Current through Reg. 49, No. 38; September 20, 2024
(a) Any proposed new ESRD facility shall be
easily accessible to the community and to service vehicles such as delivery
trucks, ambulances, and fire protection apparatus. No building may be converted
for use as an ESRD facility which, because of its location, physical condition,
state of repair, or arrangement of facilities, would be hazardous to the health
and safety of the patients.
(1) An ESRD
facility shall have at least two exits remotely located in accordance with
National Fire Protection Association (NFPA) 101, Life Safety Code, 2003 Edition
(NFPA 101), §20.2.4.1. When a required means of egress from the ESRD
facility is through another portion of the building, that means of egress shall
comply with the requirements of NFPA 101 which are applicable to the occupancy
of that other building. Such means of egress shall be open, available,
unlocked, unrestricted, and lighted at all times during the ESRD facility hours
of operation. All documents published by National Fire Protection Association
(NFPA) as referenced in this section may be obtained by writing or calling the
NFPA at the following address or telephone number: National Fire Protection
Association, 1 Batterymarch Park, Quincy, Massachusetts 02269-9101 or (800)
344-3555.
(2) Hazardous locations.
(A) A new ESRD facility or an addition to an
existing ESRD facility shall not be constructed within 150 feet of easement
boundaries or setbacks of hazardous underground locations including but not
limited to liquid butane or propane, liquid petroleum or natural gas
transmission lines, high pressure lines, and not within the easement of high
voltage electrical lines. Municipality's main natural gas lines in
right-of-ways serving dwellings and gas lines on property servicing gas
meter(s) under this provision are not consider natural high pressure
lines.
(B) A new ESRD facility and
an addition to an existing ESRD facility shall not be built within 300 feet of
above ground or underground storage tanks containing liquid petroleum or other
flammable liquids used in connection with a bulk plant, marine terminal,
aircraft refueling, bottling plant of a liquefied petroleum gas installation,
or near other hazardous or hazard producing plants.
(3) Undesirable locations.
(A) In lieu of local codes, a new ESRD
facility shall not be located closer than 1500 feet to nuisance producing
industrial sites, feed lots, sanitary landfills, or manufacturing plants
producing excessive noise or air pollution.
(B) Flood plains.
(i) When a new ESRD facility is constructed
in a designated 100-year flood plain, the building finished floor elevation
shall be one foot above the set base flood plain elevation. The building shall
meet all local flood code ordinances and local flood control
requirements.
(ii) To obtain a
license as an ESRD facility, a previously licensed ESRD facility and an
existing building or a portion of an existing building located in a designated
100-year flood plain shall meet the requirement of clause (i) of this
subparagraph.
(iii) ESRD facility
required functional components shall be constructed above the designated flood
plain in a new addition to an existing ESRD facility located in a designated
100-year flood plain. The new addition shall meet the requirement of clause (i)
of this subparagraph.
(iv)
Currently licensed ESRD facilities located within a designated 100-year flood
plain are exempt from these requirements for renovations and repairs.
(b) The ESRD
facility site shall include paved roads, walkways, and parking in accordance
with the requirements set out in this subsection.
(1) Paved roads and walkways.
(A) Paved roads shall be provided within lot
lines for access from public roads to the main entrance and to service
entrances.
(B) Finished surface
walkways shall be provided for pedestrians. When public transportation or
walkways serve the site, finished surface walkways or paved roads shall extend
from the public conveyance to the building entrance.
(2) Parking and disability requirements.
(A) Off-street parking shall be available for
visitors, employees, and staff. Parking structures directly accessible from an
ESRD facility shall be separated with two-hour fire rated noncombustible
construction. When used as required means of egress for ESRD facility
occupants, parking structures shall comply with National Fire Protection
Association 88A, Standard for Parking Structures, 2002 edition. This
requirement does not apply to freestanding parking structures. All documents
published by National Fire Protection Association (NFPA) as referenced in this
section may be obtained by writing or calling the NFPA at the following address
or telephone number: National Fire Protection Association, 1 Batterymarch Park,
P.O. Box 9101, Quincy, MA 02269-9101 or (800) 344-3555.
(B) In the absence of local code, one parking
space shall be provided for each staff member on duty, plus one space for each
four treatment stations, and one visitor's space for every five treatment
stations. This ratio may be reduced in an area convenient to a public
transportation system or to public parking facilities. Parking facilities shall
be increased accordingly when the size of existing facilities is
increased.
(C) When on-street
parking is available and acceptable to the local authorities having
jurisdiction, the numbers of parking spaces may be reduced accordingly and
shall meet the requirement of subparagraph (B) of this paragraph.
(D) Special considerations benefiting
disabled staff, visitors, and patients shall be provided. Each ESRD facility
shall comply with the Americans with Disabilities Act (ADA) of 1990, Public Law
101 - 336, 42 United States Code, Chapter 126, and Title 36 Code of Federal
Regulations, Part 1191, Appendix A, Accessibility Guidelines for Buildings and
Facilities or 16 Texas Administrative Code, Part 4, Chapter 68, §68.20
(relating to Buildings and Facilities Subject to Compliance with the Texas
Accessibility Standards), Texas Accessibility Standards (TAS), April 1, 1994
edition, issued by the Texas Department of Licensing and Regulation, under the
Texas Architectural Barriers Act, Texas Government Code, Chapter 469.
(c) Every building and
every portion thereof shall be designed and constructed to sustain all dead and
live loads in accordance with accepted engineering practices and standards and
the local governing building codes. Where there is no local governing building
code, the ESRD facility shall be constructed in accordance with the
International Building Code, 2003 edition, published by the International Code
Council, 500 New Jersey Avenue, Northwest, 6th Floor, Washington, District of
Columbia 20001-2070, (800) 344-3555.
(1) All
new construction, including conversion of an existing building to an ESRD
facility or establishing a separately licensed ESRD facility within another
existing building, shall comply with NFPA 101, Chapter 20, New Ambulatory
Health Care Occupancies, of the National Fire Protection Association 101, Life
Safety Code, 2003 edition (NFPA 101), and subchapters G and H of this chapter
(relating to Fire Prevention and Safety Requirements, and Physical Plant and
Construction Requirements, respectively). Construction documents shall be
submitted to the department in accordance with §
117.104
of this title (relating to Preparation, Submittal, Review and Approval of
Plans, and Retention of Records).
(A)
Construction types for multiple building occupancy.
(i) When an ESRD facility is part of a larger
building which complies with NFPA 101, §20.1.6, Minimum Construction
Requirements for (fire resistance) construction type, the designated ESRD
facility shall be separated from the remainder of the building with a minimum
of one-hour fire rated construction.
(ii) When an ESRD facility is located in a
multistory building of two or more stories, the entire building shall meet the
construction requirements of NFPA 101, §20.1.6.3. An ESRD facility shall
not be located in a multistory building which does not comply with the minimum
construction requirements of NFPA 101, §20.1.6.3.
(iii) When an ESRD facility is part of a
one-story building that does not comply with the construction requirements of
NFPA 101, §20.1.6.2, the ESRD facility shall be separated from the
remainder of the building with a 2-hour fire rated construction. The designated
ESRD facility portion shall have the construction type upgraded to comply with
NFPA 101, §20.1.6.2.
(B) Special provisions shall be made in the
design of a facility if located in a region where local experience shows loss
of life or extensive damage to buildings resulting from hurricanes, tornadoes,
or floods.
(2) A
physical environment that protects the health and safety of patients,
personnel, and the public shall be provided in each facility. The physical
premises of the facility and those areas of the facility's physical structure
that are used by the patients (including all stairwells, corridors, and
passageways) shall meet the local building and fire safety codes and the
requirements of this chapter.
(3)
The more stringent standard, code or requirement shall apply when a difference
in requirements for construction exists.
(4) Nothing in this subchapter shall be
construed to prohibit a better type of building construction, more exits, or
otherwise safer conditions than the minimum requirements specified in this
subchapter.
(5) Nothing in this
subchapter is intended to prevent the use of systems, methods, or devices of
equivalent or superior quality, strength, fire resistance, effectiveness,
durability, safety to health and welfare of individuals, and safety to those
prescribed by this subchapter, provided technical documentation which
demonstrates equivalency is submitted to the department for approval.
(6) Separate freestanding buildings for
nonpatient use such as the heating plant, boiler plant, laundry, repair
workshops, or general storage may be of unprotected noncombustible
construction, protected noncombustible construction, or fire-resistive
construction and be designed and constructed in accordance with other occupancy
classifications requirements listed in NFPA 101.
(d) Spatial requirements.
(1) Administration and public areas.
(A) Patient entrances shall be located at
grade level, be accessible to individuals with disabilities, and provide
exterior covered protection against inclement weather. The minimum exterior
protection covering shall be no smaller than 4 feet by 6 feet wide. A covered
area for patients in wheelchairs shall be provided next to the opening area of
the door swing and door swing shall not interfere within this area. When an
ESRD is located on a floor above grade level, elevators shall be accessible and
shall meet the requirements of §
117.103
of this title (relating to Elevators, Escalators, and Conveyors).
(B) A waiting area or lobby shall be provided
within the ESRD facility and include having the following rooms and items:
(i) public toilet facilities; and
(ii) telephone(s) for public use.
(C) A designated reception area
with desk or counter shall be provided.
(D) Space shall be provided for private
interviews for family members relating to social services, credit, or
admission.
(E) An office(s) shall
be provided for business transactions, records, and administrative and
professional staff.
(F) The
facility shall provide an area for storage of clinical records which is
separate from all patient treatment areas, and shall be secured from
unauthorized access. The facility shall store the active clinical record of
each patient currently treated by the facility on site.
(G) A general storage room with a minimum of
2 square feet per treatment station shall be provided. General storage may be
located in one or more rooms or closets, and shall be located outside of the
patient treatment areas.
(H)
Storage space for wheelchairs shall be provided, and shall be out of the direct
line of traffic.
(2)
Equipment rooms with adequate space shall be provided for mechanical and
electrical equipment. These areas shall be separate from public, patient, and
staff areas.
(3) An exam room shall
be provided for medical examinations. The room shall have a minimum clear floor
space of 80 square feet area exclusive of fixed cabinets and shelves and
contain a counter for writing and a hand washing sink with hands-free operable
controls.
(4) When a patient is
hepatitis B positive, the treatment shall be in a separated dedicated isolation
room. All treatment in the isolation room shall be for hepatitis B patients
only.
(A) A single hepatitis B patient
isolation room shall be a minimum of 120 square feet clear area exclusive of
fixed and movable cabinets and shelves.
(B) When multiple-treatment stations for
hepatitis B patients are treated in a single isolation room, each individual
patient treatment area shall be 80 square feet with a minimum of 8 feet clear
dimension exclusive of fixed or wall mounted cabinets and built-in shelves. The
clearance between the side of a station/chair and a wall/partition shall be a
minimum of 3 feet. The clearance between sides of stations/chairs shall be a
minimum of 4 feet.
(C) The
isolation treatment room shall include a work counter and a hand washing sink
with hands-free operable controls, and space for patient care supplies and
equipment. The fixed and moveable cabinets and shelves shall not encroach upon
the patient treatment station/chair clear floor space/area.
(D) The isolation treatment room shall have
viewing panels in doors and/or walls for continuous direct visual monitoring of
the patient in the room.
(E) The
dialysis equipment shall be designated, reserved, and used for hepatitis B
positive patients only.
(F)
Disinfection of dialysis equipment shall occur in the hepatitis B treatment
isolation room and shall meet the requirements of §
117.33(d)(2)(C)
of this title (relating to Sanitary Conditions and Hygienic
Practices).
(G) As of February 9,
2009, all new facilities or increasing the number of in-center dialysis
treatment stations in existing facilities shall have an isolation room or be
granted a waiver by Centers for Medicare and Medicaid Services. The waiver
shall demonstrate that there is sufficient capacity in the geographic area for
isolation rooms for hepatitis B positive patients. A written request for waiver
shall be made through the Texas Department of State Health Services, Health
Facility Compliance Group, Mail Code 1979, P.O. Box 149347, Austin, Texas,
78714-9347 for transmission to CMS.
(5) When home training is provided in the
facility, a private treatment area of at least 120 square feet exclusive of
fixed and movable cabinets and shelves shall be provided. This room shall
contain a work counter, a hand washing sink with hands-free operable controls,
and a separate drain for fluid disposal.
(6) A sufficient number of janitor's closets
shall be provided throughout the facility to maintain a clean and sanitary
environment. The closet shall contain a floor receptor or service sink and
storage space for housekeeping supplies and equipment.
(7) When laboratory services are provided on
site the following shall be provided and meet the requirements of §
117.45(l)
of this title (relating to Provision and Coordination of Treatment and
Services).
(A) The laboratory workroom/area
shall include a counter and a sink with hands-free operable controls.
Laboratory services and medication preparation and dispensing shall not be done
within the same designated space.
(B) Cabinets or closets shall be provided for
supplies and equipment used in obtaining samples for testing.
(C) Refrigerated specimen storage shall be
provided for specimens waiting for transfer to off-site testing. The
refrigerators shall be maintained with documentation of the appropriate
temperature for such storage.
(8) When laundry and linen is provided,
processing may be done within the center or off site at a commercial laundry.
(A) When on-site linen processing is
provided, soiled and clean processing operations shall be separated and
arranged to provide a one-way traffic pattern from soiled to clean areas. The
following rooms and items shall be provided:
(i) a soiled linen processing room which
includes areas for receiving, holding, sorting, and washing;
(ii) a clean linen processing room which
includes areas for drying, sorting, folding, and holding prior to
distribution;
(iii) supply storage
cabinets in the soiled and clean linen processing rooms;
(iv) hand washing sink within the soiled
linen processing room; and
(v) a
storage room for clean linen. Clean linen storage may be combined with the
clean work room.
(B)
When linen is processed off site, the following areas shall be provided:
(i) clean linen shall be stored within the
clean supply area; and
(ii) soiled
linen shall be stored in a designated space in the facility.
(9) Space shall be
provided for the safe storage and disposal of waste as appropriate for the
material being handled and in compliance with all applicable rules and
regulations.
(10) At a minimum, the
medication area shall include a counter, a refrigerator, and a hand washing
sink with hands-free operable controls. Storage and preparation of medication
shall be done from a medication area and shall be under visual control of
nursing staff. Medication preparation, dispensing and laboratory services shall
not be done within the same designated areas. The refrigerators used for
storage of medications shall be maintained with documentation of the
appropriate temperatures for such storage.
(11) When peritoneal dialysis (PD) training
is provided within the ESRD facility, a patient treatment training room shall
have a minimum of 120 square feet of clear floor area exclusive of fixed and
movable cabinets and shelves.
(A) The PD
treatment room shall contain cabinets, a work counter, and a hand washing sink
with hands-free operable controls.
(B) An additional clinical sink or equivalent
flushing rim sink with hands-free operable controls shall be provided. The
clinical sink or equivalent flushing rim sink and the hand washing sink shall
have a minimum separation of 6 feet.
(C) A physical partition between the clinical
sink or equivalent flushing rim sink and the hand washing sink may be
constructed in-lieu-of the 6 foot separation. The partition shall be a minimum
of 5 feet in height from the finished floor and 2 feet in width from the wall
or from the wall to the front edge of the countertop whichever is
greater.
(12) When a
reuse room is provided, the room shall be sufficiently sized to house dialyzers
reprocessing area, breakdown area, a storage area/room and work area. All fixed
and moveable equipment shall require a minimum of three feet of clear and
unobstructed working space on all sides of fixed or moveable equipment that
require access for staff. The reuse room shall include a work counter, deep
utility service sink and separate hand washing sink with hands-free operable
controls, refrigerator and storage space and shall meet the requirements of
§
117.32(d)
of this title (relating to Water Treatment, Dialysate Concentrates, and Reuse).
(A) Dialyzers reprocessing area shall be
arranged for the one-way movement from soiled dialyzers and materials to
cleaning and storage.
(B) Breakdown
of dialyzers shall be processed in the soiled processing area of the
reprocessing area. The deep utility service sink with hands-free operable
controls shall be located within the soiled processing area. There shall be
adequate storage space to store the soiled/used dialyzers before processing
occurs. The minimum depth of the utility sink shall not be less than 14
inches.
(C) The reuse room shall
provide either a separate storage room or within the reuse room storage space
to store all reprocessed cleaned dialyzers. There shall be a definitive
separation between storing used and reprocessed dialyzers, and the temperature
in the storage areas shall be maintained in accordance with the manufacturer's
direction for use.
(13)
The treatment area(s) or rooms shall be separate from the administrative
area(s).
(A) When individual hemodialysis
patient treatment room(s) is provided, the room shall have a minimum of 120
square feet of clear floor area exclusive of fixed and movable cabinets and
shelves. The patient treatment room shall contain cabinets, work counter, and a
hand washing sink with hands-free operable controls.
(B) In multiple-treatment stations, each
individual patient treatment area shall be 80 square feet exclusive of fixed or
wall mounted cabinets and built-in shelves. A minimum of 8 feet width shall be
provided for the head wall for each station. The clearance between the side of
a chair and a wall shall be a minimum of 3 feet, and the back of the extended
chair and a wall shall be a minimum of 1 foot. A clear unobstructed width of 3
feet 8 inches shall be available at the foot of each treatment area(s) outside
of the 80 square feet treatment area for passage of equipment, gurneys, and
personnel.
(C) The
multiple-treatment station area shall contain cabinets, work counters, and hand
washing sinks with hands-free operable controls. The fixed and moveable
cabinets and shelves shall not encroach upon the patient treatment
station.
(D) A nurse station shall
be located within the dialysis treatment area(s) and designed to provide visual
observation of all patient stations. The nurse station shall have counters for
storage and access to a hand washing sink(s) with hands-free operable
controls.
(E) One hand washing sink
with hands-free operable controls shall be provided for every six stations.
Sinks shall be uniformly distributed.
(F) When required or requested, privacy shall
be provided for each patient in the open treatment area with portable moveable
screens.
(e)
Service areas.
(1) A clean storage room or
closet shall be provided for patient care items, clean and sterile
supplies.
(2) Emergency eyewash
shall be provided conveniently for staff use and comply with ANSI
Z358.1.
(3) Dialysis solutions may
be processed from a central batch delivery system or prepared in an on-site
mixing room. When provided, a mixing room shall include a sink, storage space,
and holding tanks.
(4) Patient
toilet rooms shall be located within the treatment area(s) and include hand
washing sink(s) with hands-free operable controls. Patient toilet room shall be
at a ratio of 1 toilet room for every 40 treatment stations or fraction
thereof.
(5) Staff toilet room(s)
shall be provided and include hand washing sink(s) with hands-free operable
controls. The toilet room shall be outside the treatment area but convenient
for staff use only.
(6) The water
treatment and equipment for the dialysis shall be located in a room not
accessible to unauthorized persons. The water room shall be designed and house
the water treatment system and meet the requirements of §
117.32(b)
of this title.
(f)
Details and finishes in new construction projects, including additions and
alterations, shall be in compliance with this subsection, with NFPA 101,
Chapter 20, and with local building codes.
(1)
General detail requirements.
(A) Fire safety
features, including compartmentation, means of egress, automatic extinguishing
systems, inspections, smoking regulations, and other details relating to fire
prevention and fire protection shall comply with §
117.101
of this title (relating to Construction Requirements for an Existing End Stage
Renal Disease Facility), and NFPA 101, Chapter 20. The Fire Safety Evaluation
System for Health Care Occupancies contained in the National Fire Protection
Association 101A, Alternative Approaches to Life Safety, 2001 Edition, Chapter
4, shall not be used in new building construction, renovations or additions to
existing ESRD facilities.
(B)
Exits, corridors and doors.
(i) A facility
shall provide two exits remote from each other in accordance with NFPA 101,
§20.2.4.1. At least one exit door shall be accessible by an ambulance from
the outside. This door may also serve as an entry for loading or receiving
goods.
(ii) Corridors providing
access to all patient treatment area(s) and exits shall be at least three feet
eight inches in clear and unobstructed width, not less than seven feet six
inches in height, and constructed in accordance with requirements listed in
NFPA 101, §20.2.1.
(iii) Items
such as drinking fountains and vending machines shall be so located as to not
project into and restrict exit corridor traffic or reduce the exit corridor
width below the required minimum. Portable equipment shall not be stored so as
to project into and restrict exit corridor traffic or reduce the exit corridor
width below the required minimum.
(iv) Doors at all openings between corridors
and rooms or spaces subject to occupancy shall be swing type. Elevator doors
are excluded from this requirement.
(v) Doors, except doors to spaces such as
small closets which are not subject to occupancy, shall not swing into
corridors in a manner that might obstruct traffic flow or reduce the required
corridor width. Large walk-in type closets are considered as occupiable
spaces.
(vi) All doors in the means
of egress shall be not less than 36 inches in clear width.
(vii) The minimum width of doors for patient
access to treatment, examination, and consultation areas/rooms shall be 36
inches in clear width.
(viii) Rooms
containing a toilet, intended for patient use, shall be provided with at least
one door having hardware which will permit access from the outside in any
emergency.
(ix) Horizontal sliding
doors serving an occupant load of fewer than 10 shall be permitted. The area
served by the door shall have no high hazard contents. The door shall be
readily operable from either side without special knowledge or effort. The
force required to operate the door in the direction of door travel shall be not
more than 30 pounds per foot to set the door in motion, and shall be not more
than 15 pounds per foot to close the door or open in the minimum required
width. The door assembly shall comply with any required fire protection rating,
and, where rated, shall be self-closing or automatic closing. The sliding doors
opening to the egress corridor doors shall have a latch or other mechanism that
ensures that the doors will not rebound into a partially open position if
forcefully closed. The sliding doors may have breakaway provisions and shall be
installed to resist passage of smoke. The latching sliding panel shall have a
minimum clear opening of 36 inches in the fully open position. The fixed panels
may have recessed tracks.
(x) Doors
shall not open immediately onto a stair without a landing. The landing shall be
44 inches deep or have a depth at least equal to the door width, whichever is
greater.
(xi) All fire doors shall
be listed by an independent testing laboratory and shall meet the construction
requirements for fire doors in National Fire Protection Association 80,
Standard for Fire Doors and Fire Windows, 1999 Edition. Reference to a labeled
door shall be construed to include labeled frame and hardware.
(C) Glass doors, lights,
sidelights, borrowed lights, and windows located within 12 inches of a door
jamb or with a bottom-frame height of less than 18 inches and a top-frame
height of more than 36 inches above the finished floor which may be broken
accidentally by pedestrian traffic shall be glazed with safety glass or plastic
glazing material that will resist breaking and will not create dangerous
cutting edges when broken. Similar materials shall be used for wall openings in
activity areas such as recreation and exercise rooms, unless otherwise required
for fire safety. Safety glass, tempered or plastic glazing materials shall be
used for shower doors and bath enclosures, interior windows and doors. Plastic
and similar materials used for glazing shall comply with the flame spread
ratings of NFPA 101, §18.3.3.
(D) Grab bars shall be provided at patient
toilets and at the weight scales. The bars shall be one and one-half inches in
diameter, shall have either one and one-fourth or one and one-half inches
clearance to walls, and shall have sufficient strength and anchorage to sustain
a concentrated vertical or horizontal load of 250 pounds. Grab bars intended
for use by the disabled shall also comply with ADA requirements.
(E) Location and arrangement of fittings for
hand washing sinks shall permit their proper use and operation. Hand washing
sinks with hands-free operable controls shall be provided within each workroom,
examination, treatment room, and toilet room. Hands-free includes blade-type
handles, and foot, knee, or sensor operated controls. Particular care shall be
given to the clearances required for blade-type operating handles. Lavatories
and hand washing sinks shall be securely anchored to withstand an applied
vertical load of not less than 250 pounds on the front of the sink. In addition
to the specific areas noted, hand washing sinks shall be provided and
conveniently located for staff use throughout the ESRD facility where patient
care contact occurs and services are provided.
(F) A liquid or foam soap dispenser shall be
located at each hand washing sink.
(G) Provisions for hand drying shall be
included at all hand washing sinks. There shall be hot air dryers or individual
paper towel dispensers enclosed in such a way as to provide protection against
dust or soil and ensure single-unit dispensing.
(H) The minimum ceiling height shall be eight
feet with the following exceptions.
(i) Boiler
rooms shall have ceiling clearances not less than two feet six inches above the
main boiler header and connecting piping.
(ii) Rooms containing ceiling-mounted
equipment shall have the ceiling height clearance increased to accommodate the
equipment or fixtures.
(iii)
Suspended tracks, rails, pipes, signs, lights, door closers, exit signs, and
other fixtures that protrude into the path of normal traffic shall not be less
than six feet eight inches above the finished floor.
(I) The dialysis facility shall not be
located directly under recreation rooms, exercise rooms, and similar spaces
where impact noises may be generated unless special provisions are made to
minimize noise.
(J) Rooms
containing heat-producing equipment such as heater rooms, laundries, etc. shall
be insulated and ventilated to prevent any occupied floor surface above from
exceeding a temperature differential of 10 degrees Fahrenheit above the ambient
room temperature.
(K) Thresholds
and expansion joint covers shall be flush or not more than one-half inch above
the floor surface to facilitate the use of wheelchairs and carts. Expansion and
seismic joints shall be constructed to restrict the passage of smoke and fire
and shall be listed by a nationally recognized testing laboratory.
(2) General finish requirements.
(A) Portable privacy screens shall be
provided to assure patient privacy when required or requested by a patient.
When not in use the screens shall be stored conveniently within the treatment
area for immediate use.
(B) Flame
spread and smoke developed limitations of interior finishes shall comply with
NFPA 101, §10.2. The use of materials known to produce large or
concentrated amounts of noxious or toxic gases shall not be used in exit
accesses or in patient areas. Copies of laboratory test reports for installed
materials tested in accordance with National Fire Protection Association 255,
Standard Method of Test of Surface Burning Characteristics of Building
Materials, 2000 Edition, and National Fire Protection Association 258, Standard
Research Test Method for Determining Smoke Generation of Solid Materials, 2001
Edition, shall be provided.
(C)
Flooring shall be easy to clean and have wear resistance appropriate for the
location involved. Floors that are subject to traffic while wet shall have a
nonslip surface. In all areas frequently subject to wet cleaning methods, floor
materials shall not be physically affected by germicidal and cleaning
solutions. The following are acceptable floor finishes:
(i) painted concrete for water treatment
areas, mechanical, electrical, janitor's closets and general storage;
(ii) exposed concrete shall be sealed for
water treatment areas, mechanical, electrical, janitor's closets and general
storage;
(iii) vinyl sheets and
vinyl composition tiles for offices, lobbies, administrative areas, storage,
toilet rooms, treatment areas/rooms, isolation treatment room, exam rooms,
training room, reprocessing rooms, support spaces and nontreatment
areas;
(iv) when monolithic or
seamless flooring is installed it shall be impervious to water, coved and
installed integral with the base, tightly sealed to the wall, and without voids
that can harbor insects or retain dirt particles. The base shall not be less
than six inches in height. Welded joint flooring is acceptable;
(v) marble, ceramic and quarry tile for
offices, lobbies, waiting, toilet rooms, administrative areas, wet areas, and
similar spaces;
(vi) carpet
flooring for offices, administrative areas, and similar spaces; and
(vii) terrazzo for offices, lobbies,
administrative areas, and similar spaces.
(D) Wall finishes shall be smooth, washable,
moisture resistant, and cleanable.
(i) Wall
finishes shall be water-resistant in the immediate area of plumbing
fixtures.
(ii) Wall finishes
subject to frequent wet cleaning methods shall be impervious to water, tightly
sealed and without voids.
(E) Ceilings which are a part of a rated
roof/ceiling assembly or a floor/ceiling assembly shall be constructed of
listed components and installed in accordance with the listing. Three types of
ceilings that are required in various areas of the ESRD facility are:
(i) ordinary ceilings are required in all
areas or rooms in the ESRD facility unless a requirement requires a specific
type of ceiling for such space. This includes ceilings such as acoustical tiles
installed in a metal grid which are dry cleanable with equipment used in daily
housekeeping activities such as dusters and vacuum cleaners;
(ii) washable ceilings are ceilings that are
made of washable, smooth, moisture impervious materials such as painted lay-in
gypsum wallboard or vinyl faced acoustic tile in a metal grid when installed in
the water treatment room and reuse room;
(iii) monolithic ceilings which are
monolithic from wall to wall (painted solid gypsum wallboard), smooth and
without fissures, open joints, or crevices and with a washable and moisture
impervious finish shall be provided for the isolation room and reuse room;
and
(iv) no finished ceiling is
required in mechanical, electrical, general storage, and water treatment
rooms.
(F) Floor, wall
and ceiling penetrations by pipes, ducts, and conduits, or any direct openings
shall be tightly sealed to minimize entry of dirt particles, rodents and
insects. Joints of structural elements shall be similarly sealed.
(G) Materials known to produce noxious gases
when burned shall not be used for mattresses, upholstery, and wall
finishes.
(H) A sign shall be
posted at the entrance to each toilet/restroom to identify the facility for
public, staff or patient use.
(I)
When vinyl sheets and vinyl composition tiles are used for toilet rooms,
treatment areas/rooms, isolation treatment rooms, exam rooms, training rooms,
and reprocessing rooms the joints shall be sealed to prevent moisture and blood
from seeping into the joints and under the tile.
(g) This subsection contains
common requirements for mechanical systems; steam and hot and cold water
systems; air conditioning, heating and ventilating systems; and thermal and
acoustical insulation.
(1) When mechanical
equipment is exposed to weather, it shall be protected by weatherproof
construction or weather protected.
(2) Mechanical equipment shall be mounted on
vibration isolators as required to prevent unacceptable structure-borne
vibration. Ducts, pipes, etc. connected to mechanical equipment which is a
source of vibration shall be isolated from the equipment with vibration
isolators.
(3) Prior to completion
and acceptance of the facility, all mechanical systems shall be tested,
balanced, and operated to demonstrate to the design engineer or his
representative that the installation and performance of these systems conform
to the requirements of the plans and specifications.
(A) Upon acceptance of the mechanical system,
the owner shall be provided with parts lists and procurement information with
numbers and description for each piece of equipment.
(B) Upon acceptance of the mechanical system,
the owner shall be provided with instructions in the operational use of systems
and equipment as required.
(4) All heating, ventilating and air
conditioning (HVAC) systems shall comply with and shall be installed in
accordance with the requirements of National Fire Protection Association 90A,
Standard for the Installation of Air Conditioning and Ventilating Systems, 2002
edition (NFPA 90A), NFPA 99, Chapter 6 and the requirements contained in this
subsection.
(5) All rooms and areas
in the ESRD facility shall have provision for positive ventilation. Fans
serving exhaust systems shall be located at the discharge end and shall be
conveniently accessible for service. Exhaust systems may be combined, unless
otherwise noted, for efficient use of recovery devices required for energy
conservation. Supply air to the building and exhaust air from the building
shall be regulated to provide a positive pressure within the building with
respect to the exterior.
(A) The systems
serving all treatment areas/rooms, exam rooms, and isolation rooms, shall be
capable of maintaining a temperature range between 68 and 78 degrees Fahrenheit
and a relative humidity range between 45% and 60%.
(B) The indoor design temperature in all
other areas shall be between 68 and 75 degrees Fahrenheit with relative
humidity of not less than 30%.
(6) Ventilation systems for the reuse room
and airborne isolation room shall be connected to an air exhaust system to the
outdoors which is separate from the building exhaust system, have an exhaust
fan located at the discharge end of the system, and have an exhaust duct system
of noncombustible corrosion-resistant material as needed to meet the planned
usage of the system.
(A) The bottoms of
wall-mounted return and exhaust air openings shall be at least six inches above
the floor. All exhaust air openings and return air openings located higher than
six inches but less than seven feet above the floor shall be protected with
grilles or screens having openings through which a one-half inch sphere will
not pass.
(B) Exhaust outlets shall
be above the roof level and arranged to minimize recirculation of exhaust air
into the building. Exhaust outlets shall be located at least 25 feet from any
fresh air intake of ventilating systems. (Prevailing winds and proximity to
other structures may require more stringent requirements.) Plumbing and vacuum
vents that terminate five feet above the level of the top of the air intake may
be located as close as 10 feet.
(C)
If applicable, the reuse room and the airborne isolation room exhaust systems
shall be connected to the emergency electrical system and shall meet the
requirements of paragraph (10) of this subsection.
(7) All toilet exhaust ventilation shall be
exhausted to the outdoors. Exhaust systems may be combined, unless otherwise
noted, for efficient use of recovery devices required for energy
conservation.
(8) To reduce utility
costs, facility design may utilize energy conserving procedures including
recovery devices, variable air volume, load shedding, systems shutdown, or
reduction of ventilation rates (when specifically permitted) in certain areas
when unoccupied. In no case shall patient care be jeopardized.
(9) Mechanical systems shall be arranged to
take advantage of outside air conditions by using an economizer cycle when
appropriate to reduce heating and cooling systems loads. Innovative design that
provides for additional energy conservation while meeting the intent of this
subsection for acceptable patient care may be presented to the department for
consideration.
(10) Outside air
intakes shall be located at least 25 feet from exhaust outlets of ventilating
systems, combustion equipment stacks, plumbing vents, or areas which may
collect vehicular exhaust or other noxious fumes. (Prevailing winds and
proximity to other structures may require more stringent requirements).
Plumbing vents that terminate five feet above the level of the top of the air
intake may be located as close as 10 feet.
(11) Fully ducted supply, return and exhaust
air for HVAC systems shall be provided for all patient treatment care areas,
storage rooms, and where required for fire safety purposes. Combination
systems, utilizing both ducts and plenums for movement of air in these areas,
shall not be permitted.
(12) Air
handling systems shall not be started or operated without 30% or equal minimum
efficient rating value (merv) of 8 and the filters installed in place. Ducts
shall be cleaned thoroughly and throughout by a certified air duct cleaning
contractor when the air handling systems have been operating without the
required filters in place. When ducts are determined to be dirty or dusty, the
department shall require a written report assuring cleanliness of duct and
clean air quality.
(13) Ductwork
with duct-mounted humidifiers shall be provided with a means of removing water
accumulation. An adjustable high-limit humidistat shall be located downstream
of the humidifier to reduce the potential of condensation inside the duct. All
duct take-offs shall be sufficiently downstream of the humidifier to ensure
complete moisture absorption. Reservoir-type water spray or evaporative pan
humidifiers shall not be used.
(14)
All central air handling systems shall be equipped with filters having
efficiencies 30% or equal to 8 merv. Filter efficiencies shall be average
efficiencies tested in accordance with American Society of Heating,
Refrigerating, and Air-Conditioning Engineers (ASHRAE), Inc., Standard 52.2,
1999 edition, Method of Testing General Ventilation Air-Cleaning Devices for
Removal Efficiency by Particle Size. All joints between filter segments, and
between filter segments and the enclosing ductwork, shall have gaskets and
seals to provide a positive seal against air leakage. Air handlers serving more
than one room shall be considered as central air handlers. All documents
published by ASHRAE as referenced in this section may be obtained by writing or
calling the ASHRAE, Inc. at the following address or telephone number: ASHRAE,
Inc., 1791 Tullie Circle, Northeast, Atlanta, Georgia 30329; telephone (404)
636-8400.
(A) Filtration requirements for air
handling units serving single rooms. Dedicated air handlers serving single
rooms shall be equipped with nominal filters installed at the return air
system.
(B) A filter bed shall be
located upstream of the supply fan. Filter frames shall be durable and
constructed to provide an airtight fit with the enclosing ductwork.
(15) Thermal and acoustical
insulation for air handling systems. Asbestos insulation shall not be used.
(A) Air ducts and casings with outside
surface temperature below ambient dew point or temperature above 80 degrees
Fahrenheit shall be provided with thermal insulation.
(B) Linings in air ducts and equipment shall
meet the Erosion Test Method described in Underwriters Laboratories (UL), Inc.,
Standard Number 181 (relating to Factory-Made Duct Materials and Air Duct
Connectors), April 4, 1996 edition. This document may be obtained from the
Underwriters Laboratories, Inc., 333 Pfingsten Road, Northbrook, Illinois
60062-2096.
(C) Interior and
exterior insulation, including finishes and adhesives on the exterior surfaces
of ducts and equipment, shall have a flame spread rating of 25 or less and a
smoke developed rating of 50 or less as required by NFPA 90A, Chapters 4 and
5.
(D) Insulation of soft and
spray-on types shall not be used where it is subject to air currents or
mechanical erosion or where loose particles may create a maintenance
problem.
(16) Fire
dampers shall be located and installed in all ducts at the point of penetration
of a required two-hour or higher fire rated wall or floor in accordance with
the requirements of NFPA 101, §20.1.
(17) Smoke dampers shall be located and
installed in accordance with the requirements of NFPA 101, and NFPA 90A,
Chapter 5.
(A) Smoke dampers shall close on
activation of the fire alarm system by smoke detectors installed and located as
required by National Fire Protection Association 72, National Fire Alarm Code,
2002 Edition (NFPA 72), Chapter 8; NFPA 90A, Chapter 6; and NFPA 101,
§18.3.7; the fire sprinkler system; and upon loss of power. Smoke dampers
shall not close by fan shutdown alone unless it is a part of an engineered
smoke removal system.
(B) Air
handling fans and smoke damper controls may be interconnected so that closing
of smoke dampers will not damage the ducts.
(C) Use of frangible devices for shutting
smoke dampers is not permitted.
(18) Only fire damper and smoke damper
assemblies integral with sleeves and listed for the intended purpose shall be
acceptable.
(19) Unobstructed
access to duct openings in accordance with NFPA 90A, §4.3.4, shall be
provided in ducts within reach and sight of every fire damper, smoke damper and
smoke detector. Each opening shall be protected by an internally insulated door
which shall be labeled externally to indicate the fire protection device
located within.
(20) Controls for
restarting fans may be installed for convenient fire department use to assist
in evacuation of smoke after a fire is controlled, provided that provisions are
made to avoid possible damage to the system because of closed dampers. To
accomplish this, smoke dampers shall be equipped with remote control
devices.
(h) All piping
systems and plumbing fixtures shall be designed and installed in accordance
with the requirements of the National Standard Plumbing Code Illustrated
published by the National Association of Plumbing-Heating-Cooling Contractors
(PHCC), 2003 edition, and this paragraph. The National Standard Plumbing Code
may be obtained by writing or calling the PHCC at the following address or
telephone number: Plumbing-Heating-Cooling Contractors, Post Office Box 6808,
Falls Church, Virginia 22046; telephone (800) 533-7694.
(1) Piping systems.
(A) Water service pipe to point of entrance
to the building shall be brass pipe, copper tube (not less than type M when
buried directly), copper pipe, cast iron water pipe, galvanized steel pipe, or
approved plastic pipe. Domestic water distribution system piping within
buildings shall be brass pipe, copper pipe, copper tube, or galvanized steel
pipe. Piping systems shall be designed to supply water at sufficient pressure
to operate all fixtures and equipment during maximum demand.
(i) Each water service main, branch main,
riser, and branch to a group of fixtures shall be equipped with accessible and
readily identifiable shutoff valves. Stop valves shall be provided at each
fixture.
(ii) Backflow preventers
(vacuum breakers) shall be installed on hose bibbs, laboratory sinks, janitor
sinks, and on all other fixtures to which hoses or tubing can be attached.
Backflow preventers are not required for hoses that are directly connected to
the dialysis machines.
(iii) Flush
valves installed on plumbing fixtures shall be of a quiet operating type,
equipped with silencers.
(iv) Hot
water distribution systems for patient care areas shall be under constant
recirculation to provide continuous hot water at each hot water outlet.
Nonrecirculated fixtures branch piping shall not exceed 25 feet in length.
Tankless water system may be used at point of use.
(v) Water heating equipment shall have
sufficient capacity to supply water for clinical, use.
(vi) Water temperatures shall be measured at
hot water point of use, and shall be between 105 - 120 degrees
Fahrenheit.
(vii) The domestic hot
water system shall make provisions to limit the amount of Legionella bacteria
and opportunistic waterborne pathogens.
(viii) Domestic water storage tank(s) shall
be fabricated of corrosion-resistant metal or lined with noncorrosive material.
When potable water storage tanks (hot and cold) are used, the water shall be
used and replenished. Water shall not be stored in tanks for future use unless
the water is tested weekly for contaminates/bacteria.
(ix) Purified water distribution system
piping shall be task specific and include, but not necessarily be limited to,
polypropylene (PP), polyvinylidene fluoride (PVDF) or polyvinyl chloride (PVC)
pipe. Final installed purified water system piping assemblies shall be UL
approved and fully comply with applicable American Society for Testing and
Materials (ASTM) Fire Resistant/Smoke Density requirements. The applicable
documents are available from ASTM International, 100 Barr Harbor Drive, Post
Office Box C700, West Conshohocken, Pennsylvania 19428-2959.
(B) When fire sprinkler systems
are required and provided in an ESRD facility, the fire sprinkler systems shall
be designed, installed, and maintained in accordance with the requirements of
NFPA 13, and shall be certified as required by §
117.105(c)(1)(C)
of this title (relating to Construction, Inspections, and Approval of
Project).
(C) Main storage of
medical gases may be outside or inside the ESRD facility in accordance with
NFPA 99, §5.1.
(D) Steam and
hot water systems.
(i) When boilers are used
the boilers shall have the capacity, based upon the net ratings as published in
The I-B-R Ratings Book for Boilers, Baseboard Radiation and Finned Tube
(commercial) by the Hydronics Institute Division of GAMA, to supply the normal
requirements of all systems and equipment. The document published by the
Hydronics Institute Division of GAMA as referenced in this rule may be obtained
by writing or calling the Hydronics Institute Division of GAMA at 35 Russo
Place, P.O. Box 218, Berkeley Heights, New Jersey 07922, telephone (908)
464-8200.
(ii) Boiler feed pumps,
heating circulating pumps, condensate return pumps, and fuel oil pumps shall be
connected and installed to provide normal and standby service.
(iii) Supply and return mains and risers of
cooling, heating, and process steam systems shall be valved to isolate the
various sections of each system. Each piece of equipment shall be valved at the
supply and return ends except that vacuum condensate returns need not be valved
at each piece of equipment.
(E) Drainage systems.
(i) All underground building drains shall be:
cast iron soil pipe, hard temper copper tube (drain-waste-vent (DWV) or
heavier), acrylonitrile-butodiene-styrene (ABS) plastic pipe (DWV Schedule 40
or heavier), polyvinyl chloride (PVC) plastic pipe (DWV Schedule 40 or
heavier), or extra strength vitrified clay pipe (VCP) with compression joints
or couplings with at least 12 inches of earth cover.
(ii) Soil stacks, drains, vents, waste lines,
and leaders installed above ground within buildings shall be DWV weight or
heavier and shall be: copper pipe, copper tube, plastic pipe (DWV scheduled 40
or heavier) cast iron pipe, or galvanized iron pipe.
(iii) Drainage systems for chemical wastes
(acids and other corrosive materials) shall be provided. Materials acceptable
for chemical waste drainage systems shall include chemically resistant glass
pipe, high silicone content cast iron pipe, VCP, CPVC plastic pipe, or plastic
lined pipe.
(iv) Thermal insulation
for piping systems and equipment shall be provided for the following:
(I) boilers, smoke breeching, and
stacks;
(II) steam supply and
condensate return piping;
(III) hot
water piping and all hot water heaters, generators, converters, and storage
tanks;
(IV) chilled water,
refrigerant, other process piping, equipment operating with fluid temperatures
below ambient dew point, and water supply and drainage piping on which
condensation may occur. Insulation on cold surfaces shall include an exterior
vapor barrier; and
(V) other
piping, ducts, and equipment as necessary to maintain the efficiency of the
system.
(v) Flame spread
shall not exceed 25 and smoke development rating shall not exceed 50 for pipe
insulation as determined by an independent testing laboratory in accordance
with National Fire Protection Association 255, Standard Method of Test of
Surface Burning Characteristics of Building Materials, 2000 Edition. Smoke
development rating for pipe insulation located in environmental air areas shall
not exceed 50.
(vi) Asbestos
insulation shall not be used.
(2) Plumbing fixtures shall be made of
nonabsorptive acid-resistant materials and shall comply with the
recommendations of the National Standard Plumbing Code and this paragraph.
(A) All sinks used by medical and nursing
staff and all lavatories used by patients shall be trimmed with valves which
can be operated without the use of hands. Blade handles used for this purpose
shall not be less than four inches in length. Single lever or wrist blade
devices may be used.
(B) Clinical
sinks shall have an integral trap in which the upper portion of a visible trap
seal provides a water surface.
(C)
All plumbing fixtures and equipment shall be designed and installed to prevent
the back-flow or back-siphonage of any material into the water supply. The
over-the-rim type water inlet shall be used wherever possible. Vacuum-breaking
devices shall be properly installed when an over-the-rim type water inlet
cannot be utilized.
(D) Each
drinking fountain shall be designed so that the water issues at an angle from
the vertical, the end of the water orifice is above the rim of the bowl, and a
guard is located over the orifice to protect it from lip
contamination.
(E) All sterilizing
equipment shall be designed and installed to prevent not only the contamination
of the water supply but also the entrance of contaminating materials into the
sterilizing units. Sterilizers shall be designed and installed so that both hot
and cold water inlets shall be protected against back-siphonage at maximum
water level.
(F) No hose shall be
affixed to any faucet if the end of the hose can become submerged in
contaminated liquid unless the faucet is equipped with an approved, properly
installed vacuum breaker.
(G) The
water supply spout for lavatories and sinks required in patient care areas
shall be mounted so that its discharge point is a minimum of five inches above
the rim of the sink.
(H) Where
floor drains or floor sinks are installed, they shall be of a type that can be
easily cleaned by removal of the cover. Removable stainless steel mesh shall be
provided in addition to grilled drain cover to prevent entry of large particles
of waste which might cause stoppages.
(I) Under counter piping and above floor
drains shall be arranged (raised) so as not to interfere with cleaning of floor
below the equipment.
(J) All
ice-making machines used for human consumption shall be of the self-dispensing
type. Copper tubing shall be provided for supply connections to ice
machines.
(i)
This subsection contains common electrical requirements. The ESRD facility
shall comply with the requirements of this subsection.
(1) All new electrical material and
equipment, including conductors, controls, and signaling devices, shall be
installed in compliance with applicable sections of the National Fire
Protection Association 70, National Electrical Code, 2002 Edition (NFPA 70),
and NFPA 99 and as necessary to provide a complete electrical system.
Electrical systems and components shall be listed by nationally recognized
listing agencies as complying with available standards and shall be installed
in accordance with the listings and with the manufacturer's direction for use.
(A) All fixtures, switches, sockets, and
other pieces of apparatus shall be maintained in a safe and working
condition.
(B) All electrical
heating devices shall be equipped with a pilot light to indicate when the
device is in service, unless equipped with a temperature limiting device
integral with the heater.
(C) All
equipment, fixtures, and appliances shall be properly grounded in accordance
with NFPA 70 and NFPA 99, §4.3.2.2.2.
(D) Under counter receptacles and conduits
shall be arranged (raised) to not interfere with cleaning of floor below the
equipment.
(2)
Installation testing and certification.
(A)
The electrical installations, including alarm, nurses calling system and
communication systems, shall be tested to demonstrate that equipment
installation and operation is appropriate and functional.
(B) The grounding system shall be tested as
described in NFPA 99, 4.3.3, for patient care areas in new or renovated work.
The testing shall be performed by a qualified electrician or their qualified
electrical testing agent. The electrical contractor shall provide a letter
stating that the grounding system has been tested in accordance with NFPA 99,
the testing device use complies with NFPA 99, and whether the grounding system
passed the test. The letter shall be signed by the qualified electrical
contractor, or their designated qualified electrical testing agent, certifying
that the system has been tested and the results of the test are
indicated.
(3) Shielded
isolation transformers, voltage regulators, filters, surge suppressors, and
other safeguards shall be provided as required where power line disturbances
are likely to affect fire alarm components, data processing, equipment used for
treatment, and automated laboratory diagnostic equipment.
(4) Electrical service and switchboards
serving the required ESRD facility components shall be installed above the
designated 100-year flood plain. Main switchboards shall be located in a
permanently dry location and the electrical switchgear and distribution panels
and shall be accessible to authorized persons only. These rooms or spaces shall
be ventilated to provide an environment free of corrosive or explosive fumes
and gases, or any flammable and combustible materials. When switchboards are
installed in a damp or wet location the enclosure shall be installed in a
waterproof cabinet. Switchboards shall be located convenient for use and
readily accessible for maintenance as required by NFPA 70, Article 408.
Overload protective devices shall operate properly in ambient
temperatures.
(5) Panelboards
serving normal lighting and appliance circuits shall be located on the same
floor as the circuits they serve. Panelboards serving critical branch emergency
circuits shall be located on each floor that has major users and may also serve
the floor above and the floor below. Panelboards serving life safety branch
circuits may serve three floors, the floor where the panelboard is located, and
the floors above and below.
(6) All
conductors for controls, equipment, lighting and power operating at 100 volts
or higher shall be installed in accordance with the requirements of NFPA 70,
Article 517. All surface mounted wiring operating at less than 100 volts shall
be protected from mechanical injury with metal raceways to a height of seven
feet above the floor. Conduits and cables shall be supported in accordance with
NFPA 70, Article 300.
(7) The
wiring of the emergency system shall be mechanically protected by installation
in nonflexible metal raceways in accordance with NFPA 70,
§517.30(C)(3).
(8) Lighting
and receptacles.
(A) Lighting intensity for
staff and patient needs shall comply with guidelines for health care facilities
set forth in the Illuminating Engineering Society of North America (IESNA)
Handbook, 2000 edition, published by the IESNA, 120 Wall Street, Floor 17, New
York, New York 10005.
(i) Consideration shall
be given to controlling intensity and wavelength to prevent harm to the
patient's eyes (i.e., retina damage to cataracts due to ultraviolet
light).
(ii) Approaches to
buildings and parking lots shall be illuminated. All rooms including
storerooms, electrical and mechanical equipment rooms, and all attics shall
have sufficient artificial lighting so that all parts of these spaces shall be
clearly visible.
(iii)
Consideration shall be given to the special needs of the elderly. Excessive
contrast in lighting levels that makes effective sight adaptation difficult
shall be minimized.
(B)
Means of egress and exit sign lighting intensity shall comply with NFPA 101,
§§7.8 - 7.10.
(C)
Electric lamps, which may be subject to breakage or which are installed in
fixtures in confined locations when near woodwork, paper, clothing, or other
combustible materials, shall be protected by wire guards, or plastic
shields.
(D) Only listed hospital
grade single-grounding or duplex-grounding receptacles shall be used in all
patient care areas. This does not apply to special purpose receptacles.
(i) Installations of multiple-ganged
receptacles shall not be permitted in patient care areas.
(ii) Electrical outlets powered from the
emergency system shall be provided in all patient care, procedure, and
treatment locations in accordance with NFPA 99, §4.4.2.2.2.3. At least one
receptacle at each patient treatment station/room, exam room, or procedure
location shall be powered from the emergency electrical system power panel. At
least one receptacle at each patient treatment station/room, exam room, or
procedure location shall be powered from the normal power panel.
(iii) Replacement of malfunctioning
receptacles and installation of new receptacles powered from the emergency
system in existing facilities shall be accomplished with receptacles of the
same distinct color as the existing receptacles.
(iv) In locations where other equipment
requiring special electrical configuration is used, the additional receptacles
shall be distinctively marked for the special use.
(v) Each receptacle shall be grounded to the
reference grounding point by means of a green insulated copper equipment
grounding conductor.
(vi) All
emergency system receptacles shall be identified. The face plate for the
receptacle(s) shall have a nonremovable label or be engraved indicating the
panel and circuit number.
(E) Equipment.
(i) Equipment required for safe operation of
the ESRD facility shall be powered from the critical system in accordance with
the requirements contained in NFPA 99, §4.5.2.2.3.
(ii) Boiler accessories including feed pumps,
heat-circulating pumps, condensate return pumps, fuel oil pumps, and waste heat
boilers shall be connected and installed to provide both normal and standby
service.
(F) Ground
fault circuit interrupters (GFCI) receptacles shall be provided for all general
use receptacles located within three feet of a wash basin or sink. When GFCI
receptacles are used, they shall be connected to not affect other devices
connected to the circuit in the event of a trip. Receptacles connected to the
critical branch that may be used for equipment that should not be interrupted
do not have to be GFCI protected. Receptacles in wet locations, as defined by
NFPA 70, §517.20 and §517.21, shall be GFCI protected regardless of
the branch of the electrical system serving the receptacle.
(9) A nurses emergency calling
system shall be installed in the patient waiting area, all individual treatment
rooms, exam rooms, isolation rooms, hepatitis B rooms, and toilet rooms used by
patients to summon nursing staff in an emergency. Activation of the system
shall sound a repeating (every 5 seconds or less) distinct audible signal at
the nurse station, indicate type and location of call on the system monitor,
and activate a distinct visible signal in all areas. The visible and audible
signals shall be cancelable only at the patient calling station. A nurses
emergency call system shall be accessible to a collapsed patient lying on the
floor. Inclusion of a pull cord extending to within 6 inches of the floor will
satisfy this requirement.
(10) The
ESRD facility shall provide, at submission of construction documents/plans a
letter on facility letterhead indicating the method the ESRD facility has
chosen for implementation of the emergency contingency plan for the continuity
of emergency essential building systems (emergency generator). The contingency
plan shall consist of one of the three options as described as follows.
(A) An onsite emergency generator shall be
provided with a Type II essential electrical distribution system in accordance
with requirements of NFPA 99, §4.5, and National Fire Protection
Association 110, Standard for Emergency and Standby Power Systems, 2002
Edition.
(i) An emergency generator standby
power system(s) shall require an onsite fuel source and enough fuel capacity in
the tank for a period of twenty-four hours or more. When a vapor liquefied
petroleum gas (LPG) (natural gas) system is used, the twenty-four hour fuel
capacity on site is not required. The vapor withdrawal LPG system shall require
a dedicated fuel supply.
(ii) The
emergency generator shall be installed, tested and maintained in accordance
with the National Fire Protection Association 99, §4.5.4, and National
Fire Protection Association 110, Standard for Emergency and Standby Power
Systems, 2002 Edition.
(iii) When
the emergency generator(s) and electrical transformer(s) are located within the
same area, they shall be located at least 10 feet apart.
(iv) Sufficient quantity of potable water
supply shall be on site for the operation of the water treatment system for at
least twenty-four hours. A water valve connection shall be provided to allow
hook-up for potable water from an outside vendor to supply the water treatment
system.
(B) A executed
contract with an outside supplier/vendor(s) that will provide a portable
emergency generator(s) and potable water on demand.
(i) An electrical transfer switch with
plug-in device sized to provide emergency power for the patient care areas and
the provisions in NFPA 99, §4.5.2.2.2.
(ii) A water valve connection to allow
hook-up for potable water from an outside vendor to supply the water treatment
system.
(iii) An alternate source
of power (battery power lighting) shall be provided separate and independent
from the normal electrical power source that will be effective for a minimum of
1-1/2 hours after loss of the electrical power. The emergency lighting system
shall be capable of providing sufficient illumination to allow safe evacuation
from the building. The battery pack systems shall be maintained and tested
quarterly.
(iv) The facility shall
implement the emergency contingency plan upon the loss of electrical power
following a natural weather or man-made event when the electrical power may not
be restored within 24 hours. The facility shall exercise the contract(s) with
the supplier/vendor(s) in order to have portable emergency generator(s) and
potable water available within 36 hours after the loss of electrical
power.
(C) An executed
contract with another licensed ESRD facility within a 100 mile radius to
provide emergency contingency care for the patients.
(i) The accepting licensed ESRD facility
shall meet the requirements of paragraph (1) of this subsection.
(ii) An alternate source of power shall be
provided separate and independent from the normal electrical power source that
will be effective for a minimum of 1-1/2 hours after loss of the electrical
power. The emergency lighting system shall be capable of providing sufficient
illumination to allow safe evacuation from the building. The battery pack
systems shall be maintained and tested quarterly.
(11) A fire alarm system, which
complies with NFPA 101, §18.3.4, and with NFPA 72, Chapter 6 requirements,
shall be provided in each facility. The required fire alarm system components
are as follows:
(A) A fire alarm control
panel (FACP) shall be installed at a visible central location.
(B) Manual fire alarm pull stations shall be
installed in accordance with NFPA 101, §18.3.4.
(C) Smoke detectors for door release service
shall be installed on the ceiling at each door opening in the smoke partition
in accordance with NFPA 72, §6.15.6, where the doors are held open with
electromagnetic devices conforming with NFPA 101, §18.2.2.6.
(D) Smoke detectors shall be installed in air
ducts in accordance with NFPA 72, §5.14.4.2 and §5.14.5 and NFPA 90A,
§6.4.2.
(E) Smoke detectors
shall be installed in return air ducts in accordance with requirements of NFPA
72 §5.14.4.2.2 and §5.14.5 and NFPA 90A, §6.4.2.2.
(F) Fire sprinkler system water flow switches
shall be installed in accordance with requirements of NFPA 101, §9.6.2;
NFPA 13, §6.9; and NFPA 72, §8.5.3.3.3.4.
(G) Sprinkler system valve supervisory
switches shall be installed in accordance with the requirements of NFPA 72,
§6.8.5.5.
(H) Audible alarm
indicating devices shall be installed in accordance with the requirements of
NFPA 101, §18.3.4, and NFPA 72, §7.4.
(I) Visual fire alarm indicating devices,
which comply with the requirements of NFPA 72, §7.5, shall be
provided.
(J) Devices for
transmitting alarm for alerting the local fire brigade or municipal fire
department of fire or other emergency shall be provided. The devices shall be
listed for the fire alarm service by a nationally recognized laboratory, and be
installed in accordance with such listing and the requirements of NFPA
72.
(K) A fire alarm signal
notification, which complies with NFPA 101, §9.6.3, shall be provided to
alert occupants of fire or other emergency.
(L) Wiring for fire alarm detection circuits
and fire alarm notification circuits shall comply with requirements of NFPA 70,
Article 760.
(M) Smoke detector(s)
for shutdown of air handling units shall be provided. The detectors shall be
installed in accordance with NFPA 90A, §6.4.3.
(N) Telecommunications and information
systems central equipment shall be installed in a separate location designed
for the intended purpose. Special air conditioning and voltage regulation shall
be provided as recommended by the manufacturer.
(O) When installed, lightning protection
systems shall comply with National Fire Protection Association 780, Standard
for the Installation of Lightning Protection Systems, 2000 Edition.