Current through September 24, 2024
(1) Standard
Boilers. The maximum allowable working pressure of standard boilers shall in no
case exceed the pressure indicated by the manufacturer's identification stamped
or cast on the boiler or on a plate secured on it.
(2) Nonstandard Riveted Boilers. The maximum
allowable working pressure on the shell of a nonstandard riveted heating boiler
shall be determined in accordance with Rule 0800-03-03-.10(3) except that in no
case shall the maximum allowable working pressure of a steam heating boiler
exceed 15 psig, or a hot water boiler exceed 160 psig or 250°F.
(3) Nonstandard Welded Boiler. The maximum
allowable working pressure of a nonstandard steel or wrought iron heating
boiler of welded construction shall not exceed 15 psig for steam. For other
than steam service, the maximum allowable working pressure shall be calculated
in accordance with ASME Code, Section IV but in no case shall it exceed 30
psig.
(4) Nonstandard Cast Iron
Boilers.
(a) A maximum allowable working
pressure of a nonstandard boiler composed principally of cast iron shall not
exceed 15 psig for steam service or 30 psig for hot water service.
(b) The maximum allowable working pressure of
a nonstandard boiler having cast iron shell or heads and steel or wrought iron
tubes shall not exceed 15 psig for steam service or 30 psig for hot water
service.
(5) Safety
Valves.
(a) Each steam boiler shall have one
(1) or more ASME/NB stamped safety valves of the spring pop-type adjusted and
sealed to discharge at a pressure not to exceed 15 psig. Seals shall be
attached in a manner to prevent the valves from being taken apart without
breaking the seal. The safety valves shall be arranged so that they cannot be
reset to relieve at a higher pressure than the maximum allowable working
pressure of the boiler. A body drain connection below seat level shall be
provided by the manufacturer and this drain shall not be plugged during or
after field installation. For valves exceeding two and one half (21/2) inches
pipe size, the drain holes or holes shall be tapped not less than three eighths
(3/8) inch pipe size. For valves less than two and one half (21/2) inches, the
drain hole shall not be less than one fourth (1/4) inch in diameter.
(b) No safety valve for a steam heating
boiler shall be smaller than one half (1/2) inch unless the boiler and
radiating surface consist of a self-contained unit. No safety valve shall be
larger than four and one half (41/2) inches. The inlet opening shall have an
inside diameter equal to, or greater than, the seat diameter.
(c) The minimum relieving capacity of the
valve or valves shall be governed by the capacity marking on the
boiler.
(d) The minimum valve
capacity in pounds per hour shall be the greater of that determined by dividing
the maximum BTU output at the boiler nozzle obtained by the firing of any fuel
for which the unit is installed by one thousand (1000) or shall be determined
on the basis of the pounds of steam generated per hour per square foot of
boiler heating surface as given in Table 2. In many cases, a greater relieving
capacity of valves will have to be provided than the minimum specified by these
rules. In every case, the requirements of subparagraph (e) of this rule shall
be met.
Table 2
Minimum Pounds of Steam Per Hour
Per Square Foot of Heating Surface
|
Firetube Boilers
|
Watertube
Boilers
|
Boiler Heating
Surface
|
|
|
Hand fired
|
5
|
6
|
Stoker fired
|
7
|
8
|
Oil, gas or pulverized fuel fired
|
8
|
10
|
Waterwall Heating Surface
|
|
|
Hand fired
|
8
|
8
|
Stoker fired
|
10
|
12
|
Oil,
gas or pulverized fuel fired
|
14
|
16
|
1. When a boiler is fired only by a gas
giving a heat value not in excess of 200 BTU per cubic foot, the minimum safety
valve or safety relief valve relieving capacity may be based on the value given
for hand-fired boilers above.
2.
The minimum safety valve or safety relief valve relieving capacity for electric
boilers shall be three and one half (31/2) pounds per hour per kilowatt
input.
3. For heating surface
determination, see ASME Code, Section IV, Paragraph HG-403.
(e) The safety valve capacity for
each steam boiler shall be such that, with the fuel-burning equipment installed
and operating at maximum capacity, the pressure cannot rise more than 5 psig
above the maximum allowable working pressure.
(f) When operating conditions are changed, or
when additional boiler heating surface is installed, the valve capacity shall
be increased (if necessary) to meet the new conditions and comply with this
paragraph. When additional valves are required, they may be installed on the
outlet piping, provided there is no intervening valve.
(g) If there is any doubt as to the capacity
of the safety valve, an accumulation test shall be run. See ASME Code, Section
VI, Recommended Rules for Care and Operation of Heating Boilers.
(h) No valve of any description shall be
placed between the safety valve and the boiler , and on the discharge pipe
between the safety valve and the atmosphere. The discharge pipe shall be at
least full-size, and shall be fitted with an open drain to prevent water
lodging in the upper part of the safety valve and in the discharge pipe. When
an elbow is placed on the safety valve discharge pipe, it shall be located
close to the safety valve outlet; and the discharge pipe shall be securely
anchored and supported. All safety valve discharges shall be so located and
piped as not to endanger persons in the area.
(6) Safety Relief Valve Requirements for Hot
Water Boilers.
(a) Each hot water heating
boiler shall have at least one (1) ASME/NB stamped safety relief valve set to
relieve at or below the maximum allowable working pressure of the boiler. Each
hot water supply boiler shall have at least one (1) ASME/NB stamped safety
relief valve of the automatic reseating type set to relieve at or below maximum
allowable working pressure of the boiler safety relief valves, ASME/NB stamped
as to capacity, shall have pop action when tested by steam. When more than one
(1) safety relief valve is used on either hot water heating or hot water supply
boilers, the additional valve or valves shall be ASME/NB rated, and may be set
within a range not to exceed 6 psig above the maximum allowable working
pressure of the boiler up to and including 60 psig, and five percent (5%) for
those having a maximum allowable working pressure exceeding 60 psig. Safety
relief valves shall be spring loaded. Safety relief valves shall be so arranged
that they cannot be reset at a higher pressure than the maximum permitted by
this subparagraph.
(b) No materials
liable to fail due to deterioration or vulcanization when subject to saturated
steam temperature corresponding to capacity test pressure shall be used for any
part.
(c) No safety relief valve
shall be smaller than three fourths (3/4) inch nor larger than four and one
half (41/2) inches standard pipe size, except that boilers having a heat input
not greater than 15,000 BTU per hour may be equipped with a safety relief valve
of one half (1/2) inch standard pipe. The inlet opening shall have an inside
diameter approximately equal to, or greater than, the seat diameter. In no case
shall the minimum opening through any part of the valve be less than one fourth
(1/4) inch in diameter or its equivalent area.
(d) The required steam relieving capacity, in
pounds per hour, of the pressure relieving device or devices on a boiler shall
be the greater of that determined by dividing the maximum output in BTU at the
boiler nozzle obtained by the firing of any fuel for which the unit is
installed by one thousand (1,000) or shall be determined on the basis of pounds
of steam generated per hour per square foot of boiler heating surface as given
in Table 2. In many cases, a greater relieving capacity of valves will have to
be provided than the minimum specified by these rules. In every case, the
requirements of subparagraph (f) of this rule shall be met.
(e) When operating conditions are changed, or
when additional boiler heating surface is installed, the valve capacity shall
be increased, if necessary, to meet the new conditions and shall be in
accordance with Table 2 and subparagraph (f) of this rule. The additional
valves required, on account of changed conditions, may be installed on the
outlet piping provided there is no intervening valve.
(f) The safety relief valve capacity for each
boiler shall be such that, with the fuel burning equipment installed and
operating at maximum capacity, the pressure cannot rise more than 5 psig above
the maximum allowable working pressure for steam heating boilers, and ten
percent (10%) above maximum allowable working pressures for hot water
boilers.
(g) If there is any doubt
as to the capacity of the safety relief valve, an accumulation test shall be
run. See ASME Code, Section VI. Recommended Rules for Care and Operation of
Heating Boilers.
(h) No valve of
any description shall be placed between the safety relief valve and the boiler,
and on the discharge pipe between the safety relief valve and the atmosphere.
The discharge pipe shall be at least full-size, and shall be fitted with an
open drain to prevent water lodging in the upper part of the safety relief
valve or in the discharge pipe. When an elbow is placed on the safety relief
valve discharge pipe, it shall be located close to the safety relief valve
outlet; and the discharge pipe shall be properly supported. All safety relief
valve discharges shall be so located and piped as not to endanger persons in
the area.
(7) Steam
Gauges.
(a) Each steam boiler shall have a
steam gauge connected to its steam space, its water column, or its steam
connection, by means of a siphon or equivalent device exterior to the boiler.
The siphon (or equivalent device) shall be a sufficient capacity to keep the
gauge tube filled with water and shall be so arranged that the gauge cannot be
shut off from the boiler except by a cock with tee or lever handle placed in
the pipe near the gauge. The handle of the cock shall be parallel to the pipe
in which it is located when the cock is open.
(b) The scale on the dial of a steam gauge
shall be graduated to not less than 30 psig - nor more than 60 psig. The gauge
shall be provided with effective stops for the indicating pointer at the zero
(0) point and at the maximum pressure point. The travel of the pointer from
zero (0) to 30 psig pressure shall be at least three (3) inches.
(8) Pressure or Altitude Gauge and
Thermometers.
(a) Each hot water heating or
hot water supply boiler shall have a pressure or altitude gauge connected to it
or to its flow connection in such a manner that it cannot be shut off from the
boiler except by a cock with tee or lever handle, placed on the pipe near the
gauge. The handle of the cock shall be parallel to the pipe in which it is
located when the cock is open.
(b)
The scale on the dial of the pressure or altitude gauge shall be graduated
approximately to not less than one and one half (11/2) nor more than three and
one half (31/2) times the pressure at which the safety relief valve is set. See
NBIC Part 1, Section 3.8.2.1.
(c)
Piping or tubing for pressure or altitude gauge connections shall be of
nonferrous metal when smaller than one (1) inch pipe size.
(d) Each hot water boiler shall have a
thermometer so located and connected that it will be easily readable when
observing the water pressure or altitude gauge. The thermometer shall be so
located that it will at all times indicate the temperature in degrees
Fahrenheit of the water in the boiler at or near the outlet.
(9) Water Gauge Glasses.
(a) Each steam boiler shall have one (1) or
more water gauge glasses attached to the water column or boiler by means of
valved fittings. The lower fitting shall be provided with a drain valve of the
straightaway type, with opening not less than one fourth (1/4) inch diameter to
facilitate cleaning. Gauge glass replacement shall be possible while the boiler
is under pressure.
(b) Transparent
material, other than glass, may be used for the water gauge, provided that the
material has proven suitable for the pressure temperature and corrosive
conditions encountered in service.
(10) Stop Valves and Check Valves.
(a) If a boiler may be closed off from the
heating system by closing a steam stop valve, there shall be a check valve in
the condensate return line between the boiler and the system.
(b) If any part of a heating system may be
closed off from the remainder of the system by closing a steam stop valve,
there shall be a check valve in the condensate return pipe from the part of the
system.
(11) Feedwater
Connections.
(a) Feedwater, make-up water, or
water treatment shall be introduced into a boiler through the return piping
system or through an independent feedwater connection which does not discharge
against parts of the boiler exposed to direct radiant heat from the fire.
Feedwater, make-up water, or water treatment shall not be introduced through
openings or connections provided for inspection or cleaning, safety valve,
safety relief valve, surface blowoff, water column water gauge glass, pressure
gauge or temperature gauge.
(b) The
feedwater pipe shall be provided with a check valve near the boiler and a stop
valve or cock between the check valve and the boiler or return pipe
system.
(12) Return
Pump. Each boiler equipped with a condensate return pump shall be provided with
a water level control arranged to automatically maintain the water level in the
boiler within the range of the gauge glass.
(13) Repairs and Renewals of Fittings and
Appliances. Whenever fittings or appliances are repaired or replaced, the work
shall comply with the rules governing new installations.
Authority:
T.C.A. §
68-122-102.