate all fixtures and equipment
during maximum demand.
(i) Valves. Each water
service main, branch main, riser, and branch to a group of fixtures shall be
equipped with accessible and readily identifiable shutoff valves. Stop valves
shall be provided at each fixture.
(ii) Backflow preventers. Backflow preventers
(vacuum breakers) shall be installed on hose bibs, laboratory sinks, janitor
sinks, bedpan flushing attachments, and all other fixtures to which hoses or
tubing can be attached. Connections to high hazard sources, e.g., X-ray film
processors, shall be from a cold water hose bib through a reduced pressure
principle type backflow preventer (RPBFP).
(iii) Flushing valves. Flush valves installed
on plumbing fixtures shall be of a quiet operating type, equipped with
silencers.
(iv) Capacity of water
heating equipment. Water heating equipment shall have sufficient capacity to
supply water for all clinical needs based on accepted engineering practices
using actual number and type of fixtures and for heating, when
applicable.
(v) Domestic hot water
system. Hot water distribution system serving all patient care areas shall be
under constant recirculation to provide continuous hot water at each hot water
outlet.
(vi) Water temperature
measurements. Water temperatures shall be measured at hot water point of use or
at the inlet to processing equipment. Hot water temperature at point of use for
patients, staff, and visitors shall be in the range of 105 to 120 degrees
Fahrenheit.
(vii) Water storage
tanks. Domestic water storage tank(s) shall be fabricated of
corrosion-resistant metal or lined with noncorrosive material. When potable
water storage tanks (hot and cold) are used, the water shall be used and
replenished. Water shall not be stored in tanks for future use unless the water
is tested weekly for contaminates/bacteria.
(viii) Purified water supply system. Purified
water distribution system piping shall be task specific and include, but not
necessarily be limited to, polypropylene (PP), polyvinylidene fluoride (PVDF)
or polyvinyl chloride (PVC) pipe. Final installed purified water system piping
assemblies shall be UL approved and fully comply with applicable American
Society for Testing and Materials (ASTM) Fire Resistant/Smoke Density
requirements. The applicable documents are available from ASTM International,
100 Barr Harbor Drive, Post Office Box C700, West Conshohocken, Pennsylvania
19428-2959.
(ix) Dead-end piping.
Dead-end piping (risers with no flow, branches with no fixture) shall not be
installed. In any renovation work, dead-end piping shall be removed. Empty
risers, mains and branches installed for future use are permitted.
(B) Fire sprinkler systems. When
provided, fire sprinkler systems shall comply with the requirements of NFPA
101, §9.7, Automatic Sprinklers and Other Extinguishing Equipment, and the
requirements of this subparagraph. All fire sprinkler systems shall be
designed, installed, and maintained in accordance with the requirements of NFPA
13, Standard for the Installation of Sprinkler Systems, 2002 Edition, and shall
be certified as required by §
135.55(c)(1)(C)
of this title (relating to Construction, Inspections, and Approval of
Project).
(C) Piped nonflammable
medical gas and clinical vacuum systems. When provided, piped nonflammable
medical gas and clinical vacuum system installations shall be designed,
installed, and certified in accordance with the requirements of NFPA 99,
§5.1 for Level 1 Piped Systems and the requirements of this subparagraph.
(i) Outlets. Nonflammable medical gas and
clinical vacuum outlets shall be provided in accordance with Table 3 of §
135.56(c)
of this title.
(ii) Installer
qualifications. All installations of the medical gas piping systems including
source tanks and related piping shall be done only by, or under the direct
supervision of, a holder of a master plumber license or a journeyman plumber
license with a medical gas piping installation endorsement issued by the Texas
State Board of Plumbing Examiners.
(iii) Installer tests. Prior to closing of
walls, the installer shall perform an initial pressure test, a blowdown test, a
secondary pressure test, a cross-connection test, and a purge of the piping
system as required by NFPA 99.
(iv)
Qualifications for conducting verification tests and inspections. Verification
testing shall be performed and inspected by a party, other than the installer,
installing contractor, or material vendor. Testing shall be conducted by a
medical gas system verifier registered with an acceptable organization by this
department and is technically competent and experienced in the field of medical
gas and vacuum pipeline testing and meets the requirements of The American
Society of Safety Engineers (ASSE) Personnel Standard 6030, Professional
Qualifications Standard for Medical Gas Systems. The document published by ASSE
Personnel Standard 6030, Professional Qualifications Standard for Medical Gas
Systems as referenced in this rule may be obtained by writing or calling The
American Society of Safety Engineers (ASSE) at ASSE International Office, 901
Canterbury, Suite A, Westlake, Ohio 44145, telephone (440) 885-3040.
(v) Verification tests. Upon completion of
the installer inspections and tests and after closing of walls, verification
tests of the medical gas piping systems, the warning system, and the gas supply
source shall be conducted. The verification tests shall include a
cross-connection test, valve test, flow test, piping purge test, piping purity
test, final tie-in test, operational pressure tests, and medical gas
concentration test.
(vi)
Verification test requirements. Verification tests of the medical gas piping
system and the warning system shall be performed on all new piped medical gas
systems, additions, renovations, or repaired portions of an existing system.
All systems that are breached and components that are added, renovated, or
replaced shall be inspected and appropriately tested. The breached portions of
the systems subject to inspection and testing shall be all of the new and
existing components in the immediate zone or area located upstream of the point
or area of intrusion and downstream to the end of the system or a properly
installed isolation valve.
(vii)
Warning system verification tests. Verification tests of piped medical gas
systems shall include tests of the source alarms and monitoring safeguards,
master alarm systems, and the area alarm systems.
(viii) Source equipment verification tests.
Source equipment verification tests shall include medical gas supply sources
(bulk and manifold) and the compressed air source systems (compressors, dryers,
filters, and regulators).
(ix) ASC
responsibility. Before new piped medical gas systems, additions, renovations,
or repaired portions of an existing system are put into use, ASC medical
personnel shall be responsible for ensuring that the gas delivered at the
outlet is the gas shown on the outlet label and that the proper connecting
fittings are checked against their labels.
(x) Written certification. Upon successful
completion of all verification tests, written certification for affected piped
medical gas systems and piped medical vacuum systems including the supply
sources and warning systems shall be provided by a party technically competent
and experienced in the field of medical gas pipeline testing stating that the
provisions of NFPA 99 have been adhered to and systems integrity has been
achieved. The written certification shall be submitted directly to the ASC and
the installer. A copy shall be available at final department construction
inspection.
(xi) Documentation of
medical gas and clinical vacuum outlets. Documentation of the installed,
modified, extended or repaired medical gas piping system shall be submitted to
the department by the same party certifying the piped medical gas systems. The
number and type of medical gas outlets (e.g., oxygen, vacuum, medical air,
nitrogen, nitrous oxide) shall be documented and arranged tabularly by room
numbers and room types.
(D) Medical gas storage facilities. Main
storage of medical gases may be outside or inside the ASC in accordance with
NFPA 99, §5.1. Provision shall be made for additional separate storage of
reserve gas cylinders necessary to complete at least one day's
procedures.
(E) Multiple gas
outlets on one medical gas outlet. Y-connections, "twinning", or other similar
devices shall not be used on any medical gas outlet.
(F) Waste anesthetic gas disposal (WAGD)
systems. Each space routinely used for administering inhalation anesthesia
shall be provided with a WAGD system as required by NFPA 99,
§5.1.3.7.
(2) Steam
and hot water systems.
(A) Boilers. When
provided, the boilers shall have the capacity, based upon the net ratings as
published in The I-B-R Ratings Book for Boilers, Baseboard Radiation and Finned
Tube (commercial) by the Hydronics Institute Division of GAMA, to supply the
normal heating, hot water, and steam requirements of all systems and equipment.
The document published by the Hydronics Institute Division of GAMA as
referenced in this rule may be obtained by writing or calling the Hydronics
Institute Division of GAMA at 35 Russo Place, Post Office Box 218, Berkeley
Heights, New Jersey 07922, telephone (908) 464-8200.
(i) Boiler accessories. Boiler feed pumps,
heating circulating pumps, condensate return pumps, and fuel oil pumps shall be
connected and installed to provide normal and standby service.
(ii) Valves. Supply and return mains and
risers of cooling, heating, and process steam systems shall be valved to
isolate the various sections of each system. Each piece of equipment shall be
valved at the supply and return ends except that vacuum condensate returns need
not be valved at each piece of equipment.
(B) Boiler certification. When required, the
ASC shall ensure compliance with Texas Department of Licensing and Regulation,
Boiler Section, Texas Boiler Law, (Health and Safety Code, Chapter 755,
Boilers), which requires certification documentation for boilers to be posted
on site at each boiler installation.
(3) Drainage systems. Building sewers shall
discharge into a community sewage system. Where such a system is not available,
a facility providing sewage treatment shall conform to applicable local and
state regulations.
(A) Above ground piping.
Soil stacks and roof drains installed above ground within buildings shall be
drain-waste-vent (DWV) weight or heavier and shall be: copper pipe, copper
tube, cast iron pipe, or Schedule 40 polyvinyl chloride (PVC) pipe. Buildings
or portions of buildings remodeled to an ASC need not comply with this
requirement.
(B) Underground
piping. All underground building drains shall be cast iron soil pipe, hard
temper copper tube (DWV or heavier), acrylonitrile-butodiene-styrene (ABS)
plastic pipe (DWV Schedule 40 or heavier), or PVC pipe (DWV Schedule 40 or
heavier. Underground piping shall have at least 12 inches of earth cover or
comply with local codes. Existing buildings or portions of buildings that are
being remodeled need not comply with this subparagraph.
(C) Drains for chemical wastes. Separate
drainage systems for chemical wastes (acids and other corrosive materials)
shall be provided. Materials acceptable for chemical waste drainage systems
shall include chemically resistant borosilicate glass pipe, high silicone
content cast iron pipe, polypropylene plastic pipe, or plastic lined
pipe.
(D) Drainage and waste
piping. Drainage and waste piping shall not be installed above or below
ceilings in operating rooms, special procedure rooms, and sterile processing
rooms unless precautions are taken to protect the space below from leakage and
condensation from necessary overhead piping. Secondary protection shall be
required to drain. Any required secondary protection shall be labeled, "code
required secondary drain system" every 20 feet in a highly visible print or
label.
(4) Thermal
insulation for piping systems and equipment. Asbestos containing insulation
materials shall not be used.
(A) Insulation.
Insulation shall be provided for the following:
(i) boilers, smoke breeching, and
stacks;
(ii) steam supply and
condensate return piping;
(iii) hot
water piping and all hot water heaters, generators, converters, and storage
tanks;
(iv) chilled water,
refrigerant, other process piping, equipment operating with fluid temperatures
below ambient dew point, and water supply and drainage piping on which
condensation may occur. Insulation on cold surfaces shall include an exterior
vapor barrier; and
(v) other
piping, ducts, and equipment as necessary to maintain the efficiency of the
system.
(B) Insulation
flame spread. Flame spread shall not exceed 25 and smoke development rating
shall not exceed 50 for pipe insulation as determined by an independent testing
laboratory in accordance with NFPA 255, Standard Method of Test of Surface
Burning Characteristics of Building Materials, 2000 Edition.
(5) Plumbing fixtures. Plumbing
fixtures shall be made of nonabsorptive, acid-resistant materials and shall
comply with the requirements of the National Standard Plumbing Code, and this
paragraph.
(A) Sink and lavatory controls.
All lavatories used by medical and nursing staff and by patients shall be
trimmed with valves or electronic controls which can be operated without the
use of hands. Blade handles used for this purpose shall not be less than four
inches in length. Single lever or wrist blade devices may also be
used.
(B) Clinical sink traps.
Clinical sinks shall have an integral trap in which the upper portion of a
visible trap seal provides a water surface.
(C) Sinks for disposal of plaster of paris.
Sinks that are used for the disposal of plaster of paris shall have a plaster
trap.
(D) Back-flow or siphoning.
All plumbing fixtures and equipment shall be designed and installed to prevent
the back-flow or back-siphonage of any material into the water supply. The
over-the-rim type water inlet shall be used wherever possible. Vacuum-breaking
devices shall be properly installed when an over-the-rim type water inlet
cannot be utilized.
(E) Drinking
fountain. Each drinking fountain shall be designed so that the water issues at
an angle from the vertical, the end of the water orifice is above the rim of
the bowl, and a guard is located over the orifice to protect it from lip
contamination.
(F) Sterilizing
equipment. All sterilizing equipment shall be designed and installed to prevent
not only the contamination of the water supply but also the entrance of
contaminating materials into the sterilizing units.
(G) Hose attachment. No hose shall be affixed
to any faucet if the end of the hose can become submerged in contaminated
liquid unless the faucet is equipped with an approved, properly installed
vacuum breaker.
(H) Bedpan washers
and sterilizers. When provided, bedpan washers and sterilizers shall be
designed and installed so that both hot and cold water inlets shall be
protected against back-siphonage at maximum water level.
(I) Flood level rim clearance. The water
supply spouts for lavatories and sinks required in patient care areas shall be
mounted so that their discharge points are a minimum of five inches above the
rim of the fixture.
(J) Scrub sink
controls. Freestanding scrub sinks and lavatories used for scrubbing in
procedure rooms shall be trimmed with foot, knee, or electronic hands-free
controls. Single lever wrist blades are not acceptable at scrub
sinks.
(K) Floor drains or floor
sinks. Where floor drains or floor sinks are installed, they shall be of a type
that can be easily cleaned by removal of the cover. Removable stainless steel
mesh shall be provided in addition to a grilled drain cover to prevent entry of
large particles of waste which might cause stoppages.
(L) Under counter piping. Under counter
piping and above floor drains shall be arranged (raised) so as not to interfere
with cleaning of the floor below the equipment.
(M) Ice machines. All ice-making machines
used for human consumption shall be of the self-dispensing type. Copper tubing
shall be provided for supply connections to ice machines.
(i) General electrical
requirements. This paragraph contains common electrical and essential emergency
system requirements.
(1) Electrical
requirements. All electrical material and equipment, including conductors,
controls, and signaling devices, shall be installed in compliance with
applicable sections of the NFPA 70, National Electrical Code, 2002 Edition,
§517; NFPA 99, Chapter 14; the requirements of this subsection; and as
necessary to provide a complete electrical system. Electrical systems and
components shall be listed by nationally recognized listing agencies as
complying with available standards and shall be installed in accordance with
the listings and manufacturer's instructions.
(A) All fixtures, switches, sockets, and
other pieces of apparatus shall be maintained in a safe and working
condition.
(B) Extension cords and
cables shall not be used for permanent wiring.
(C) All electrical heating devices shall be
equipped with a pilot light to indicate when the device is in service, unless
equipped with a temperature limiting device integral with the heater.
(D) All equipment, fixtures, and appliances
shall be properly grounded in accordance with NFPA 70.
(E) Under counter electrical installations
shall be arranged (raised) to not interfere with cleaning of the floor below
the equipment.
(2)
Installation testing and certification.
(A)
Installation testing. The electrical installations, including grounding
continuity, fire alarm, nurses calling system and communication systems, shall
be tested to demonstrate that equipment installation and operation is
appropriate and functional. A written record of performance tests on special
electrical systems and equipment shall show compliance with applicable codes
and standards and shall be available to the department upon request.
(B) Grounding system testing. The grounding
system shall be tested as described in NFPA 99, §4.3.3, for patient care
areas in new or renovated work. The testing shall be performed by a qualified
electrician or their qualified electrical testing agent. The electrical
contractor shall provide a letter stating that the grounding system has been
tested in accordance with NFPA 99, the testing device use complies with NFPA
99, and whether the grounding system passed the test. The letter shall be
signed by the qualified electrical contractor, or their designated qualified
electrical testing agent, certifying that the system has been tested and the
results of the test are indicated.
(3) Electrical safeguards. Shielded isolation
transformers, voltage regulators, filters, surge suppressors, and other
safeguards shall be provided as required where power line disturbances are
likely to affect fire alarm components, data processing, equipment used for
treatment, and automated laboratory diagnostic equipment.
(4) Services and switchboards. Electrical
service and switchboards serving the required ASC components shall be installed
above the designated 100-year flood plain. Main switchboards shall be located
in separate rooms, separated from adjacent areas with one-hour fire-rated
enclosures containing only electrical switchgear and distribution panels and
shall be accessible to authorized persons only. These rooms shall be ventilated
to provide an environment free of corrosive or explosive fumes and gases, or
any flammable and combustible materials. Switchboards shall be located
convenient for use and readily accessible for maintenance as required by NFPA
70, Article 384. Overload protective devices shall operate properly in ambient
temperatures.
(5) Panelboard.
Panelboards serving normal lighting and appliance circuits shall be located on
the same floor as the circuits they serve. Panelboards serving critical branch
emergency circuits shall be located on each floor that has major users
(operating rooms, special procedure room, etc.) and may also serve the floor
above and the floor below. Panelboards serving life safety branch circuits may
serve three floors, the floor where the panelboard is located, and the floors
above and below.
(6) Wiring. All
conductors for controls, equipment, lighting and power operating at 100 volts
or higher shall be installed in metal or metallic raceways in accordance with
the requirements of NFPA 70, Article 517. All surface mounted wiring operating
at less than 100 volts shall be protected from mechanical injury with metal
raceways to a height of seven feet above the floor. Conduits and cables shall
be supported in accordance with NFPA 70, Article 300.
(7) Mechanical protection of the emergency
system. The wiring of the emergency system shall be mechanically protected by
installation in nonflexible metal raceways in accordance with NFPA 70,
§517.30(C)(3).
(8) Lighting.
(A) Lighting intensity for staff and patient
needs shall comply with guidelines for health care facilities set forth in the
Illuminating Engineering Society of North America (IESNA) Handbook, 2000
edition, published by the IESNA, 120 Wall Street, Floor 17, New York, New York
10005.
(i) Consideration shall be given to
controlling light intensity and wavelength to prevent harm to the patient's
eyes.
(ii) Approaches to buildings
and parking lots, and all spaces within buildings shall have fixtures that can
be illuminated as necessary. All rooms including storerooms, electrical and
mechanical equipment rooms, and all attics shall have sufficient artificial
lighting so that all spaces shall be clearly visible.
(iii) Consideration shall be given to the
special needs of the elderly. Excessive contrast in lighting levels that makes
effective sight adaptation difficult shall be minimized.
(B) Means of egress and exit sign lighting
intensity shall comply with NFPA 101, §§7.8, 7.9, and 7.10.
(C) Electric lamps, which may be subject to
breakage or which are installed in fixtures in confined locations when near
woodwork, paper, clothing, or other combustible materials, shall be protected
by wire guards, or plastic shields.
(D) Ceiling mounted surgical and examination
light fixtures shall be suspended from rigid support structures mounted above
the ceiling.
(E) Operating rooms
shall have general lighting in addition to local lighting provided by special
lighting units at the surgical tables. Each fixed special lighting unit at the
tables, except for portable units, shall be connected to an independent
circuit.
(F) X-ray film
illuminators for handling at least two films simultaneously shall be provided
in each operating room and special procedure room. When the entire surgical
suite is provided with digital imaging system capabilities the film
illuminators may be omitted.
(9) Receptacles. Only listed hospital grade
single-grounding or duplex-grounding receptacles shall be used in the operating
rooms, special procedure rooms, postoperative recovery suite, and all patient
care areas. This does not apply to special purpose receptacles.
(A) Installations of multiple-ganged
receptacles shall not be permitted in patient care areas.
(B) Electrical outlets powered from the
critical branch shall be provided in all patient care, procedure and treatment
locations in accordance with NFPA 99, §4.4.2.2.2.3. At least one
receptacle at each patient treatment or procedure location shall be powered
from the normal power panel. All receptacles powered from the critical branch
shall be colored red.
(C)
Replacement of malfunctioning receptacles and installation of new receptacles
powered from the critical branch in existing facilities shall be accomplished
with receptacles of the same distinct color as the existing
receptacles.
(D) All critical care
area receptacles shall be identified. The face plate for the receptacle(s)
shall have a nonremovable label or be engraved indicating the panel and circuit
number.
(E) In locations where
mobile X-ray or other equipment requiring special electrical configuration is
used, the additional receptacles shall be distinctively marked for the special
use.
(F) Each receptacle shall be
grounded to the reference grounding point by means of a green insulated copper
equipment grounding conductor in accordance with NFPA 70,
§517-13.
(G) Each operating
room and special procedure room shall have at least four duplex receptacles
located convenient to the head of the procedure table and one receptacle on the
other walls.
(H) Each work table or
counter shall have access to one duplex receptacle for every six feet of table
or counter space or fraction thereof.
(I) A minimum of one duplex receptacle in
each wall shall be installed in each work area or room other than storage or
lockers.
(J) Appliances shall be
grounded in accordance with NFPA 99, Chapter 9.
(K) Ground fault circuit interrupters (GFCI)
receptacles shall be provided for all general use receptacles located within
three feet of a wash basin or sink. When GFCI receptacles are used, they shall
be connected to not affect other devices connected to the circuit in the event
of a trip. Receptacles connected to the critical branch that may be used for
equipment that should not be interrupted do not have to be GFCI protected.
Receptacles in wet locations, as defined by NFPA 70, §§517.20 and
517.21, shall be GFCI protected regardless of the branch of the electrical
system serving the receptacle.
(10) Equipment.
(A) The following shall be powered from the
Type I essential electrical system in accordance with the requirements of NFPA
99, §§3-4.2.2.3, when such a system is required for safe operation of
the ASC referenced in paragraph (14) of this subsection.
(i) Boiler accessories including feed pumps,
heat-circulating pumps, condensate return pumps, fuel oil pumps, and waste heat
boilers shall be connected to the equipment system.
(ii) Ventilating system serving preoperative
areas, operating rooms, and the postoperative recovery suite shall be connected
to the equipment system in accordance with the requirements of NFPA 99, Chapter
3.
(B) Laser equipment
shall be installed according to manufacturer recommendations and shall be
registered with Department of State Health Services, Radiation Safety Licensing
Branch, Post Office Box 149347, Austin, Texas 78714-9347.
(C) A "kill switch" shall be provided for
disconnection of each HVAC serving the building in accordance with the
requirements of NFPA 90A, §6.2.1.
(11) Wet patient care location. Wet patient
care locations shall be protected against shock in accordance with the
requirements of NFPA 99, §4.3.2.2.9.1.
(12) Grounding requirements. Fixed electrical
equipment shall be grounded in accordance with the requirements of NFPA 99,
§4.3.3.1, and NFPA 70, Article 517.
(13) Nurses calling systems.
(A) A nurse emergency calling system shall be
installed in all toilets used by patients to summon nursing staff in an
emergency. Activation of the system shall sound an audible signal which repeats
every five seconds at a staffed location, and shall activate a distinct visible
signal outside of toilet room where the call originated. The visible and
audible signals shall be cancelable only at the patient calling station.
Activation of the system shall also activate distinct visible signals in the
clean workroom, in the soiled workroom, and if provided, in the nourishment
station.
(B) A staff emergency
assistance calling system station shall be located in each operating room,
treatment room, examination room, postoperative recovery, and preoperative
holding area to be used by staff to summon additional help in an emergency.
Activation of the system shall sound an audible signal at a staffed location,
indicate type and location of call on the system monitor, and activate a
distinct visible signal in the corridor at the door. Additional visible signals
shall be installed at corridor intersections in multi-corridor facilities.
Distinct visible and audible signals shall be activated in the clean workroom,
in soiled workroom, sterile processing room, equipment storage, and if
provided, in the nourishment station.
(14) Essential electrical system. The
essential electrical system shall comply with the requirements of NFPA 99,
§4.4.
(A) A Type 1 essential electrical
system shall be installed, maintained and tested in each ASC in accordance with
requirements of NFPA 99, §4.4; NFPA 101, §20.2.9; and National Fire
Protection Association 110, Standard for Emergency and Standby Power Systems,
2002 Edition.
(i) At least one
autoclaving/sterilizing equipment shall be connected to the emergency
electrical essential power system.
(ii) One electrical outlet connected to the
life safety branch of the electrical system shall be provided adjacent to (or
on) the emergency generator.
(iii)
The battery charger for emergency lighting at the emergency generator shall be
connected to the life safety branch of the electrical system.
(B) Fuel storage capacity for an
on-site generator for a Type 1 essential electrical system shall allow
continuous operation, under full load for eight hours of testing as required by
NFPA 99, §4.4.4.1.1.2.
(C)
When a vapor liquefied petroleum gas (LPG - natural gas) system is used, the
24-hour fuel capacity on-site is not required. The vapor withdrawal LPG system
shall require a dedicated fuel supply.
(D) When the emergency generator(s) and
electrical transformer(s) are located within the same area, they shall be
located at least 10 feet apart.
(15) Fire alarm system. A fire alarm system
which complies with NFPA 101, §20.3.4, and with NFPA 72, Chapter 6
requirements, shall be provided in each facility. The required fire alarm
system components are as follows.
(A) A fire
alarm control panel (FACP) shall be installed at a visual location such as the
main lobby. A remote fire alarm annunciator listed for fire alarm service and
installed at a continuously attended location and capable of indicating both
visual and audible alarm, trouble, and supervisory signals in accordance with
the requirements of NFPA 72 may be substituted for the FACP.
(B) Manual fire alarm pull stations shall be
installed in accordance with NFPA 101, §20.3.4.
(C) Ceiling-mounted smoke detector(s) shall
be installed in room containing the FACP when this room is not attended
continuously by staff as required by NFPA 72, §4.4.5.
(D) Smoke detectors shall be installed in air
ducts in accordance with NFPA 72, §5.14.4.2 and §5.14.5 and NFPA 90A,
§6.4.2.
(E) Smoke detectors
shall be installed in return air ducts in accordance with requirements of NFPA
72 §5.14.4.2.2 and §5.14.5 and NFPA 90A, §6.4.2.2.
(F) Fire sprinkler system water flow switches
shall be installed in accordance with requirements of NFPA 101, §9.6.2;
NFPA 13, §6.9; and NFPA 72, §8.5.3.3.3.4.
(G) Sprinkler system valve supervisory
switches shall be installed in accordance with the requirements of NFPA 72,
§6.8.5.5.
(H) A fire alarm
signal notification which complies with NFPA 101, §9.6.3, shall be
provided to alert occupants of fire or other emergency.
(I) Audible alarm indicating devices shall be
installed in accordance with the requirements of NFPA 101, §20.3.4, and
NFPA 72, §7.4.
(J) Visual fire
alarm indicating devices which comply in accordance with the requirements of
NFPA 72, §7.5, shall be provided.
(K) Devices for transmitting alarm for
alerting the local fire brigade or municipal fire department of fire or other
emergency shall be provided. The devices shall be listed for the fire alarm
service by a nationally recognized laboratory, and be installed in accordance
with such listing and the requirements of NFPA 72.
(L) Wiring for fire alarm detection circuits
and fire alarm notification circuits shall comply with requirements of NFPA 70,
Article 760.