(2) General detail and finish
requirements. Details and finishes in new construction projects, including
additions and alterations, shall be in compliance with this paragraph, with
NFPA 101, Chapter 18, with local building codes, and with any specific detail
and finish requirements for the particular unit as contained in §
133.163
of this title (relating to Spatial Requirements for New Construction).
(A) General detail requirements.
(i) Fire safety. Fire safety features,
including compartmentation, means of egress, automatic extinguishing systems,
inspections, smoking regulations, and other details relating to fire prevention
and fire protection shall comply with §
133.161
of this title (relating to Requirements for Buildings in Which Existing
Licensed Hospitals Are Located), and NFPA 101, Chapter 18 requirements for
hospitals. The Fire Safety Evaluation System for Health Care Occupancies
contained in the National Fire Protection Association 101A, Alternative
Approaches to Life Safety, 2001 edition, Chapter 3, shall not be used in new
building construction, renovations or additions to existing
hospitals.
(ii) Access to exits.
Corridors providing access to all patient, diagnostic, treatment, and sleeping
rooms and exits shall be at least eight feet in clear and unobstructed width
(except as allowed by NFPA 101, §18.2.3.4, Exceptions 1 and 2), not less
than seven feet six inches in height, and constructed in accordance with
requirements listed in NFPA 101, §18.3.6.
(iii) Corridors in other occupancies. Public
corridors in outpatient, administrative, and service areas which are designed
to other than hospital requirements and are the required means of egress from
the hospital shall be not less than five feet in width.
(iv) Encroachment into the means of egress.
Items such as drinking fountains, telephone booths or stations, and vending
machines shall be so located as to not project into and restrict exit corridor
traffic or reduce the exit corridor width below the required minimum. Portable
equipment shall not be stored so as to project into and restrict exit corridor
traffic or reduce the exit corridor width below the required minimum.
(v) Doors in means of egress. All door leaves
in the means of egress shall be not less than 44 inches wide or as otherwise
permitted for hospitals by NFPA 101, §18.2.3.6.
(vi) Sliding doors. Horizontal sliding doors
serving an occupant load of fewer than 10 shall be permitted. The area served
by the door has no high hazard contents. The door is readily operable from
either side without special knowledge or effort. The force required to operate
the door in the direction of door travel is not more than 30 pounds per foot to
set the door in motion and is not more than 15 pounds per foot to close the
door or open in the minimum required width. The door assembly complies with any
required fire protection rating, and, where rated, is self-closing or automatic
closing. The sliding doors opening to the egress corridor doors shall have a
latch or other mechanism that ensures that the doors will not rebound into a
partially open position if forcefully closed. The sliding doors may have
breakaway provisions and shall be installed to resist passage of smoke. The
latching sliding panel shall have a minimum clear opening of 41.5 inches in the
fully open position. The fixed panels may have recessed tracks.
(vii) Control doors. Designs that include
cross-corridor control doors should be avoided. When unavoidable,
cross-corridor control doors shall consist of two 44-inch wide leaves which
swing in a direction opposite from the other, or of the double acting type.
Each door leaf shall be provided with a view window.
(viii) Emergency access. Rooms containing
bathtubs, showers, and water closets, intended for patient use shall be
provided with at least one door having hardware which will permit access from
the outside in any emergency. Door leaf width of such doors shall not be less
than 36 inches.
(ix) Obstruction of
corridors. All doors which swing towards the corridor must be recessed.
Corridor doors to rooms not subject to occupancy (any room that you can walk
into and close the door behind you is considered occupiable) may swing into the
corridor, provided that such doors comply with the requirements of NFPA 101,
§7.2.1.4.4.
(x) Stair landing.
Doors shall not open immediately onto a stair without a landing. The landing
shall be 44 inches deep or have a depth at least equal to the door width,
whichever is greater.
(xi) Doors to
rooms subject to occupancy. All doors to rooms subject to occupancy shall be of
the swing type except that horizontal sliding doors complying with the
requirements of NFPA 101, §18.2.2.2.9 are permitted. Door leaves to rooms
subject to occupancy shall not be less than 36 inches wide.
(xii) Operable windows and exterior doors.
Windows that can be opened without tools or keys and outer doors without
automatic closing devices shall be provided with insect screens.
(xiii) Glazing. Glass doors, lights,
sidelights, borrowed lights, and windows located within 12 inches of a door
jamb or with a bottom-frame height of less than 18 inches and a top-frame
height of more than 36 inches above the finished floor which may be broken
accidentally by pedestrian traffic shall be glazed with safety glass or plastic
glazing material that will resist breaking and will not create dangerous
cutting edges when broken. Similar materials shall be used for wall openings in
activity areas such as recreation and exercise rooms, unless otherwise required
for fire safety. Safety glass, tempered or plastic glazing materials shall be
used for shower doors and bath enclosures, interior windows and doors. Plastic
and similar materials used for glazing shall comply with the flame spread
ratings of NFPA 101, §18.3.3.
(xiv) Fire doors. All fire doors shall be
listed by an independent testing laboratory and shall meet the construction
requirements for fire doors in National Fire Protection Association 80,
Standard for Fire Doors and Fire Windows, 1999 edition. Reference to a labeled
door shall be construed to include labeled frame and hardware.
(xv) Grab bars. Grab bars shall be provided
at patient toilets, showers and tubs. The bars shall be one and one-half inches
in diameter, shall have either one and one-fourth or one and one-half inches
clearance to walls, and shall have sufficient strength and anchorage to sustain
a concentrated vertical or horizontal load of 250 pounds. Grab bars are not
permitted at bathing and toilet fixtures in mental health and chemical
dependency units unless designed and installed to eliminate the possibility of
patients harming themselves. Grab bars intended for use by the disabled shall
also comply with ADA requirements.
(xvi) Soap dishes. Soap dishes shall be
provided at all showers and bathtubs.
(xvii) Hand washing facilities. Location and
arrangement of fittings for hand washing facilities shall permit their proper
use and operation. Hand washing fixtures with hands-free operable controls
shall be provided within each workroom, examination, and treatment room.
Hands-free includes blade-type handles, and foot, knee, or sensor operated
controls. Particular care shall be given to the clearances required for
blade-type operating handles. Lavatories and hand washing facilities shall be
securely anchored to withstand an applied vertical load of not less than 250
pounds on the front of the fixture. In addition to the specific areas noted,
hand washing facilities shall be provided and conveniently located for staff
use throughout the hospital where patient care contact occurs and services are
provided.
(xviii) Soap dispensers.
A liquid or foam soap dispenser shall be located at each hand washing
facility.
(xix) Alcohol-based hand
rubs. Alcohol-based hand rubs (ABHRs) are considered flammable. When used, the
ABHRs shall meet the following requirements:
(I) The dispensers may be installed in a
corridor so long as the corridor width is six feet or greater. The dispensers
shall be installed at least four feet apart.
(II) The maximum individual dispenser fluid
capacity is 1.2 liters for dispensers in rooms, corridors, and areas open to
corridors, and 2.0 liters for dispensers in suites of rooms.
(III) The dispensers shall not be installed
over or directly adjacent to electrical outlets and switches.
(IV) Dispensers installed directly over
carpeted surfaces shall be permitted only in sprinklered smoke
compartments.
(V) Each smoke
compartment may contain a maximum aggregate of 10 gallons of ABHR solution in
dispensers and a maximum of five gallons in storage.
(xx) Hand drying. Provisions for hand drying
shall be included at all hand washing facilities except scrub sinks. There
shall be hot air dryers or individual paper or cloth units enclosed in such a
way as to provide protection against dust or soil and ensure single-unit
dispensing.
(xxi) Mirrors. Mirrors
shall not be installed at hand washing fixtures where asepsis control and
sanitation requirements would be lessened by hair combing. Mirrors may be
installed in patient rooms, patient toilet rooms, lockers, and public toilet
rooms.
(xxii) Ceiling heights. The
minimum ceiling height shall be seven feet six inches with the following
exceptions.
(I) Boiler rooms. Boiler rooms
shall have ceiling clearances not less than two feet six inches above the main
boiler header and connecting piping.
(II) Rooms with ceiling-mounted equipment.
Rooms containing ceiling-mounted equipment shall have the ceiling height
clearance increased to accommodate the equipment or fixtures.
(III) Overhead clearance. Suspended tracks,
rails, pipes, signs, lights, door closers, exit signs, and other fixtures that
protrude into the path of normal traffic shall not be less than six feet eight
inches above the finished floor.
(xxiii) Areas producing impact noises.
Recreation rooms, exercise rooms, and similar spaces where impact noises may be
generated shall not be located directly over patient bed area or operating
rooms unless special provisions are made to minimize noise.
(xxiv) Noise reduction. Noise reduction
criteria in accordance with the Table 1 in §
133.169(a)
of this title (relating to Tables) shall apply to partitions, floor, and
ceiling construction in patient areas.
(xxv) Rooms with heat-producing equipment.
Rooms containing heat-producing equipment such as heater rooms, laundries, etc.
shall be insulated and ventilated to prevent any occupied floor surface above
from exceeding a temperature differential of 10 degrees Fahrenheit above the
ambient room temperature.
(xxvi)
Chutes. Linen and refuse chutes shall comply with the requirements of National
Fire Protection Association 82, Standard on Incinerators, Waste and Linen
Handling Systems and Equipment, 2004 edition, and NFPA 101,
§18.5.4.
(xxvii) Thresholds
and expansion joint covers. Thresholds and expansion joint covers shall be
flush or not more than one-half inch above the floor surface to facilitate the
use of wheelchairs and carts. Expansion and seismic joints shall be constructed
to restrict the passage of smoke and fire and shall be listed by a nationally
recognized testing laboratory.
(xxviii) Housekeeping room.
(I) In addition to the housekeeping room(s)
required in certain departments, sufficient housekeeping rooms shall be
provided throughout the hospital as required to maintain a clean and sanitary
environment.
(II) Each housekeeping
room shall contain a floor receptor or service sink and storage space for
housekeeping equipment and supplies.
(B) General finish requirements.
(i) Cubicle curtains and draperies.
(I) Cubicle curtains, draperies and other
hanging fabrics shall be noncombustible or flame retardant and shall pass both
the small scale and the large-scale tests of National Fire Protection
Association 701, Standard Methods of Fire Tests for Flame-Resistant Textiles
and Films, 1999 edition. Copies of laboratory test reports for installed
materials shall be submitted to the department at the time of the final
construction inspection.
(II)
Cubicle curtains shall be provided to assure patient privacy.
(ii) Flame spread, smoke
development and noxious gases. Flame spread and smoke developed limitations of
interior finishes shall comply with Table 2 of §
133.169(b)
of this title and NFPA 101, §10.2. The use of materials known to produce
large or concentrated amounts of noxious or toxic gases shall not be used in
exit accesses or in patient areas. Copies of laboratory test reports for
installed materials tested in accordance with National Fire Protection
Association 255, Standard Method of Test of Surface Burning Characteristics of
Building Materials, 2000 edition, and National Fire Protection Association 258,
Standard Research Test Method for Determining Smoke Generation of Solid
Materials, 2001 edition, shall be provided.
(iii) Floor finishes. Flooring shall be easy
to clean and have wear resistance appropriate for the location involved. Floors
that are subject to traffic while wet (such as shower and bath areas, kitchens,
and similar work areas) shall have a nonslip surface. In all areas frequently
subject to wet cleaning methods, floor materials shall not be physically
affected by germicidal and cleaning solutions. The following are acceptable
floor finishes:
(I) painted
concrete;
(II) vinyl and vinyl
composition tiles and sheets;
(III)
monolithic or seamless flooring. Where required, seamless flooring shall be
impervious to water, coved and installed integral with the base, tightly sealed
to the wall, and without voids that can harbor insects or retain dirt
particles. The base shall not be less then six inches in height. Welded joint
flooring is acceptable;
(IV)
ceramic and quarry tile;
(V) wood
floors. Wood floors subject to frequent cleaning methods shall be avoided. When
wood floors are used, the floor shall be tightly sealed, without voids and the
joints shall be impervious to water;
(VI) carpet flooring. Carpeting installed in
intensive care units, nurseries, patient rooms and similar patient care areas
shall be treated to prevent bacterial and fungal growth;
(VII) terrazzo; and
(VIII) poured in place floors.
(iv) Wall finishes. Wall finishes
shall be smooth, washable, moisture resistant, and cleanable by standard
housekeeping practices. Wall finishes shall comply with requirements contained
in Table 2 of §
133.169(b)
of this title, and NFPA 101, §18.3.3.
(I) Wall finishes shall be water-resistant in
the immediate area of plumbing fixtures.
(II) Wall finishes subject to frequent wet
cleaning methods shall be impervious to water, tightly sealed and without
voids.
(v) Floor, wall
and ceiling penetrations. Floor, wall and ceiling penetrations by pipes, ducts,
and conduits or any direct openings shall be tightly sealed to minimize entry
of dirt particles, rodents and insects. Joints of structural elements shall be
similarly sealed.
(vi) Ceiling
types. Ceilings which are a part of a rated roof/ceiling assembly or a
floor/ceiling assembly shall be constructed of listed components and installed
in accordance with the listing. Three types of ceilings that are required in
various areas of the hospital are:
(I)
Ordinary ceilings. Ceilings such as acoustical tiles installed in a metal grid
which are dry cleanable with equipment used in daily housekeeping activities
such as dusters and vacuum cleaners.
(II) Washable ceilings. Ceilings that are
made of washable, smooth, moisture impervious materials such as painted lay-in
gypsum wallboard or vinyl faced acoustic tile in a metal grid.
(III) Monolithic ceilings. Ceilings which are
monolithic from wall to wall (painted solid gypsum wallboard), smooth and
without fissures, open joints, or crevices and with a washable and moisture
impervious finish.
(vii)
Special construction. Special conditions may require special wall and ceiling
construction for security in areas such as storage of controlled substances and
areas where patients are likely to attempt suicide or escape.
(viii) Flammable anesthetizing locations.
Flammable anesthetic locations in which flammable anesthetic agents are stored
or administered shall comply with Annex E of the National Fire Protection
Association 99, Standard for Health Care Facilities, 2002 edition (NFPA
99).
(ix) Materials finishes.
Materials known to produce noxious gases when burned shall not be used for
mattresses, upholstery, and wall finishes.
(x) Signage. A sign shall be posted at the
entrance to each toilet/restroom to identify the facility for public, staff or
patient use. Signs are not required for patient room bathrooms.