Current through Reg. 49, No. 38; September 20, 2024
(a) Any proposed new facility shall be easily
accessible to the community and to service vehicles such as delivery trucks,
ambulances, and fire protection apparatus. No building may be converted for use
as a facility which, because of its location, physical condition, state of
repair, or arrangement of facilities, would be hazardous to the health and
safety of the patients.
(1) A facility shall
have at least two exits remotely located in accordance with National Fire
Protection Association (NFPA) 101, Life Safety Code, 2003 Edition (NFPA 101),
§20.2.4.1. When a required means of egress from the facility is through
another portion of the building, that means of egress shall comply with the
requirements of NFPA 101 which are applicable to the occupancy of that other
building. Such means of egress shall be open, available, unlocked,
unrestricted, and lighted at all times during the facility hours of operation.
All documents published by National Fire Protection Association (NFPA) as
referenced in this section may be obtained by writing or calling the NFPA at
the following address or telephone number: National Fire Protection
Association, 1 Batterymarch Park, Quincy, Massachusetts 02269-9101 or (800)
344-3555. NFPA documents are also available for public inspection during
regular working hours at the offices of Architectural Review Group, Texas
Department of State Health Services, 1100 West 49th Street, Austin, Texas
78756-3199.
(2) Hazardous
locations.
(A) A new facility or an addition
to an existing facility shall not be constructed within 150 feet of easement
boundaries or setbacks of hazardous underground locations including but not
limited to liquid butane or propane, liquid petroleum or natural gas
transmission lines, high pressure lines, and not within the easement of high
voltage electrical lines. Municipality's main natural gas lines in right-of
ways serving dwellings and gas lines on property servicing gas meter(s) under
this provision are not consider natural high pressure lines.
(B) A new facility and an addition to an
existing facility shall not be built within 300 feet of above ground or
underground storage tanks containing liquid petroleum or other flammable
liquids used in connection with a bulk plant, marine terminal, aircraft
refueling, bottling plant of a liquefied petroleum gas installation, or near
other hazardous or hazard producing plants.
(3) Undesirable locations.
(A) In lieu of local codes, a new facility
shall not be located closer than 1500 feet to nuisance producing industrial
sites, feed lots, sanitary landfills, or manufacturing plants producing
excessive noise or air pollution.
(B) Flood plains.
(i) When a new facility is constructed in a
designated 100-year flood plain, the building finished floor elevation shall be
one foot above the set base flood plain elevation. The building shall meet all
local flood code ordinances and local flood control requirements.
(ii) To obtain a license as a facility, a
previously licensed facility and an existing building or a portion of an
existing building located in a designated 100-year flood plain shall meet the
requirement of clause (i) of this subparagraph.
(iii) Facility required functional components
shall be constructed above the designated flood plain in a new addition to an
existing facility located in a designated 100-year flood plain. The new
addition shall meet the requirement of clause (i) of this
subparagraph.
(iv) Currently
licensed facilities located within a designated 100-year flood plain are
exempted from these requirements for renovations and repairs.
(b) The
facility site shall include paved roads, walkways, and parking in accordance
with the requirements set out in this subsection.
(1) Paved roads and walkways.
(A) Paved roads shall be provided within lot
lines for access from public roads to the main entrance and to service
entrances.
(B) Finished surface
walkways shall be provided for pedestrians. When public transportation or
walkways serve the site, finished surface walkways or paved roads shall extend
from the public conveyance to the building entrance.
(2) Parking and disability requirements.
(A) Off-street parking shall be available for
visitors, employees, and staff. Parking structures directly accessible from a
facility shall be separated with two-hour fire rated noncombustible
construction. When used as required means of egress for facility occupants,
parking structures shall comply with National Fire Protection Association 88A,
Standard for Parking Structures, 2002 edition. This requirement does not apply
to freestanding parking structures.
(B) In the absence of local code, one parking
space shall be provided for each staff member on duty, plus one space for each
three treatment or examination stations, one space for each three diagnostic
rooms and one visitor's space for every five treatment/exam/diagnostic
stations/rooms. Parking facilities shall be increased accordingly when the size
of existing facilities is increased.
(C) When on-street parking is available and
acceptable to the local authorities having jurisdiction, the numbers of parking
spaces may be reduced accordingly and shall meet the requirement of
subparagraph (B) of this paragraph.
(D) Special considerations benefiting
disabled staff, visitors, and patients shall be provided. Each facility shall
comply with the Americans with Disabilities Act (ADA) of 1990,
Public Law
101-336, 42 United States Code, Chapter 126, and
Title 36 Code of Federal Regulations, Part 1191, Appendix A, Accessibility
Guidelines for Buildings and Facilities or 16 TAC, §
68.20(relating
to Buildings and Facilities Subject to Compliance with the Texas Accessibility
Standards), Texas Accessibility Standards (TAS), April 1, 1994 edition, issued
by the Texas Department of Licensing and Regulation, under the Texas
Architectural Barriers Act, Government Code, Chapter 469.
(c) Every building and every
portion thereof shall be designed and constructed to sustain all dead and live
loads in accordance with accepted engineering practices and standards and the
local governing building codes. Where there is no local governing building
code, the facility shall be constructed in accordance with the International
Building Code, 2003 edition, published by the International Code Council, 500
New Jersey Avenue, Northwest, 6th Floor, Washington, District of Columbia
20001-2070, (888) 422-7233.
(1) All new
construction, including conversion of an existing building to a facility or
establishing a separately licensed facility within another existing building,
shall comply with NFPA 101, Chapter 20, New Ambulatory Health Care Occupancies,
of the National Fire Protection Association 101, Life Safety Code, 2003 edition
(NFPA 101), and Subchapters F and G of this chapter (relating to Fire
Prevention and Safety Requirements, and Physical Plant and Construction
Requirements, respectively). Construction documents shall be submitted to the
department in accordance with §
131.146
of this title (relating to Preparation, Submittal, Review and Approval of
Plans, and Retention of Records).
(A)
Construction types for multiple building occupancy.
(i) When a facility is part of a larger
building which complies with NFPA 101, §20.1.6, Minimum Construction
Requirements for (fire resistance) construction type, the designated facility
shall be separated from the remainder of the building with a minimum of
one-hour fire rated construction.
(ii) When a facility is located in a
multistory building of two or more stories, the entire building shall meet the
construction requirements of NFPA 101, §20.1.6.3. A facility shall not be
located in a multistory building which does not comply with the minimum
construction requirements of NFPA 101, §20.1.6.3.
(iii) When a facility is part of a one-story
building that does not comply with the construction requirements of NFPA 101,
§20.1.6.2, the facility shall be separated from the remainder of the
building with a 2-hour fire rated construction. The designated facility portion
shall have the construction type upgraded to comply with NFPA 101,
§20.1.6.2.
(B)
Special provisions shall be made in the design of a facility if located in a
region where local experience shows loss of life or extensive damage to
buildings resulting from hurricanes, tornadoes, or floods.
(2) A facility shall provide a physical
environment that protects the health, safety, and welfare of patients,
personnel, and the public.
(3) The
more stringent standard, code or requirement shall apply when a difference in
requirements for construction exists.
(4) Nothing in this subchapter shall be
construed to prohibit a better type of building construction, more exits, or
otherwise safer conditions than the minimum requirements specified in this
subchapter.
(5) Nothing in this
subchapter is intended to prevent the use of systems, methods, or devices of
equivalent or superior quality, strength, fire resistance, effectiveness,
durability, safety to health and welfare of individuals, and safety to those
prescribed by this subchapter, provided technical documentation which
demonstrates equivalency is submitted to the department for approval.
(6) Separate freestanding buildings for
non-patient use such as the heating plant, boiler plant, laundry, repair
workshops, or general storage may be of unprotected noncombustible
construction, protected noncombustible construction, or fire-resistive
construction and be designed and constructed in accordance with other occupancy
classifications requirements listed in NFPA 101.
(d) Spatial requirements.
(1) Administration and public areas.
(A) A primary entrance shall be located at
grade level and be accessible to individuals with disabilities, and protected
against inclement weather with a canopy from the point of passenger loading and
unloading to the building entrance. The canopy shall at least extend over the
passenger side of the vehicle to minimally protect the patient from inclement
weather.
(B) A main lobby shall be
located at the primary entrance and shall include a reception and information
counter or desk, waiting space(s), private interview space/alcove, public
toilet facilities located convenient to the lobby/waiting area, public
telephones, drinking fountain(s), bottled water or water cooler, and storage
room or alcove for wheelchairs. Private interview space/alcove may be omitted
if all interviews are conducted in treatment or exam rooms.
(C) General office(s) space shall be provided
for business transactions, medical and financial records, and administrative
and professional staff on site or off site.
(D) Storage. Storage room or closet for
office equipment and supplies shall be provided and located outside of the
patient treatment areas.
(E) When a
facility is fully digitalized, an IT closet shall be provided for computer
servers. When the facility is not fully digitalized, the facility shall provide
an area for storage of clinical records which is separate from patient
treatment and diagnostic areas, and shall be secured from unauthorized
access.
(2) Emergency
entrance and signage.
(A) A separate
ambulance entrance at grade level shall be well-illuminated, identified by
sign(s), and protected from inclement weather. The ambulance entry shall have a
drive under canopy for protection from inclement weather. The primary and
ambulance entry to permit discharge of patients from automobiles and ambulances
shall be paved. Parking shall be provided near and convenient to the pedestrian
primary entrance.
(B) Emergency
entry signage. An emergency sign shall be provided at the entry from the public
road(s) or street(s) serving the site. The emergency sign at the entry to the
site shall be illuminated and connected to the emergency essential electrical
system. Additional sign(s) on-site may be required to direct patients to the
emergency treatment area entrance when the emergency treatment area is not
visible from the site entry. The letters on the entry sign shall be red or
white with a contrasting background, all capitalized, at least eight inches in
height, and include an arrow indicating direction.
(C) A facility that is not in continuous
operation 24 hours per day and 7 days per week shall display clearly visible
signage at the main entry and ambulance entry points of the facility. The
signage letter size shall be readable and not smaller than half an inch in
height. The signage shall provide the information required under §
131.22(c)
of this title (relating to Classifications of Facilities).
(D) A facility that is not in continuous
operation shall comply with the requirements under §
133.22(d)
of this title.
(3)
Emergency suite.
(A) Control station/nurse
station shall be located to permit staff observation and control of access to
treatment room(s), exam rooms, pedestrian and ambulance entrances, and public
waiting area(s). Video cameras may be substituted for direct visual observation
for pedestrian and ambulance entrances, and public waiting area(s). The nurse
station shall contain cabinets, work counter, and a hand washing fixture with
hands-free operable controls. The counter height shall not exceed 42 inches.
The nurse station may be combined with or include centers for reception and
communication.
(B) When a dedicated
triage space/room is provided, it shall include a counter with a hand washing
fixture with hands-free operable controls.
(C) Charting and dictation space for
physician's space may be in a separate room or alcove or control station/nurse
station. Suitable space shall be provided when computers are used for the
clinical records.
(D) As a minimum
requirement, all facilities shall provide at least one emergency treatment room
to handle emergencies. The room(s) and facilities shall meet the following
requirements.
(i) The emergency treatment room
for a single patient shall have a minimum clear area of 120 square feet clear
floor area exclusive of fixed and movable cabinets and shelves. The minimum
clear room dimension exclusive of fixed cabinets and built-in shelves shall be
10 feet. The emergency treatment room shall contain cabinets, work counter,
examination light, and a hand washing fixture with hands-free operable
controls.
(ii) When a multiple-bed
emergency treatment room is provided, the clearance between the side of a
bed/gurney and a wall/partition shall be a minimum of four feet. The clearance
between the sides of beds/gurneys shall be a minimum of six feet. The minimum
distance at the foot of the bed/gurney shall not be less than seven feet for
single load area/room or ten feet for double load area/room. Four feet of the
passage space at the foot of the bed may be shared between two beds/gurneys.
The multiple-bed emergency treatment room shall contain cabinets, medication
storage, work counter, examination light, and a hand washing fixture with
hands-free operable controls. The fixed and movable cabinets and shelves shall
not encroach upon the bed/gurney clear floor space/area. The requirements of
this clause are illustrated in Table (5), Diagram (A) of §
131.148(e)
of this title (relating to Tables).
(iii) One hand washing fixture with
hands-free operable controls shall be provided for each bed/gurney location.
One hand washing fixture may serve two beds/gurneys if distributed
appropriately between the two.
(iv)
Storage space shall be provided within the room or suite and be under staff
control for general medical-surgical emergency supplies and medications.
Adequate space shall be provided for emergency equipment such as emergency
treatment trays, ventilator, defibrillator, splints, cardiac monitor,
etc.
(E) As a minimum
requirement, all facilities shall provide at least one exam room. The room(s)
and facilities shall meet the following requirements.
(i) The exam room for a single patient shall
have a minimum clear area of 100 square feet clear floor area exclusive of
fixed and movable cabinets and shelves. The minimum clear room dimension
exclusive of fixed cabinets and built-in shelves shall be 9 feet. The
examination room shall contain cabinets, work counter, examination light, and a
hand washing fixture with hands-free operable controls.
(ii) When a multiple-bed exam room is
provided, the clearance between the side of the bed/gurney and a wall/partition
shall be a minimum of 3 feet. The clearance between sides of the beds/gurneys
shall be a minimum of 6 feet. The minimum distance at the foot of the
bed/gurney shall not be less than seven feet for single load area/room or 10
feet for double load area/room. Four feet of the passage space at the foot of
the bed may be shared between 2 beds/gurneys. The multiple-bed examination room
shall contain cabinets, work counters, and a hand washing fixture with
hands-free operable controls. The fixed and moveable cabinets and shelves shall
not encroach upon the bed/gurney clear floor space/area. The requirements of
this clause are illustrated in Table 5, Diagram (B) of §
131.148(e)
of this title. Provisions shall be made for visual privacy between multiple
stations.
(iii) One hand washing
fixture shall be provided for every four beds/gurneys or fraction thereof.
Fixtures shall be uniformly distributed and not located within the exam area
behind the curtains.
(F)
Storage space shall be provided within the emergency suite and be under staff
control for general medical emergency supplies and medications. Adequate space
shall be provided for emergency equipment such as emergency treatment trays,
ventilator, defibrillator, splints, cardiac monitor, etc.
(G) A medical staff work area and charting
area(s) shall be provided. The area may be combined with the control
station/nurse station.
(H) An area
or alcove located out of traffic and convenient to the treatment and exam
room(s) shall be provided for an emergency crash cart.
(I) An alcove shall be provided for stretcher
and wheelchair storage. The storage shall be located out of the line of
traffic.
(J) A nourishment station
shall be provided containing a work counter with sink, microwave, refrigerator
and storage cabinets and not located in the clean workroom.
(K) When provided, an ice machine supplying
ice for therapeutic purposes shall be located in the clean utility room. A
self-dispensing ice machine shall be provided for ice for human consumption and
located in a clean utility room or the nurse station.
(L) Patient toilet room(s) shall be provided
and shall be convenient to treatment rooms, examination rooms, and trauma rooms
a hand washing fixture with hands-free operable controls. Patient toilet room
shall be at a ratio of 1 toilet room for every 5 treatment, exam, trauma
stations or fraction thereof.
(M) A
clean storage room shall be provided for clean supplies and linens as needed. A
hand washing fixture shall be provided within the room with hands-free operable
controls.
(N) Soiled workroom shall
be provided and contain a work counter, a clinical sink or equivalent flushing
type fixture, hand washing fixture with hands-free operable controls, waste
receptacles, and soiled linen receptacles.
(O) A housekeeping room containing a floor
receptor or service sink and storage space for housekeeping supplies and
equipment shall be provided for the exclusive use of the emergency suite and
shall be directly accessible from the emergency suite. When automatic film
processors are used, a receptacle of adequate size with hot and cold water for
cleaning the processor racks shall be provided. When there is only one
housekeeping room for the entire facility there shall be policies and
procedures in place, as describe in §
131.55
of this title (relating to Sanitary Conditions and Hygienic Practices) for
proper use of cleaning up body fluids versus general cleaning, and the use of
separate equipment and supplies.
(P) Staff toilets may be outside the suite
but shall be convenient for staff use and include hand washing fixtures with
hands-free operable controls. When a department has 4 or more treatment or
examination rooms, toilet facilities shall be in the suite.
(4) Trauma Treatment rooms. When
provided, a trauma room it shall comply with the following.
(A) A trauma room shall be 250 square feet of
clear floor area exclusive of aisles and fixed and moveable cabinets and
shelves. The minimum clear dimension between fixed cabinets and built-in
shelves shall be 12 feet. The trauma room shall contain a work counter,
cabinets, and examination light.
(B) When multiple-patient trauma stations are
provided, the clearance between the head of the bed/gurney to the
wall/partition shall be a minimum of 3 feet. The clearance between the side of
a bed/gurney and a wall/partition shall be a minimum of 6 feet. The clearance
between the sides of beds/gurneys shall be a minimum of 12 feet. The minimum
distance at the foot of the bed/gurney shall not be less than 7 feet for single
load area/room or 10 feet for double load area/room. Four feet of the passage
space at the foot of the bed may be shared between 2 beds/gurneys. The
multiple-bed trauma room shall contain cabinets, medication storage, work
counter, examination light, and scrub sink with hands-free operable controls.
The fixed and moveable cabinets and shelves shall not encroach upon the
bed/gurney clear floor space/area. The requirements of this subparagraph are
illustrated in Table 5, Diagram (C) of §
131.148(e)
of this title. Provisions shall be made for visual privacy between multiple
stations.
(C) A scrub station shall
be located within five feet of the either inside or outside entrance to each
trauma room. One scrub station may serve two trauma beds/gurneys. Scrub
facilities shall be arranged to minimize any incidental splatter on nearby
personnel or supply carts. The scrub sinks shall be recessed out of the main
line of traffic.
(D) All doorway
openings from the ambulance entrance to the trauma room shall be a minimum of
five feet wide.
(5)
Holding or observation room/area.
(A) When a
holding or observation room/area is provided within or adjacent to the
emergency suite, it shall comply with the following.
(B) A single holding/observation room shall
have a minimum clear area of 100 square feet exclusive of fixed and movable
cabinets and shelves. The holding/observation room shall contain a work counter
and hand washing fixture with hands-free operable controls.
(i) The single holding/observation room shall
be near the nurse station and near a patient toilet room which contains a hand
washing fixture with hands-free operable controls.
(ii) In a multiple-bed holding/observation
room/area, the clearance between the side of the bed/gurney and a
wall/partition shall be a minimum of 3 feet. The clearance between sides of the
beds/gurneys shall be a minimum of 6 feet. The minimum distance at the foot of
the bed/gurney shall not be less than 7 feet for single load area/room or 10
feet for double load area/room. Four feet of the passage space at the foot of
the bed may be shared between 2 beds/gurneys. The multiple-bed
holding/observation room/area shall contain cabinets, work counters, and a hand
washing fixture with hands-free operable controls. One hand washing fixture
shall be provided for every 4 holding/observation beds or fraction thereof.
Fixtures shall be uniformly distributed. The fixed and moveable cabinets and
shelves shall not encroach upon the bed/gurney clear floor space/area. The
requirements of this clause are illustrated in Table 5, Diagram (B) of §
131.148(e)
of this title.
(iii) In a
multiple-bed holding/observation room/area, a patient toilet room with a hand
washing fixture with hands-free operable controls shall be provided within the
room or area.
(C) When a
multiple-bed gurney holding or observation room is not within or adjacent to
the emergency suite, the following additional spaces shall be provided:
(i) A stretcher and wheelchair storage
alcove/room shall be provided. The alcove/room for stretcher and wheelchair
storage shall be located out of the line of traffic.
(ii) A clean storage room shall be provided
within or adjacent to the holding or observation room. The clean storage room
shall be provided for clean supplies and linen as needed. A hand washing
fixture shall be provided with hands-free operable controls.
(iii) Soiled workroom. A soiled workroom
shall be provided within or adjacent to the holding or observation room. The
workroom shall contain a work counter, a clinical sink or equivalent flushing
type fixture, hand washing fixture with hands-free operable controls, waste
receptacles, and soiled linen receptacles. The soiled workroom required in
support of a treatment/exam room may be combined with the holding or
observation room/area if confidently located between the 2 areas.
(6) Medication work
room or alcove. A medication work room or alcove shall be provided and located
separate from patient and public areas and under the direct supervision of
staff. A work counter, refrigerator, medication storage, and locked storage for
biologicals and drugs shall be provided. A hand washing fixture with hands-free
operable controls shall be located in the medication work room or alcove. Water
spouts used at lavatories and sinks shall have clearances adequate to avoid
contaminating utensils and the contents of carafes, etc.
(A) Functional space shall be provided and
areas required for records, reports, and accounting activities.
(B) Space for the poison control center shall
be provided with storage facilities for reaction data and drug information
centers.
(7) Diagnostic
radiographic (X-ray). A diagnostic radiographic (X-ray) room shall be provided
and be readily available to the emergency suite. The diagnostic radiographic
(X-ray) room size shall be in compliance with the manufacturer's
recommendations. Clearance and unobstructed space shall not be less than three
feet around the diagnostic equipment. Dressing room(s) shall be provided and
located near the X-ray room.
(8)
Computed tomography (CT) scanning. A CT room shall be provided and be readily
available to the emergency suite. Clearance and unobstructed space shall not be
less than three feet on each side of the diagnostic equipment. The CT room(s)
size shall be in compliance with the manufacturer's recommendations and shall
contain the following.
(A) A control room
shall be provided with a view window permitting view of the patient. The
control room shall be located to allow convenient film processing.
(B) A patient toilet room shall be provided
conveniently to the procedure room. When directly accessible to the scan room,
the toilet room shall be arranged so that a patient may leave the toilet room
without having to reenter the scan room. The toilet room shall have a hand
washing fixture with hands-free operable controls.
(9) Laboratory services. Laboratory suite
shall be provided with the following minimum facilities.
(A) The laboratory work room(s) shall include
counter(s), space appropriately designed for laboratory equipment, and sink(s)
with hands-free operable controls.
(B) Each laboratory room or work area shall
be provided with a hand washing fixture(s) with hands-free operable
controls.
(C) General storage,
including refrigeration for reagents, standards, supplies, and stained specimen
microscope slides, etc. shall be provided. Separate facilities shall be
provided for such incompatible materials as acids and bases, and vented storage
shall be provided for volatile solvents.
(D) A refrigerator or other similar equipment
shall be provided for specimen storage waiting for transfer to off-site
testing.
(E) Specimen room/area for
blood collection shall be provided with a counter, space for seating, and hand
washing fixture with hands-free operable controls. A toilet and lavatory with
hands-free operable controls shall be provided for specimen collection. This
facility may be outside the laboratory suite if conveniently located.
(F) When chemical safety is a requirement, an
emergency shower and eye flushing devices shall be provided.
(G) Flammable or combustible liquids, when
used, shall be stored in approved containers, in accordance with National Fire
Protection Association 30, Flammable and Combustible Liquids Code, 2003
edition.
(H) When radioactive
materials are employed, safe storage facilities shall be provided.
(I) Each laboratory unit shall meet the
requirements of Chapter 11 of NFPA 99 (relating to Laboratories), and Chapter
20 of NFPA 101 (relating to New Ambulatory Health Care Occupancies).
(10) Isolation room. The need for
an airborne infection isolation room in the emergency suite shall be determined
by the governing body and the infection risk assessment.
(A) When the facility provides treatment
rooms to perform procedures on persons who are known or suspected of having an
airborne infectious disease, these procedures shall be performed in a
designated emergency airborne infection isolation treatment rooms and meeting
airborne infection isolation ventilation requirements. The isolation room shall
meet the ventilation requirements contained in Table 1 of §
131.148(a)
of this title.
(B) The emergency
airborne infection isolation treatment room for a single patient shall have a
minimum clear area of 120 square feet clear floor area exclusive of fixed and
movable cabinets and shelves. The minimum clear room dimension exclusive of
fixed cabinets and built-in shelves shall be 10 feet. The emergency treatment
room shall contain cabinets, medication storage, work counter, examination
light, and a hand washing fixture with hands-free operable controls.
(C) The emergency airborne infection
isolation room shall be provided with an enclosed anteroom. The enclosed
anteroom shall open to directly into the emergency airborne infection isolation
treatment room. The enclosed anteroom shall have facilities for hand washing,
gowning, and storage of clean and soiled materials. One enclosed anteroom may
serve multiple isolation rooms.
(D)
The door from the enclosed anteroom to the emergency airborne infection
isolation room shall be provided with a self-closing device.
(E) Pressure differential monitors or air
flow devices shall be installed outside the isolation room and anteroom.
Devices shall be installed in corridors, passageways, etc.
(11) Secured holding room. When provided,
this room shall be constructed to allow for security, patient and staff safety,
patient observation, and sound mitigation. The secure holding room shall have a
minimum clear area of 100 square feet clear floor area exclusive of fixed
cabinets. The minimum clear room dimension exclusive of fixed cabinets shall be
10 feet.
(12) Orthopedic and cast
room. When provided, the room(s) may be in separate room(s) or in the trauma
room. The room(s) shall contain a work counter, storage for splints and
orthopedic supplies, traction hooks, medication storage, examination light, and
a hand washing fixture with hands-free operable controls. When a cast room is
provided it shall be equipped with hand washing facilities, storage, and other
provisions required for cast procedures.
(13) Film processing room. When a
radiographic (X-ray) room is provided, a darkroom for processing film shall be
provided unless the processing equipment does not require a darkroom for
loading and transfer. When daylight processing is used, the darkroom may be
minimal for emergency and special uses. Film processing shall be located
convenient to the darkroom.
(14)
Housekeeping room. Sufficient number of janitor's closets shall be provided
throughout the facility to maintain a clean and sanitary environment. The
closet shall contain a floor receptor or service sink and storage space for
housekeeping supplies and equipment. When there is only 1 housekeeping room for
the entire facility there shall be policies and procedures in place, as
describe in §
131.55
of this title for proper use of cleaning up body fluids versus general
cleaning, and the use of separate equipment and supplies.
(15) Medical waste. Space and facilities
shall be provided for the safe storage and disposal of medical waste as
appropriate for the material being handled and in compliance with all
applicable federal, state, or local laws, codes, rules, regulations and
ordinances.
(16) Decontamination
room.
(A) When a decontamination room is
provided, the exterior entry point shall be far as practical from any other
entry point to the emergency treatment area.
(B) The internal door from the
decontamination room shall open directly to the corridor into the emergency
treatment area.
(C) The door shall
swing into the room and be lockable against ingress from the
corridor.
(D) The room shall be a
minimum of 80 square feet of clear floor area with a hand washing fixture with
hands-free operable controls.
(E)
The decontamination room shall be equipped with 2 hand-held showerheads with
temperature controls and a dedicated holding tank with a floor drain.
(F) The decontamination room floor shall be
self-coved to a height of 6 inches. The room shall have all smooth, nonporous,
scrubable, nonabsorbent and nonperforated surfaces.
(17) Supply rooms.
(A) A storage room/area for breakdown of
supplies shall be provided. The storage room/area shall have adequate space for
breakdown of prepackaged supplies to be loaded on cart(s) to transport to the
appropriate storage spaces. The breakdown area shall not reduce the clear
unobstructive width in the egress corridor.
(B) Sterile/clean supply room. A
sterile/clean supply room shall be provided. Storage of sterile/clean supplies
shall not occur within the breakdown room.
(C) An equipment storage room shall be
provided. The equipment room may be in the emergency suite.
(18) Laundry and linen may be
processed within the facility or off site at a commercial laundry.
(A) When on-site linen processing is
provided, soiled and clean processing operations shall be separated and
arranged to provide a one-way traffic pattern from soiled to clean areas. The
following rooms and items shall be provided:
(i) a soiled linen processing room that
includes areas for receiving, holding, sorting, and washing;
(ii) a clean linen processing room that
includes areas for drying, sorting, folding, and holding before
distribution;
(iii) supply storage
cabinets in the soiled and clean linen processing rooms;
(iv) hand washing sink within the soiled
linen processing room; and
(v) a
storage room for clean linen. Clean linen storage may be combined with the
clean work room.
(B)
When linen is processed off site, the following areas shall be provided:
(i) clean linen shall be stored within the
clean supply area; and
(ii) soiled
linen shall be stored in a designated space in the facility.
(19) Employee
facilities. An employee suite shall be provided containing lockers, a lounge,
and staff toilets for employees and volunteers. The toilet room(s) may be
unisex.
(20) Engineering suite and
equipment areas shall be provided.
(A) An
engineer's office/area with file space and provisions for protected storage of
facility drawings, records, manuals, etc.
(B) A general maintenance shop(s) for repair,
maintenance, supplies and equipment. An area for medical equipment which
includes provisions for the storage, repair, and testing of electronic and
other medical equipment.
(C) When
necessary, a separate room or building for yard maintenance equipment and
supplies. When a separate room is within the physical plant, the room shall be
located so that equipment may be moved directly to the exterior. Yard equipment
or vehicles using flammable liquid fuels shall not be stored or housed within
the facility.
(D) Sufficient space
shall be provided in all mechanical and electrical equipment rooms for proper
maintenance of equipment. Provisions shall also be made for removal and
replacement of equipment.
(E)
Additional areas or room(s) for mechanical and electrical equipment shall be
provided within the physical plant or installed in separate buildings or
weatherproof enclosures with the following exceptions.
(i) An area shall be provided for cooling
towers and heat rejection equipment when such equipment is used.
(ii) An area for the medical gas park and
equipment shall be provided. For smaller medical gas systems, the equipment may
be housed in a room within the physical plant in accordance with National Fire
Protection Association 99, Standard for Health Care Facilities, 2002 edition
(NFPA 99), Chapters 4 and 8.
(iii)
When provided, compactors, dumpsters, and incinerators shall be located in an
area remote from public entrances.
(e) General detail requirements. Details in
new construction projects, including additions and alterations, shall comply
with this subsection, with NFPA 101, Chapter 20, and with local building codes.
(1) Fire safety features, including smoke
compartmentation, means of egress, automatic extinguishing systems,
inspections, smoking regulations, and other details relating to fire prevention
and fire protection shall comply with NFPA 101, Chapter 20. The Fire Safety
Evaluation System for Health Care Occupancies contained in the National Fire
Protection Association 101A, Alternative Approaches to Life Safety, 2001
Edition, Chapter 3, shall not be used in new building construction,
renovations, or additions to existing facilities.
(2) Exits, corridors and doors.
(A) A facility shall provide 2 exits remote
from each other in accordance with NFPA 101, §20.2.4.1. At least 1 exit
door shall be accessible by an ambulance from the outside. This door may also
serve as an entry for loading or receiving goods.
(B) Encroachment into the means of egress.
Such items as drinking fountains, telephone booths or stations, and vending
machines shall not project into and restrict exit corridor traffic or reduce
the exit corridor width below the required minimum. Portable equipment, when
stored, shall not project into and restrict exit corridor traffic or reduce the
exit corridor width below the required minimum.
(C) Corridors.
(i) The minimum clear and unobstructed width
of a public corridor shall be at least 4 feet.
(ii) The communicating corridor shall be used
to convey patients by stretcher, gurney, or bed.
(iii) The communicating corridor shall link
the treatment room/area, exam room/area, and holding room/area and shall be
continuous to at least 1 exit.
(iv)
The minimum clear and unobstructed width of the communicating corridor shall be
6 feet.
(D) Doors at all
openings between corridors and rooms or spaces subject to occupancy shall be
swing type. Elevator doors are excluded from this requirement.
(E) Doors, except doors to spaces such as
small closets which are not subject to occupancy, shall not swing into
corridors in a manner that might obstruct traffic flow or reduce the required
corridor width. Large walk-in type closets are considered as occupiable
spaces.
(F) The minimum width of
doors for patient access to treatment, examination, diagnostic, and imaging
rooms requiring access for beds and gurneys shall be 3 feet 8 inches.
(G) Emergency access rooms containing a
restroom, intended for patient use, shall be provided with at least one door
having hardware which will permit access from the outside in any emergency.
Door leaf width of such doors shall not be less than 36 inches.
(H) Horizontal sliding doors serving an
occupant load of fewer than 10 shall be permitted. The area served by the door
shall have no high hazard contents. The door shall be readily operable from
either side without special knowledge or effort. The force required to operate
the door in the direction of door travel shall be not more than 30 pounds per
foot to set the door in motion, and shall be not more than 15 pounds per foot
to close the door or open in the minimum required width. The door assembly
shall comply with any required fire protection rating, and, where rated, shall
be self-closing or automatic closing. The sliding doors opening to the egress
corridor doors shall have a latch or other mechanism that ensures that the
doors will not rebound into a partially open position if forcefully closed. The
sliding doors shall be installed to resist passage of smoke and may have
breakaway provisions. The latching sliding panel shall have a minimum clear
opening of 36 inches in the fully open position. The fixed panels may have
recessed tracks.
(I) All fire doors
shall be listed by an independent testing laboratory and shall meet the
construction requirements for fire doors in National Fire Protection
Association 80, Standard for Fire Doors and Fire Windows, 1999 Edition.
Reference to a labeled door shall be construed to include labeled frame and
hardware.
(3) Glazing
for glass doors, lights, sidelights, borrowed lights, and windows located
within 12 inches of a door jamb or with a bottom-frame height of less than 18
inches and a top-frame height of more than 36 inches above the finished floor
which may be broken accidentally by pedestrian traffic shall be glazed with
safety glass or plastic glazing material that will resist breaking and will not
create dangerous cutting edges when broken. Similar materials shall be used for
wall openings in activity areas such as recreation and exercise rooms, unless
otherwise required for fire safety. Safety glass, tempered or plastic glazing
materials shall be used for shower doors and bath enclosures, interior windows
and doors. Plastic and similar materials used for glazing shall comply with the
flame spread ratings of NFPA 101, §18.3.3.
(4) Grab bars shall be provided at patient
toilets and showers. The bars shall be one and one-half inches in diameter,
shall have either one and one-fourth or one and one-half inches clearance to
walls, and shall have sufficient strength and anchorage to sustain a
concentrated vertical or horizontal load of 250 pounds. Grab bars intended for
use by the disabled shall also comply with ADA requirements.
(5) Location and arrangement of fittings for
hand washing facilities shall permit their proper use and operation. Hand
washing fixtures with hands-free controls shall be provided in each
examination, treatment, trauma, diagnostic, imaging, holding/observation
room/area, soiled utility room, clean work room, and toilet room. Particular
care shall be given to the clearances required for blade-type operating
handles. Lavatories and hand washing facilities shall be securely anchored to
withstand an applied vertical load of not less than 250 pounds on the front of
the fixture. In addition to the specific areas noted, hand washing facilities
shall be conveniently located for staff use in rooms and areas noted under
spatial requirements in subsection (d) of this section and throughout the
center where patient care services are provided.
(6) A liquid or foam soap dispenser shall be
located at each hand washing facility.
(7) Provisions for hand drying shall be
included at all hand washing facilities. Hot air dryers or individual paper or
cloth units shall be enclosed to provide protection against dust or soil and
shall provide single-unit dispensing.
(8) A sign shall be posted at the entrance to
each toilet/restroom to identify the facility for public, staff, or patient
use.
(9) Emergency eyewash shall be
provided conveniently located within the emergency suite for staff use and
comply with ANSI Z358.1.
(10) The
minimum ceiling height shall be eight feet six inches with the following
exceptions.
(A) Rooms containing
ceiling-mounted light fixtures or equipment. Trauma rooms or other rooms
containing ceiling-mounted light fixtures or equipment shall have a ceiling
height of not less than 9 feet. Additional ceiling height may be required to
accommodate special fixtures or equipment.
(B) Ceilings in storage rooms, toilet rooms,
and other minor rooms shall be not less than 7 feet 6 inches.
(C) Boiler rooms shall have ceiling
clearances not less than 2 feet 6 inches above the main boiler header and
connecting piping.
(D) Overhead
clearance for suspended tracks, rails, pipes, signs, lights, door closers, exit
signs, and other fixtures that protrude into the path of normal traffic shall
not be less than six feet eight inches above the finished floor.
(11) Areas producing impact noises
like recreation rooms, exercise rooms, and similar spaces shall not be located
directly over trauma or treatment rooms/area unless special provisions are made
to minimize noise.
(12) Rooms
containing heat-producing equipment, such as mechanical and electrical
equipment and laundry rooms, shall be insulated and ventilated to prevent
floors of any occupied room located above it from exceeding a temperature
differential of 10 degrees Fahrenheit above the ambient room
temperature.
(13) When the entire
facility is provided with digital imaging system capabilities, a minimum of 2
X-ray film illuminators viewers shall be provided in a central
location.
(14) Radiation shielding
shall be designed, tested, and approved by a medical physicist licensed under
the Medical Physics Practice Act, Occupations Code, Chapter 602. The facility
shall obtain a certificate of registration issued by the Radiation Safety
Licensing Branch to use radiation machines.
(f) General finish requirements. Finishes in
new construction projects, including additions and alterations, shall comply
with this subsection, with NFPA 101, Chapter 20, and with local building codes.
(1) Privacy screens, cubicle curtains, and
draperies.
(A) Cubicle curtains or privacy
screens shall be provided to assure patient privacy when required or requested
by a patient.
(B) Cubicle curtains,
draperies and other hanging fabrics shall be noncombustible or flame retardant
and shall pass both the small-scale and the large-scale tests of National Fire
Protection Association 701, Standard Methods of Fire Tests for Flame-Resistant
Textiles and Films, 1999 Edition. Copies of laboratory test reports for
installed materials shall be submitted to the department at the time of the
final construction inspection.
(2) Flame spread, smoke development and
noxious gases. Flame spread and smoke developed limitations of interior
finishes shall comply with Table 4 of §
131.148(d)
of this title and NFPA 101, §10.2. The use of materials known to produce
large or concentrated amounts of noxious or toxic gases shall not be used in
exit accesses or in patient areas. Copies of laboratory test reports for
installed materials tested in accordance with National Fire Protection
Association 255, Standard Method of Test of Surface Burning Characteristics of
Building Materials, 2000 Edition, and National Fire Protection Association 258,
Standard Research Test Method for Determining Smoke Generation of Solid
Materials, 2001 Edition, shall be provided.
(3) Floor finishes.
(A) Flooring shall be easy to clean and have
wear resistance appropriate for the location involved. Floors that are subject
to traffic while wet (such as shower and bath areas and similar work areas)
shall have a nonslip surface. In all areas frequently subject to wet cleaning
methods, floor materials shall not be physically affected by germicidal and
cleaning solutions. The following are acceptable floor finishes:
(i) painted concrete for mechanical,
electrical, communication rooms, and janitor's closets;
(ii) vinyl and vinyl composition tiles and
sheets tiles for offices, lobbies, administrative areas, storage, staff and
public toilet rooms, support spaces, and non-treatment areas. The joints shall
be sealed to prevent moisture penetration between the joints and under the
tile;
(iii) monolithic or seamless
flooring shall be provided for all treatment rooms/areas, exam rooms/areas,
patient toilet rooms, and soiled workrooms. Seamless flooring shall be
impervious to water, coved and installed integral with the base, tightly sealed
to the wall, and without voids that can harbor insects or retain dirt
particles. The base shall not be less then six inches in height. Welded joint
flooring is acceptable;
(iv)
marble, ceramic and quarry tile for offices, lobbies, staff and public toilet
rooms, administrative areas, wet areas, and similar spaces;
(v) carpet flooring for offices, lobbies, and
administrative areas. Carpeting shall not be installed in any holding rooms,
toilet rooms, treatment rooms, examination rooms, diagnostic, imaging, and
similar spaces; and
(vi) terrazzo
for offices, lobbies, administrative areas, and similar spaces.
(B) Thresholds at doorways shall
not exceed 3/4-inch in height for exterior sliding doors or 1/2-inch for other
type doors. Raised thresholds and floor level changes at accessible doorways
shall be beveled with a slope no greater than 1:2. Expansion joint covers shall
not exceed 1/2-inch in height and shall have beveled edges with a slope no
greater than 1:2.
(4)
Wall finishes. Wall finishes in patient exam, treatment, or diagnostic rooms,
toilet rooms, soiled work room, clean work/storage rooms, and laboratory, shall
be smooth, washable, moisture resistant, and cleanable by standard housekeeping
practices. Wall finishes shall be in compliance with the requirements of NFPA
101, §38.3.3, relating to flame spread.
(A) Wall finishes shall be water-resistant in
the immediate area of plumbing fixtures.
(B) Wall finishes in areas subject to
frequent wet cleaning methods shall be impervious to water, tightly sealed, and
without voids.
(5)
Ceiling finishes. All occupied rooms and spaces shall be provided with finished
ceilings, unless otherwise noted. Ceilings which are a part of a rated
roof/ceiling assembly or a floor/ceiling assembly shall be constructed of
listed components and installed in accordance with the listing. Three types of
ceilings that are required in various areas of the facility are:
(A) ordinary ceilings are required in all
areas or rooms in the facility unless otherwise noted. This includes ceilings
such as acoustical tiles installed in a metal grid which are dry cleanable with
equipment used in daily housekeeping activities such as dusters and vacuum
cleaners;
(B) washable ceilings
that dictate this type of cleaning or protection for these spaces (such as soil
utility or soil workroom). The ceilings shall be made of washable, smooth,
moisture impervious materials such as painted lay-in gypsum wallboard or vinyl
faced acoustic tile in a metal grid; and
(C) monolithic ceilings which are monolithic
from wall to wall (painted solid gypsum wallboard), smooth and without
fissures, open joints, or crevices, and with a washable and moisture impervious
finish shall be provided in the airborne isolation rooms, soiled workrooms,
trauma rooms, and sterilizing facilities when provided.
(D) Nonfinished ceilings may be omitted in
mechanical, electrical, communication rooms, shops, and similar spaces unless
required for fire-resistive purposes.
(6) Floor, wall, and ceiling penetrations.
Floor, wall, and ceiling penetrations by pipes, ducts, and conduits, or any
direct openings shall be tightly sealed to minimize entry of dirt particles,
rodents, and insects. Joints of structural elements shall be similarly
sealed.
(7) Material finishes.
Materials known to produce noxious gases when burned shall not be used for
mattresses, upholstery, and wall finishes.
(g) General mechanical requirements. This
subsection contains requirements for mechanical systems; air conditioning,
heating and ventilating systems; steam and hot and cold water systems; and
thermal and acoustical insulation.
(1) Cost.
All mechanical systems shall be designed for overall efficiency and life cycle
costing, including operational costs. Recognized engineering practices shall be
followed to achieve the most economical and effective results except that in no
case shall patient care or safety be sacrificed for conservation.
(2) Equipment location. Mechanical equipment
may be located indoors, outdoors when in a weatherproof enclosure, or in a
separate building(s).
(3) Vibration
isolation. Mechanical equipment shall be mounted on vibration isolators as
required to prevent unacceptable structure-borne vibration. Ducts, pipes, etc.
connected to mechanical equipment which is a source of vibration shall be
isolated from the equipment with vibration isolators.
(4) Performance and acceptance. Prior to
completion and acceptance of the facility to the owner/operator, all mechanical
systems shall be tested, balanced, and operated to demonstrate to the design
engineer or their representative that the installation and performance of these
systems conform to the requirements of the plans and specifications.
(A) Upon completion of the contract, the
facility owner/operator shall obtain from the construction contractor parts
lists and procurement information with numbers and descriptions for each piece
of equipment.
(B) Upon completion
of the contract, the facility owner/operator shall obtain from the construction
contractor instructions in the operational use and maintenance of systems and
equipment as required.
(5) Heating, ventilating, and air
conditioning (HVAC) systems.
(A) All central
HVAC systems shall comply with and shall be installed in accordance with the
requirements of NFPA 90A, Standard for the Installation of Air Conditioning and
Ventilating Systems, 2002 Edition, or NFPA 90B, Standard for the Installation
of Warm Air Heating and Air-Conditioning Systems, 2002 Edition, as applicable
and the requirements contained in this paragraph. Air handling units serving
two or more rooms are considered to be central units.
(B) Noncentral air handling systems, i.e.,
individual room units that are used for heating and cooling purposes (e.g.,
fan-coil units, heat pump units, and packaged terminal air conditioning units)
shall be equipped with permanent (cleanable) or replaceable filters. The
filters shall have an average efficiency of 25 - 30% and an average arrestance
of 85% based on American Society of Heating, Refrigerating, and
Air-Conditioning Engineers (ASHRAE), Inc., Standard 52.2, 1999 edition, Method
of Testing General Ventilation Air Cleaning Devices for Removal Efficiency by
Particle Size. These units shall be used as air recirculating units only. All
outdoor air requirements shall be met by a separate central air handling system
with the proper filtration, as required in Table 1 of §
131.148(a)
of this title.
(C) General
ventilation requirements. All rooms and areas in the facility shall have
provision for positive ventilation. Fans serving exhaust systems shall be
located at the discharge end and shall be conveniently accessible for service.
Exhaust systems may be combined, unless otherwise noted, for efficient use of
recovery devices required for energy conservation. The ventilation rates shown
in Table 1of §
131.148(a)
of this title shall be used only as minimum requirements, since they do not
preclude the use of higher rates that may be appropriate.
(i) To reduce utility costs, facility design
may utilize energy conserving procedures including recovery devices, variable
air volume, load shedding, systems shutdown, or reduction of ventilation rates
(when specifically permitted) in certain areas when unoccupied. In no case
shall patient care be jeopardized.
(ii) Mechanical systems shall be arranged to
take advantage of outside air conditions by using an economizer cycle when
appropriate to reduce heating and cooling systems loads. Innovative design that
provides for additional energy conservation while meeting the intent of this
section for acceptable patient care may be presented to the department for
consideration.
(iii) Fully ducted
supply, return and exhaust air for HVAC systems shall be provided for all
patient care areas, storage rooms, and where required for fire safety purposes.
Combination systems, utilizing both ducts and plenums for movement of air in
these areas, shall not be permitted. All ductwork access panels shall be
labeled.
(iv) The designed capacity
of the HVAC systems shall be capable of providing the ranges of temperatures
and humidities as shown in Table 1 of §
131.148(a)
of this title. Where no values are noted or indicated, the indoor design
temperature in all other areas shall be between 68 and 75 degrees Fahrenheit
with relative humidity of not less than 30%.
(v) Each trauma room shall have temperature
and humidity indicating devices mounted at eye level.
(vi) Outside air intake locations.
(I) Outside air intakes shall be located at
least 25 feet from exhaust outlets of ventilating systems, combustion equipment
stacks, medical-surgical vacuum system outlets, plumbing vents, or areas which
may collect vehicular exhaust or other noxious fumes. (Prevailing winds and
proximity to other structures may require other arrangements.)
(II) Plumbing and vacuum vents that terminate
5 feet above the level of the top of the air intake may be located as close as
10 feet to the air intake.
(III)
The bottom of outside air intakes serving central systems shall be located as
high as practical but at least 6 feet above ground level, or if installed above
the roof, 3 feet above the roof level.
(vii) Contaminated air exhaust outlets from
areas (laboratory hoods, etc.) that exhaust contaminated air shall be above the
roof and be arranged to exhaust upward unless the air has been treated by an
appropriate means where sidewall exhaust will be allowed.
(viii) All toilet exhaust ventilation shall
be exhausted to the exterior. Exhaust systems may be combined, unless otherwise
noted, for efficient use of recovery devices required for energy
conservation.
(ix) Directional air
flow. Ventilation systems shall be designed and balanced to provide pressure
relationships contained in Table 1 of §
131.148(a)
of this title. Provisions in Note 4 of Table 1 of §
131.148(a)
of this title shall be followed for the reductions and shut down of ventilation
systems when a room is unoccupied.
(x) Air distribution devices. Turbulence and
other factors of air movement to minimize airborne particulate matter shall be
considered in the design of air distribution devices. Where extraordinary
procedures require special designs, the installation shall be reviewed on a
case-by-case basis.
(I) All supply diffusers
grilles shall be located on the ceiling or on a wall within four inches from
the ceiling.
(II) Air supply for
the treatment rooms/areas, exam rooms/areas, and trauma rooms/areas shall be
from ceiling outlets near the center of the work area to efficiently control
air movement.
(III) A minimum of
two return air inlets located diagonally opposite from one another and near
floor level shall be provided. Bottoms of the wall mounted return air grilles
in trauma and other anesthetizing locations shall be at least four inches above
the floor.
(xi) The air
handling units (AHU) shall not be started or operated without the filters
installed in place, including. This includes the 90% efficiency filters where
required. This includes during construction operations. Ducts shall be cleaned
thoroughly and throughout by a National Air Duct Cleaners Association (NADCA)
certified air duct cleaning contractor when the air handling systems have been
operating without the required filters in place. When ducts are determined to
be dirty or dusty, the department shall require a written report assuring
cleanliness of duct and clean air quality.
(xii) When duct humidifiers are located
upstream of the final filters, they shall be located at least 15 feet from the
filters. Duct work with duct-mounted humidifiers shall be provided with a means
of removing water accumulation. An adjustable high-limit humidistat shall be
located downstream of the humidifier to reduce the potential of condensation
inside the duct. All duct takeoffs shall be sufficiently downstream of the
humidifier to ensure complete moisture absorption. Reservoir-type water spray
or evaporative pan humidifiers shall not be used.
(xiii) All air handling units shall be
equipped with filters having efficiencies equal to, or greater than, those
specified in Table 2 of §
131.148(b)
of this title. Filter efficiencies shall be average dust spot efficiencies
tested in accordance with American Society of Heating, Refrigerating, and
Air-Conditioning Engineers (ASHRAE), Inc., Standard 52.2, 1999 edition, Method
of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by
Particle Size. All joints between filter segments, and between filter segments
and the enclosing ductwork, shall have gaskets and seals to provide a positive
seal against air leakage. Air handlers serving more than one room shall be
considered as central air handlers. All documents published by ASHRAE as
referenced in this section may be obtained by writing or calling the ASHRAE,
Inc. at the following address or telephone number: ASHRAE, 1791 Tullie Circle,
Northeast, Atlanta, Georgia 30329; telephone (404) 636-8400.
(I) Filtration for air handling units serving
single rooms requiring asepsis control. Dedicated air handlers serving only one
room where asepsis control is required (such as, but not limited to trauma
rooms/areas, treatment rooms/areas, exam rooms/areas) shall be equipped with
filters having efficiencies equal to, or greater than, those specified for
patient care areas in Table 2 of §
131.148(b)
of this title.
(II) Filtration
requirements for air handling units serving other single rooms. Dedicated air
handlers serving all other single rooms shall be equipped with nominal filters
installed at the return air system.
(III) Location of multiple filters. Where 2
filter beds are required by Table 2 of §
131.148(b)
of this title, filter bed number one shall be located upstream of the air
conditioning equipment, and filter bed number 2 shall be downstream of the
supply air blowers, cooling and heating coils.
(IV) Where only 1 filter bed is required by
Table 2 of §
131.148(b)
of this title, it shall be located upstream of the supply fan. Filter frames
shall be durable and constructed to provide an airtight fit with the enclosing
ductwork.
(V) Pressure monitoring
devices. A manometer or draft gauge shall be installed across each filter bed
having a required efficiency of 75% or more, including laboratory hoods
requiring high efficiency particulate air (HEPA) filters. The pressure
monitoring device shall be mounted below the ceiling line within the facility
such that it can be observed by staff.
(D) Thermal and acoustical insulation for air
handling systems. Asbestos containing insulation materials shall not be used.
(i) Air ducts and casings with outside
surface temperature below the ambient dew point or temperature above 80 degrees
Fahrenheit shall be provided with thermal insulation.
(ii) When installed, linings in air ducts and
equipment shall meet the Erosion Test Method described in Underwriters
Laboratories (UL), Standard 181, relating to Factory-Made Duct Materials and
Air Duct Connectors, April 4, 1996 edition. This document may be obtained from
the Underwriters Laboratories, 333 Pfingsten Road, Northbrook, Illinois
60062-2096.
(iii) Interior and
exterior insulation, including finishes and adhesives on the exterior surfaces
of ducts and equipment, shall have a flame spread rating of 25 or less and a
smoke developed rating of 50 or less as required by NFPA 90A, Chapters 4 and 5
and as determined by an independent testing laboratory in accordance with NFPA
255, A Standard Method of Test of Surface Burning Characteristics of Building
Materials, 2000 Edition.
(iv) Duct
lining and acoustical traps exposed to air movement shall not be used in ducts
serving any trauma rooms, treatment rooms, examination rooms, holding areas,
clean room, and critical care areas. This requirement shall not apply to mixing
boxes and acoustical traps that have approved nonabrasive coverings over such
linings.
(v) Insulation of soft and
spray-on types shall not be used where subject to air currents or mechanical
erosion or where loose particles may create a maintenance problem or occupant
discomfort.
(vi) Internal linings
shall not be used in ducts, terminal boxes, or other air system components
supplying all patient care areas. This requirement shall not apply to mixing
boxes and acoustical traps that have special coverings over such
lining.
(E) Ventilation
for anesthetizing locations. When anesthesia is administered, ventilation for
anesthetizing locations, as defined in NFPA 99, §3-3, shall comply with
NFPA 99, §13.4.1.2 and any specific ventilation requirements of clauses
(i) - (iii) of this subparagraph.
(i) Smoke
removal systems for anesthetizing locations. Smoke removal systems shall be
provided in all windowless anesthetizing locations in accordance with NFPA 99,
§6.4.1.2. Supply and exhaust systems for windowless anesthetizing
locations shall be arranged to automatically exhaust smoke and products of
combustion, prevent recirculation of smoke originating within the surgical
suite, and prevent the circulation of smoke entering the system intakes,
without in either case interfering with the exhaust function of the
system.
(ii) Smoke removal systems
for surgical suites. Smoke removal systems shall be provided in all surgical
suites in accordance with NFPA 99, §6.4.1.3.
(iii) Smoke exhaust grilles. Exhaust grilles
for smoke evacuation systems shall be ceiling-mounted or wall-mounted within 12
inches of the ceiling.
(F) Location of return and exhaust air
devices. The bottoms of wall-mounted return and exhaust air openings shall be
at least 4 inches above the floor. Return air openings located less than 6
inches above the floor shall be provided with nominal filters. All exhaust air
openings and return air openings located higher than 6 inches but less than 7
feet above the floor shall be protected with grilles or screens having openings
through which a 1/2-inch sphere will not pass.
(G) Ray protection. Ducts which penetrate
construction intended for X-ray or other ray protection shall not impair the
effectiveness of the protection.
(H) Fire damper requirements. Fire dampers
shall be located and installed in all ducts at the point of penetration of a
required 2-hour or higher fire-rated wall or floor in accordance with the
requirements of NFPA 101, §18.5.2.
(I) Smoke damper requirements. Smoke dampers
shall be located and installed in accordance with the requirements of NFPA 101,
§20.3.7.3, and NFPA 90A, Chapter 5.
(i)
Combination fire and smoke leakage limiting dampers (Class II) shall be
installed in accordance with manufacturer's instructions for all ducts
penetrating one and two-hour rated fire and smoke partitions required by NFPA
101, §20.3.7, Subdivision of Building Space (not required in facility
meeting the provisions of NFPA 101, §20.3.7.2, Exception Number
1).
(ii) Combination smoke and fire
dampers shall close on activation of the fire alarm system by smoke detectors
installed and located as required by National Fire Protection Association 72,
National Fire Alarm Code, 2002 Edition (NFPA 72), Chapter 8; NFPA 90A, Chapter
6; and NFPA 101, §20.3.5; the fire sprinkler system; and upon loss of
power. Smoke dampers shall not close by fan shutdown alone unless it is a part
of an engineered smoke removal system.
(iii) Air handling fans and smoke damper
controls may be interconnected so that closing of smoke dampers will not damage
the ducts.
(iv) Use of frangible
devices for shutting smoke dampers is not permitted.
(J) Acceptable damper assemblies. Only fire
damper and smoke damper assemblies integral with sleeves and listed for the
intended purpose shall be acceptable.
(K) Duct access doors. Unobstructed access to
duct openings in accordance with NFPA 90A, §4.3, shall be provided in
ducts within reach and sight of every fire damper, smoke damper and smoke
detector. Each opening shall be protected by an internally insulated door which
shall be labeled externally to indicate the fire protection device located
within.
(L) Restarting controls.
Controls for restarting fans may be installed for convenient fire department
use to assist in evacuation of smoke after a fire is controlled, provided that
provisions are made to avoid possible damage to the system because of closed
dampers. To accomplish this, smoke dampers shall be equipped with remote
control devices.
(M) Make-up air.
If air supply requirements in Table 1 of §
131.148(a)
of this title do not provide sufficient air for use by exhaust hoods and safety
cabinets, filtered make-up air shall be ducted to maintain the required air
flow direction in that room. Make-up systems for hoods shall be arranged to
minimize short circuiting of air and to avoid reduction in air velocity at the
point of contaminant capture.
(h) Piping systems and plumbing fixture
requirements. All piping systems and plumbing fixtures shall be designed and
installed in accordance with the requirements of the National Standard Plumbing
Code Illustrated published by the National Association of
Plumbing-Heating-Cooling Contractors (PHCC), 2003 edition, and this paragraph.
The National Standard Plumbing Code may be obtained by writing or calling the
PHCC at the following address or telephone number: Plumbing-Heating-Cooling
Contractors, P.O. Box 6808, Falls Church, Virginia 22046; telephone (800)
533-7694.
(1) Piping systems.
(A) Water supply piping systems. Water
service pipe to point of entrance to the building shall be brass pipe, copper
tube (not less than type M when buried directly), copper pipe, cast iron water
pipe, galvanized steel pipe, or approved plastic pipe. Domestic water
distribution system piping within buildings shall be brass pipe, copper pipe,
copper tube, or galvanized steel pipe. Piping systems shall be designed to
supply water at sufficient pressure to operate all fixtures and equipment
during maximum demand.
(i) Each water service
main, branch main, riser, and branch to a group of fixtures shall be equipped
with accessible and readily identifiable shutoff valves. Stop valves shall be
provided at each fixture.
(ii)
Backflow preventers (vacuum breakers) shall be installed on hose bibs,
laboratory sinks, janitor sinks, bedpan flushing attachments, and all other
fixtures to which hoses or tubing can be attached. Connections to high hazard
sources, e.g., X-ray film processors, shall be from a cold water hose bib
through a reduced pressure principle type backflow preventer (RPBFP).
(iii) Flush valves installed on plumbing
fixtures shall be of a quiet operating type, equipped with silencers.
(iv) Water heating equipment shall have
sufficient capacity to supply water for all clinical needs based on accepted
engineering practices using actual number and type of fixtures and for heating,
when applicable.
(v) Hot water
distribution system serving all patient care areas shall be under constant
recirculation to provide continuous hot water at each hot water
outlet.
(vi) Water temperatures
shall be measured at hot water point of use or at the inlet to processing
equipment. Hot water temperature at point of use for patients, staff, and
visitors shall be in the range of 105 to 120 degrees Fahrenheit.
(vii) When potable water storage tanks (hot
and cold) are used, the water shall be used and replenished. Domestic water
storage tank(s) shall be fabricated of corrosion-resistant metal or lined with
noncorrosive material. Water shall not be stored in tanks for future use unless
the water is tested weekly for contaminates/bacteria.
(viii) Purified water distribution system
piping shall be task specific and include, but not necessarily be limited to,
polypropylene (PP), polyvinylidene fluoride (PVDF) or polyvinyl chloride (PVC)
pipe. Final installed purified water system piping assemblies shall be UL
approved and fully comply with applicable American Society for Testing and
Materials (ASTM) Fire Resistant/Smoke Density requirements. The applicable
documents are available from ASTM International, 100 Barr Harbor Drive, P.O.
Box C700, West Conshohocken, Pennsylvania 19428-2959.
(ix) Dead-end piping (risers with no flow,
branches with no fixture) shall not be installed. In any renovation work,
dead-end piping shall be removed. Empty risers, mains and branches installed
for future use are permitted.
(B) Fire sprinkler systems. When provided,
fire sprinkler systems shall comply with the requirements of NFPA 101,
§9.7, Automatic Sprinklers and Other Extinguishing Equipment, and the
requirements of this subparagraph. All fire sprinkler systems shall be
designed, installed, and maintained in accordance with the requirements of NFPA
13, Standard for the Installation of Sprinkler Systems, 2002 Edition, and shall
be certified as required by §
131.147(c)(1)(C)
of this title (relating to Construction, Inspection, and Approval of
Project).
(C) Piped nonflammable
medical gas and clinical vacuum systems. Piped nonflammable medical gas and
clinical vacuum system shall be designed, installed, and certified in
accordance with the requirements of NFPA 99, §5.1 for Level 1 Piped
Systems and the requirements of this subparagraph.
(i) Nonflammable medical gas and clinical
vacuum outlets shall be provided in accordance with Table 3 of §
131.148(c)
of this title.
(ii) Medical gas
piping systems including source tanks and related piping shall be installed
only by, or under the direct supervision of, a holder of a master plumber
license or a journeyman plumber license with a medical gas piping installation
endorsement issued by the Texas State Board of Plumbing Examiners.
(iii) Prior to closing of walls, the
installer shall perform an initial pressure test, a blowdown test, a secondary
pressure test, a cross-connection test, and a purge of the piping system as
required by NFPA 99.
(iv)
Qualifications verification testing shall be performed and inspected by a
party, other than the installer, installing contractor, or material vendor.
Testing shall be conducted by a medical gas system verifier registered with an
acceptable organization by this department and is technically competent and
experienced in the field of medical gas and vacuum pipeline testing and meets
the requirements of The American Society of Safety Engineers (ASSE) Personnel
Standard 6030, Professional Qualifications Standard for Medical Gas Systems.
The document published by ASSE Personnel Standard 6030, Professional
Qualifications Standard for Medical Gas Systems as referenced in this rule may
be obtained by writing or calling The American Society of Safety Engineers
(ASSE) at ASSE International Office, 901 Canterbury, Suite A, Westlake, Ohio
44145, telephone (440) 885-3040.
(v) Upon completion of the installer
inspections and tests and after closing of walls, verification tests of the
medical gas piping systems, the warning system, and the gas supply source shall
be conducted. The verification tests shall include a cross-connection test,
valve test, flow test, piping purge test, piping purity test, final tie-in
test, operational pressure tests, and medical gas concentration test.
(vi) Verification testing of the medical gas
piping systems and the warning systems shall be performed on all new piped
medical gas systems, additions, renovations, or repaired portions of an
existing system. All systems that are breached and components that are added,
renovated, or replaced shall be inspected and appropriately tested. The
breached portions of the systems subject to inspection and testing shall all be
of the new and existing components in the immediate zone or area located
upstream of the point or area of intrusion and downstream to the end of the
system or a properly installed isolation valve.
(vii) Verification tests of piped medical gas
systems shall include tests of the source alarms and monitoring safeguards,
master alarm systems, and the area alarm systems.
(viii) Source equipment verification tests.
Source equipment verification tests shall include medical gas supply sources
(bulk and manifold) and the compressed air source systems (compressors, dryers,
filters, and regulators).
(ix)
Before new piped medical gas systems, additions, renovations, or repaired
portions of an existing system are put into use, facility medical personnel
shall be responsible for ensuring that the gas delivered at the outlet is the
gas shown on the outlet label and that the proper connecting fittings are
checked against their labels.
(x)
Upon successful completion of all verification tests, written certification for
affected piped medical gas systems and piped medical vacuum systems including
the supply sources and warning systems shall be provided by a party technically
competent and experienced in the field of medical gas pipeline testing stating
that the provisions of NFPA 99 have been adhered to and systems integrity has
been achieved. The written certification shall be submitted directly to the
facility and the installer. A copy shall be available at final department
construction inspection.
(xi)
Documentation of the installed, modified, extended or repaired medical gas
piping system shall be submitted to the department by the same party certifying
the piped medical gas systems. The number and type of medical gas outlets
(e.g., oxygen, vacuum, medical air, nitrogen, nitrous oxide) shall be
documented and arranged tabularly by room numbers and room types.
(D) Main storage of medical gases
may be outside or inside the facility in accordance with NFPA 99, §5.1.
Provision shall be made for additional separate storage of reserve gas
cylinders necessary to complete at least one day's procedures.
(E) Multiple gas outlets on one medical gas
outlet. Y-connections, "twinning," or other similar devices shall not be used
on any medical gas outlet.
(2) Steam and hot water systems.
(A) Boilers. When provided, the boilers shall
have the capacity, based upon the net ratings as published in The I-B-R Ratings
Book for Boilers, Baseboard Radiation and Finned Tube (commercial) by the
Hydronics Institute Division of GAMA, to supply the normal heating, hot water,
and steam requirements of all systems and equipment. The document published by
the Hydronics Institute Division of GAMA as referenced in this rule may be
obtained by writing or calling the Hydronics Institute Division of GAMA at 35
Russo Place, P.O. Box 218, Berkeley Heights, New Jersey 07922, telephone (908)
464-8200.
(i) Boiler feed pumps, heating
circulating pumps, condensate return pumps, and fuel oil pumps shall be
connected and installed to provide normal and standby service.
(ii) Supply and return mains and risers of
cooling, heating, and process steam systems shall be valved to isolate the
various sections of each system. Each piece of equipment shall be valved at the
supply and return ends except that vacuum condensate returns need not be valved
at each piece of equipment.
(B) When required, the facility shall ensure
compliance with Texas Department of Licensing and Regulation, Boiler Section,
Texas Boiler Law (Health and Safety Code, Chapter 755, Boilers), which requires
certification documentation for boilers to be posted on site at each boiler
installation.
(3)
Building sewers shall discharge into a community sewage system. Where such a
system is not available, a facility providing sewage treatment shall conform to
applicable local and state regulations.
(A)
Above ground piping. Soil stacks and roof drains installed above ground within
buildings shall be drain-waste-vent (DWV) weight or heavier and shall be:
copper pipe, copper tube, cast iron pipe, or Schedule 40 polyvinyl chloride
(CPVC) pipe.
(B) All underground
building drains shall be cast iron soil pipe, hard temper copper tube (DWV
schedule 40 or heavier), acrylonitrile-butodiene-styrene (ABS) plastic pipe, or
PVC, VCP, CPVC pipe. Underground piping shall have at least 12 inches of earth
cover or comply with local codes. Existing buildings or portions of buildings
that are being remodeled need not comply with this subparagraph.
(C) Separate drainage systems for chemical
wastes (acids and other corrosive materials) shall be provided. Materials
acceptable for chemical waste drainage systems shall include chemically
resistant borosilicate glass pipe, high silicone content cast iron pipe,
polypropylene plastic pipe, or plastic lined pipe.
(D) Drainage and waste piping shall not be
installed above or below ceilings in trauma rooms/areas and sterile processing
rooms unless precautions are taken to protect the space below from leakage and
condensation from necessary overhead piping. Secondary protection shall be
required to drain. Any required secondary protection shall be labeled, "code
required secondary drain system" every 20 feet in a highly visible print or
label.
(4) Thermal
insulation for piping systems and equipment. Asbestos containing insulation
materials shall not be used.
(A) Insulation
shall be provided for the following:
(i)
boilers, smoke breeching, and stacks;
(ii) steam supply and condensate return
piping;
(iii) hot water piping and
all hot water heaters, generators, converters, and storage tanks;
(iv) chilled water, refrigerant, other
process piping, equipment operating with fluid temperatures below ambient dew
point, and water supply and drainage piping on which condensation may occur.
Insulation on cold surfaces shall include an exterior vapor barrier;
and
(v) other piping, ducts, and
equipment as necessary to maintain the efficiency of the system.
(B) Insulation flame spread. Flame
spread shall not exceed 25 and smoke development rating shall not exceed 50 for
pipe insulation as determined by an independent testing laboratory in
accordance with NFPA 255, Standard Method of Test of Surface Burning
Characteristics of Building Materials, 2000 Edition.
(5) Plumbing fixtures. Plumbing fixtures
shall be made of nonabsorptive, acid-resistant materials and shall comply with
the requirements of the National Standard Plumbing Code, and this paragraph.
(A) Sink and lavatory controls. All
lavatories used by medical and nursing staff and by patients shall be trimmed
with valves or electronic controls which can be operated without the use of
hands. Blade handles used for this purpose shall not be less than 4 inches in
length. Single lever or wrist blade devices may also be used.
(B) Clinical sink traps. Clinical sinks shall
have an integral trap in which the upper portion of a visible trap seal
provides a water surface.
(C)
Back-flow or siphoning. All plumbing fixtures and equipment shall be designed
and installed to prevent the back-flow or back-siphonage of any material into
the water supply. The over-the-rim type water inlet shall be used wherever
possible. Vacuum-breaking devices shall be properly installed when an
over-the-rim type water inlet cannot be utilized.
(D) Drinking fountain. Each drinking fountain
shall be designed so that the water issues at an angle from the vertical, the
end of the water orifice is above the rim of the bowl, and a guard is located
over the orifice to protect it from lip contamination.
(E) Sterilizing equipment. All sterilizing
equipment shall be designed and installed to prevent contamination of the water
supply and the entrance of contaminating materials into the sterilizing
units.
(F) Hose attachment. No hose
shall be affixed to any faucet if the end of the hose may become submerged in
contaminated liquid unless the faucet is equipped with an approved, properly
installed vacuum breaker.
(G)
Bedpan washers and sterilizers. When provided, bedpan washers and sterilizers
shall be designed and installed so that both hot and cold water inlets shall be
protected against back-siphonage at maximum water level.
(H) Flood level rim clearance. The water
supply spouts for lavatories and sinks required in patient care areas shall be
mounted so that their discharge points are a minimum of 5 inches above the rim
of the fixture.
(I) Scrub sink
controls. Freestanding scrub sinks and lavatories used for scrubbing in
procedure rooms shall be trimmed with foot, knee, or electronic hands-free
controls. Single lever wrist blades are not acceptable at scrub
sinks.
(J) Floor drains or floor
sinks. Where floor drains or floor sinks are installed, they shall be of a type
that can be easily cleaned by removal of the cover. Removable stainless steel
mesh shall be provided in addition to a grilled drain cover to prevent entry of
large particles of waste which might cause stoppages.
(K) Under counter piping. Under counter
piping and above floor drains shall be arranged (raised) so as not to interfere
with cleaning of the floor below the equipment.
(L) Ice machines. All ice-making machines
used to provide ice for human consumption shall be of the self-dispensing type.
Copper tubing shall be provided for supply connections to ice
machines.
(i)
General electrical requirements. This subsection contains common electrical and
essential emergency system requirements.
(1)
Electrical requirements. All electrical material and equipment, including
conductors, controls, and signaling devices, shall be installed in compliance
with applicable sections of the NFPA 70, National Electrical Code, 2002
Edition, §517; NFPA 99, Chapter 14; the requirements of this subsection,
and as necessary to provide a complete electrical system. Electrical systems
and components shall be listed by nationally recognized listing agencies as
complying with available standards and shall be installed in accordance with
the listings and manufacturer's instructions.
(A) All fixtures, switches, sockets, and
other pieces of apparatus shall be maintained in a safe and working
condition.
(B) Extension cords and
cables shall not be used for permanent wiring.
(C) All electrical heating devices shall be
equipped with a pilot light to indicate when the device is in service, unless
equipped with a temperature limiting device integral with the heater.
(D) All equipment, fixtures, and appliances
shall be properly grounded in accordance with NFPA 70.
(E) Under counter electrical installations
shall be arranged (raised) to not interfere with floor cleaning below the
equipment.
(2)
Installation testing and certification.
(A)
Installation testing. The electrical installations, including grounding
continuity, fire alarm, nurses calling system and communication systems, shall
be tested to demonstrate that equipment installation and operation is
appropriate and functional. A written record of performance tests on special
electrical systems and equipment shall show compliance with applicable codes
and standards and shall be available to the department upon request.
(B) Grounding system testing. The grounding
system shall be tested as described in NFPA 99, §4.3.3, for patient care
areas in new or renovated work. The testing shall be performed by a qualified
electrician or their qualified electrical testing agent. The electrical
contractor shall provide a letter stating that the grounding system has been
tested in accordance with NFPA 99, the testing device use complies with NFPA
99, and whether the grounding system passed the test. The letter shall be
signed by the qualified electrical contractor, or their designated qualified
electrical testing agent, certifying that the system has been tested and the
results of the test are indicated.
(3) Electrical safeguards. Shielded isolation
transformers, voltage regulators, filters, surge suppressors, and other
safeguards shall be provided as required where power line disturbances are
likely to affect fire alarm components, data processing, equipment used for
treatment, and automated laboratory diagnostic equipment.
(4) Services and switchboards. Electrical
service and switchboards serving the required facility components shall be
installed above the designated 100-year flood plain. Main switchboards shall be
located in separate rooms, separated from adjacent areas with one-hour
fire-rated enclosures containing only electrical switchgear and distribution
panels and shall be accessible to authorized persons only. These rooms shall be
ventilated to provide an environment free of corrosive or explosive fumes and
gases, or any flammable and combustible materials. Switchboards shall be
located convenient for use and readily accessible for maintenance as required
by NFPA 70, Article 384. Overload protective devices shall operate properly in
ambient temperatures.
(5)
Panelboard. Panelboards serving normal lighting and appliance circuits shall be
located on the same floor as the circuits they serve. Panelboards serving
critical branch emergency circuits shall be located on each floor that has
major users (treatment rooms/areas, exam rooms/areas, trauma rooms/areas, etc.)
and may also serve the floor above and the floor below. Panelboards serving
life safety branch circuits may serve 3 floors, the floor where the panelboard
is located, and the floors above and below.
(6) Wiring. All conductors for controls,
equipment, lighting and power operating at 100 volts or higher shall be
installed in metal or metallic raceways in accordance with the requirements of
NFPA 70, Article 517. All surface mounted wiring operating at less than 100
volts shall be protected from mechanical injury with metal raceways to a height
of 7 feet above the floor. Conduits and cables shall be supported in accordance
with NFPA 70, Article 300.
(7)
Mechanical protection of the emergency system. The wiring of the emergency
system shall be mechanically protected by installation in nonflexible metal
raceways in accordance with NFPA 70, §517.30(C)(3).
(8) Lighting.
(A) Lighting intensity for staff and patient
needs shall comply with guidelines for health care facilities set forth in the
Illuminating Engineering Society of North America (IESNA) Handbook, 2000
edition, published by the IESNA, 120 Wall Street, Floor 17, New York, New York
10005.
(i) Light intensity and wavelength
control to prevent harm to the patient's eyes shall be considered.
(ii) Approaches to buildings and parking
lots, and all spaces within buildings shall have fixtures that can be
illuminated as necessary. All rooms and spaces including storerooms, electrical
and mechanical equipment rooms, and attics shall have sufficient artificial
lighting for clear visibility.
(iii) The special needs of the elderly shall
be considered. The facility shall minimize excessive contrast in lighting
levels that makes effective sight adaptation difficult.
(B) Means of egress and exit sign lighting
intensity shall comply with NFPA 101, §§7.8, 7.9, and 7.10.
(C) Electric lamps, which may be subject to
breakage or which are installed in fixtures in confined locations when near
woodwork, paper, clothing, or other combustible materials, shall be protected
by wire guards, or plastic shields.
(D) Ceiling mounted surgical and examination
light fixtures shall be suspended from rigid support structures mounted above
the ceiling.
(E) Trauma rooms/areas
shall have general lighting in addition to local lighting provided by special
lighting units at the procedure tables. Each fixed special lighting unit at the
tables, except for portable units, shall be connected to an independent
circuit.
(F) X-ray film
illuminators for handling at least two films simultaneously shall be provided
in each trauma room/area and treatment room/area. When the entire emergency
suite is provided with digital imaging system capabilities, a minimum of two
X-ray film illuminator viewers shall be provided. The film illuminators shall
be mounted within the central area of the emergency suite.
(9) Receptacles. Only listed hospital grade
single-grounding or duplex-grounding receptacles shall be used in the trauma,
treatment, exam, diagnostic, imaging rooms, and all patient care areas. This
does not apply to special purpose receptacles.
(A) Installations of multiple-ganged
receptacles shall not be permitted in all patient care areas.
(B) Electrical outlets powered from the
critical branch shall be provided in all patient care areas, diagnostic,
imaging, procedure and treatment locations in accordance with NFPA 99,
§4.4.2.2.2.3. At least one receptacle at each patient treatment or
procedure location shall be powered from the normal power panel. All
receptacles powered from the critical branch shall be colored red.
(C) Replacement of malfunctioning receptacles
and installation of new receptacles powered from the critical branch in
existing facilities shall be replaced or installed with receptacles of the same
distinct color as the existing receptacles.
(D) All receptacles connected to the
essential electrical system shall be identified. The face plate for the
receptacle(s) shall have a nonremovable label or be engraved indicating the
panel and circuit number.
(E) In
locations where mobile X-ray or other equipment requiring special electrical
configuration is used, the additional receptacles shall be distinctively marked
for the special use.
(F) Each
receptacle shall be grounded to the reference grounding point by means of a
green insulated copper equipment grounding conductor in accordance with NFPA
70, §517-13.
(G) Each
treatment, examination, and trauma room in the emergency suite shall have a
minimum of 6 duplex electrical receptacles located convenient to the head of
each procedure table. All other walls shall have a minimum of at least 1
receptacle.
(H) Each work table or
counter shall have access to 1 duplex receptacle for every 6 feet of table or
counter space or fraction thereof. Each work counter and table shall have at
least 1 duplex receptacle connected to the critical branch of the emergency
electrical system.
(I) A minimum of
one duplex receptacle in each wall shall be installed in each work area or room
other than storage or lockers.
(J)
Appliances shall be grounded in accordance with NFPA 99, Chapter 9.
(K) Ground fault circuit interrupters (GFCI)
receptacles shall be provided for all general use receptacles located within 3
feet of a wash basin or sink. When GFCI receptacles are used, they shall be
connected to not affect other devices connected to the circuit in the event of
a trip. Receptacles connected to the critical branch used for equipment that
should not be interrupted do not require GFCI protection. Receptacles in wet
locations, as defined by NFPA 70, §§517.20 and 517.21, shall be GFCI
protected regardless of the branch of the electrical system serving the
receptacle.
(10)
Equipment.
(A) The following shall be powered
from the Type II essential electrical system in accordance with the
requirements of NFPA 99, §3.4.2.2.3, when such a system is required for
safe operation of the facility referenced in paragraph (14) of this subsection.
(i) Boiler accessories including feed pumps,
heat-circulating pumps, condensate return pumps, fuel oil pumps, and waste heat
boilers shall be connected to the equipment system.
(ii) Ventilating system serving trauma,
treatment and exam rooms, shall be connected to the equipment system in
accordance with the requirements of NFPA 99, Chapter 3.
(B) A "kill switch" shall be provided for
disconnection of each HVAC serving the building in accordance with the
requirements of NFPA 90A, §6.2.1.
(11) Wet patient care location. Wet patient
care locations shall be protected against shock in accordance with the
requirements of NFPA 99, §4.3.2.2.9.1.
(12) Grounding requirements. Fixed electrical
equipment shall be grounded in accordance with the requirements of NFPA 99,
§4.3.3.1, and NFPA 70, Article 517.
(13) Nurses calling systems.
(A) A nurse's emergency calling system shall
be installed in the all treatment room/area station(s), exam rooms/area
station(s), isolation room(s), patient holding stations, imaging, diagnostic
and patient toilet room(s) to summon nursing staff in an emergency. Activation
of the system shall sound a distinct audible signal which repeats every 5
seconds or less at the nurse station, indicate type and location of call on the
system monitor, and activate a distinct visible signal in all areas. The
activation of the system shall also activate distinct visible signals in the
clean workroom, soiled workroom, and if provided, in the nourishment station.
The visible and audible signals shall be cancelable only at the patient calling
station. A nurse's emergency call system shall be accessible to a collapsed
patient lying on the floor. Inclusion of a pull cord extending to within 6
inches of the floor will satisfy this requirement.
(B) A staff emergency assistance calling
system station shall be located in each treatment room/area, examination
room/area, trauma room/area, and holding room/area to be used by staff to
summon additional help in an emergency. Activation of the system shall sound an
audible signal at a staffed location, indicate type and location of call on the
system monitor, and activate a distinct visible signal in the corridor at the
door. Additional visible signals shall be installed at corridor intersections
in multi-corridor facilities. Distinct visible and audible signals shall be
activated in the clean workroom, in the soiled workroom, equipment storage, and
if provided, in the nourishment station.
(14) Essential electrical system. The
facility shall provide, at submission of construction documents/plans, a letter
on facility letterhead indicating the method the facility has chosen for
implementation of the emergency contingency plan for the continuity of
emergency essential building systems (emergency generator). The contingency
plan shall consist of one of the two options as described in subparagraphs (A)
and (B) of this paragraph.
(A) An onsite
emergency generator shall be provided with a Type II essential electrical
distribution system in accordance with requirements of NFPA 99, §4.5 (2),
and National Fire Protection Association 110, Standard for Emergency and
Standby Power Systems, 2002 Edition.
(i) An
emergency generator standby power system(s) shall require an onsite fuel source
and enough fuel capacity in the tank for a period of twenty-four hours or more.
The facility shall execute a contract with an outside supplier/vendor(s) that
will provide fuel on demand. When a vapor liquefied petroleum gas (LPG)
(natural gas) system is used, the 24 hour fuel capacity on site is not
required. The vapor withdrawal LPG system shall require a dedicated fuel
supply.
(ii) The emergency
generator shall be installed, tested and maintained in accordance with the
National Fire Protection Association 99, §4.5.4, and National Fire
Protection Association 110, Standard for Emergency and Standby Power Systems,
2002 Edition.
(iii) When the
emergency generator(s) and electrical transformer(s) are located within the
same area, they shall be located at least 10 feet apart.
(iv) One electrical outlet connected to the
life safety branch of the electrical system shall be provided adjacent to (or
on) the emergency generator.
(v)
The battery charger for emergency lighting at the emergency generator shall be
connected to the life safety branch of the electrical system.
(B) An executed contract with an
outside supplier/vendor(s) that will provide a portable emergency generator(s)
and fuel on demand.
(i) An electrical transfer
switch with plug-in device sized to provide emergency power for the patient
care areas and the provisions in NFPA 99, §4.5.2.2.2.
(ii) An alternate source of power (battery
power lighting) shall be provided separate and independent from the normal
electrical power source that will be effective for a minimum of one and one
half hours after loss of the electrical power. The emergency lighting system
shall be capable of providing sufficient illumination to allow safe evacuation
from the building. The battery pack systems shall be maintained and tested
quarterly.
(iii) The facility shall
implement the emergency contingency plan upon the loss of electrical power
following a natural weather or man-made event when the electrical power may not
be restored within 24 hours. The facility shall exercise the contract(s) with
the supplier/vendor(s) to have portable emergency generator(s) available within
36 hours after the loss of electrical power.
(15) Fire alarm system. A fire alarm system
which complies with NFPA 101, §20.3.4, and with NFPA 72, Chapter 6
requirements, shall be provided in each facility. The required fire alarm
system components are as follows.
(A) A fire
alarm control panel (FACP) shall be installed at a visual location such as the
main lobby. A remote fire alarm annunciator listed for fire alarm service and
installed at a continuously attended location and capable of indicating both
visual and audible alarm, trouble, and supervisory signals in accordance with
the requirements of NFPA 72 may be substituted for the FACP.
(B) Manual fire alarm pull stations shall be
installed in accordance with NFPA 101, §20.3.4.
(C) Ceiling-mounted smoke detector(s) shall
be installed in room containing the FACP when this room is not attended
continuously by staff as required by NFPA 72, §4.4.5.
(D) Smoke detectors shall be installed in air
ducts in accordance with NFPA 72, §5.14.4.2 and §5.14.5 and NFPA 90A,
§6.4.2.
(E) Smoke detectors
shall be installed in return air ducts in accordance with requirements of NFPA
72 §5.14.4.2.2 and §5.14.5 and NFPA 90A, §6.4.2.2.
(F) Fire sprinkler system water flow switches
shall be installed in accordance with requirements of NFPA 101, §9.6.2;
NFPA 13, §6.9; and NFPA 72, §8.5.3.3.3.4.
(G) Sprinkler system valve supervisory
switches shall be installed in accordance with the requirements of NFPA 72,
§6.8.5.5.
(H) A fire alarm
signal notification which complies with NFPA 101, §9.6.3, shall be
provided to alert occupants of fire or other emergency.
(I) Audible alarm indicating devices shall be
installed in accordance with the requirements of NFPA 101, §20.3.4, and
NFPA 72, §7.4.
(J) Visual fire
alarm indicating devices which comply with the requirements of NFPA 72,
§7.5, shall be provided.
(K)
Devices for transmitting alarm for alerting the local fire brigade or municipal
fire department of fire or other emergency shall be provided. The devices shall
be listed for the fire alarm service by a nationally recognized laboratory, and
be installed in accordance with such listing and the requirements of NFPA
72.
(L) Wiring for fire alarm
detection circuits and fire alarm notification circuits shall comply with
requirements of NFPA 70, Article 760.