(1)
Regarding alternative methods of subsurface sewage disposal, if a conflict
occurs between this rule and other rules of these regulations, the items of
this rule shall apply. However, the Commissioner may allow repairs if the site
does not meet soil suitability and reserve area requirements. The wastewater
flow for residences or other similar establishments served by alternative
methods of subsurface sewage disposal shall be based upon one hundred fifty
(150) gallons per bedroom per day.
(2) Large Alternative Subsurface Methods of
Sewage Disposal - Any alternative subsurface sewage disposal system that has a
wastewater flow greater than seven hundred fifty (750) gallons per day shall be
considered a large alternative subsurface sewage disposal system.
(a) A site specific design for each large
alternative subsurface sewage disposal system shall be submitted to the
department for review.
(b) The
design shall be stamped with the seal of a licensed engineer.
(c) Prior to design approval, a licensed
engineer must agree, in writing, to monitor the installation and construction
of the system and upon completion, provide a final set of as built plans
encompassing all components of the system and certification that the
installation is in accordance with the design specifications.
(d) It shall be the responsibility of the
department to review the aforementioned design and notify the engineer, in
writing, of approval of the plans, denial of the plans or needed modifications
to the plans.
(3) A Low
Pressure Pipe (LPP) system is a subsurface sewage disposal system, which has
three (3) basic design principles different from conventional subsurface sewage
disposal systems. They are:
(1) uniform distribution of effluent,
(2) dosing and resting cycles, and
(3) shallow placement of
trenches. When lots that are less than twenty thousand (20,000) square feet are
proposed, the department shall determine the necessity, location and design of
buffer zones. LPP systems shall not be used to dispose of wastewater wherein
the average concentration of grease exceeds one hundred fifty (150) milligrams
per liter (mg/L) because of the clogging potential of the distribution network.
LPP systems designed to accommodate wastewater flows in excess of
seven hundred fifty (750) gallons per day must be designed by a licensed
engineer. The design shall be reviewed by the department applying the
requirements of paragraph (2) of this rule.
(a) Site and Soil Requirements
1. Prior to the design of the LPP system, the
suitability of the site must be demonstrated through acceptable soil absorption
rates, acceptable soil conditions and other topographic characteristics. The
acceptable soil absorption rate range shall be from ten (10) minutes per inch
through seventy-five (75) minutes per inch as determined by an extra-high
intensity soil map prepared by an approved soil consultant. If the soil
absorption rate is determined to be greater than seventy-five (75) minutes per
inch based upon the extra-high intensity soil map, then percolation tests may
be conducted. However, soils with absorption rates in excess of seventy-five
(75) minutes per inch due to wetness that cannot be corrected by drainage shall
not be eligible for percolation tests. Percolation rates from seventy-six (76)
minutes per inch through one hundred twenty (120) minutes per inch are
acceptable if no water problems exist.
2. A minimum soil depth of thirty (30) inches
over any underlying restrictive horizon is required. However, a modified LPP
system may utilize a maximum of six (6) inches of compatible fill, as
determined by an approved soil consultant, to obtain the required thirty (30)
inches of depth.
3. Slopes of more
than thirty (30) percent shall be considered unsuitable.
4. An area of suitable soil must be available
to install the initial system and maintain a suitable area of adequate size for
one hundred (100) percent duplication.
5. The size of the LPP system shall be
determined by the following:
(i) An extra-high
intensity soil map, provided by a soil consultant approved by the department,
shall establish the soil absorption rate.
(ii) If the extra-high intensity soil map
determines that a percolation test is necessary to establish a rate, the
percolation holes shall be located in a grid pattern with maximum perpendicular
distances between holes of twenty-five (25) feet and the gridded portion shall
encompass the entire area to be utilized for the system and duplicate area.
Greater distances may be allowed as determined by the Commissioner. The
percolation test procedure in Rule 0400-48-01-.05 shall apply.
(iii) The daily wastewater flow divided by
the loading rate (Table II) shall determine the area (ft2) required for the
initial system.
(iv) Hydraulic
overloading of the disposal field may occur when excessive amounts of effluent
are distributed over a continuous common slope. Therefore, buffer zones are
required if there is more than six (6) feet of elevation difference between the
upper and lower laterals or if the distance between the upper and lower
laterals exceeds fifty (50) feet. The buffer zone size and the use of soil
improvement or soil protection practices are site specific and shall be
determined by the Commissioner based on the recommendation of an approved soil
consultant. The buffer zone shall not be included as part of the reserve area.
Table II. Maximum Loading Rate
Established Rate (mpi)
|
Loading Rate (gpd/ft 2
)
|
10
|
0.400
|
20
|
0.400
|
30
|
0.350
|
40
|
0.300
|
45
|
0.275
|
50
|
0.250
|
60
|
0.200
|
75
|
0.150
|
90
|
0.100
|
120
|
0.050
|
(b) Layout of the LPP System
1. The required linear footage is determined
by dividing the amount of required square footage of suitable soil area by five
(5).
2. The location of the septic
tank, dosing chamber and the disposal field shall be in accordance with Rule
0400-48-01-.11.
3. The lateral
lines shall be placed on contour and lengths shall not exceed those specified
as follows:
5/32 in. Orifice
|
Maximum Lateral Length
(ft)
|
|
Pipe Size (in)
|
Hole Spacing (ft)
|
1
|
1.25
|
1.5
|
2
|
3
|
50
|
75
|
100
|
140
|
4
|
55
|
80
|
110
|
150
|
5
|
60
|
90
|
120
|
N/A
|
6
|
65
|
100
|
125
|
N/A
|
7
|
70
|
110
|
135
|
N/A
|
8
|
75
|
120
|
145
|
N/A
|
3/16 in.
Orifice
|
Maximum Lateral Length (ft)
|
|
Pipe Size
(in)
|
Hole Spacing
(ft)
|
1
|
1.25
|
1.5
|
2
|
3
|
30
|
55
|
75
|
115
|
4
|
35
|
60
|
85
|
130
|
5
|
40
|
65
|
100
|
145
|
6
|
45
|
75
|
110
|
150
|
7
|
50
|
80
|
115
|
N/A
|
8
|
55
|
85
|
125
|
N/A
|
7/32 in.
Orifice
|
Maximum Lateral Length (ft)
|
|
Pipe Size
(in)
|
Hole Spacing
(ft)
|
1
|
1.25
|
1.5
|
2
|
3
|
30
|
50
|
65
|
90
|
4
|
35
|
55
|
70
|
105
|
5
|
40
|
60
|
80
|
115
|
6
|
45
|
65
|
85
|
130
|
7
|
50
|
70
|
95
|
140
|
8
|
55
|
80
|
105
|
150
|
1/4 in. Orifice
|
Maximum Lateral Length
(ft)
|
|
Pipe Size (in)
|
Hole Spacing (ft)
|
1
|
1.25
|
1.5
|
2
|
3
|
30
|
40
|
60
|
80
|
4
|
35
|
45
|
65
|
90
|
5
|
35
|
55
|
70
|
100
|
6
|
40
|
60
|
75
|
110
|
7
|
40
|
65
|
80
|
120
|
8
|
45
|
70
|
85
|
130
|
4. The trench
bottom of each lateral shall be at the same elevation throughout that
lateral.
5. The distance between
laterals (center to center) shall not be less than five (5) feet.
6. Trench width shall be a minimum of twelve
(12) inches.
7. Trench depth shall
range between eighteen (18) and twenty-two (22) inches.
8. A minimum of twelve (12) inches of soil
material shall be present between the bottom of the trenches and the
restrictive layer.
9. Individual
lateral lines shall be a maximum of one hundred (100) feet in length, unless
supported by an engineered design.
(c) Dosing and Distribution System Design
1. The dosing rate per linear foot of
disposal trench shall be uniform over the entire system. This may be
accomplished by varying the hole spacing, hole sizing or placement of valves in
the manifold or laterals to compensate for changes in ground elevation. Table
III shall be used to calculate dosing rates.
Table III.
Pressure Head vs. gpm Flow Per Hole
Pressure
Head |
Hole Diameter (in)
|
ft |
psi
|
5/32
|
3/16
|
7/32
|
1
|
0.43
|
0.29
|
0.42
|
0.56
|
2
|
0.87
|
0.41
|
0.59
|
0.80
|
3
|
1.30
|
0.50
|
0.72
|
0.98
|
4
|
1.73
|
0.58
|
0.83
|
1.13
|
5
|
2.16
|
0.64
|
0.94
|
1.26
|
2. The first and last holes in a lateral
shall be thirty (30) inches from the ends of the lateral. Hole spacing shall
not exceed seven and one-half (71/2) feet.
3. Hole sizes shall be within the range of
five thirty-seconds (5/32) inches through seven thirty-seconds (7/32)
inches.
4. Calculation of gallons
per minute (gpm) flow and total dynamic head.
(i) The gallons per minute flow amount that
the pump must provide shall be determined by adding the gallons per minute
flows per hole over the system dosed by that pump.
(ii) The total dynamic head (TDH) shall be
determined by adding the following:
(I)
Elevation head is the difference in elevation between the bottom of the pump
and the highest ground elevation at the disposal field. The minimum assigned
elevation head shall be five (5) feet.
(II) Friction head shall be determined from
Appendix III plus fittings loss.
(III) A pressure head average of three (3)
feet shall be used for TDH calculations. The range shall be one (1) through
five (5) feet.
5. When pumping uphill, a check valve must be
utilized if the volume of the supply line, manifold and the volume of the
laterals that drain back into the pump tank exceeds one-fourth (1/4) daily
flow.
6. The minimum dosing volume
shall be determined by adding the volume of the supply line, manifold and five
(5) times the volume of the laterals. If a check valve is utilized, the minimum
dosing volume shall be determined by adding the volume of the manifold and five
(5) times the volume of the laterals.
7. The dosing volume shall be between
one-fourth (1/4) and one-half (1/2) daily flow, except in those situations
where the minimum dose exceeds one-half (1/2) daily flow, then the calculated
minimum dose shall be the dosing volume.
(d) Equipment and Material Specifications
1. Septic Tank and Dosing Chamber
(i) The septic tanks shall conform to all
design, construction and installation criteria set forth in Rules
0400-48-01-.08 and 0400-48-01-.09.
(ii) The dosing chamber shall conform to all
design construction and installation criteria set forth in Rule
0400-48-01-.12.
2. Pipe
and Fittings
(i) All pipe materials shall be
PVC and have a minimum equivalent strength of Schedule 40.
(ii) All fittings shall be pressure
fittings.
(iii) All connections
shall be adequately cleaned with cleaning solvent and glued with PVC solvent
cement.
(iv) The gate or globe
valve(s) and check valve shall be either bronze or PVC.
(v) The lateral pipe diameter shall be a
minimum of one (1) inch.
(vi) The
distal end of each lateral shall be equipped with a capped turn-up that
provides above-ground access.
3. Pump, Float Controls and Alarm System
(i) The pump shall be an effluent pump of
sufficient quality and size to meet or exceed the flow requirement and the
total dynamic head requirement of the system.
(ii) The pump float controls must be
adjustable and must be sealed against entry of effluent or gases.
(iii) Alarm System
(I) A high water alarm shall be required and
consist of an audible and visible alarm located in a visible place and clearly
marked "wastewater system alarm".
(II) The alarm and alarm switches shall be
placed on a separate electrical circuit from the pump power line.
(III) The alarm float control shall be placed
so as to be activated when the pump chamber water level rises above the "pump
on" float control.
4. Disposal Field Media
The disposal
field media size shall be within the range of one-half (1/2) to one (1) inch.
It must be washed and free of fines.
(e) Installation Procedures
1. Site Preparation and Imported Fill
(i) The soil area reserved for the initial
and duplicate systems must not be cut, filled, compacted or disturbed in any
manner prior to or after system installation.
(ii) No site preparation shall occur if the
soil is wet. The designated person responsible for monitoring system
installation shall determine when the soil is adequately dry.
(iii) If imported fill is used during
installation it must be of compatible material, which shall be determined by
the soil consultant approved by the department. The area to be filled must be
disked prior to adding fill. The fill material must be applied with a minimum
amount of wheeled traffic and must be incorporated to ensure even
mixing.
2. Supply Line
and Manifold
(i) The manifold and laterals
shall be designed and installed to drain after each use.
(ii) The supply line shall be designed and
installed to drain after each use unless system design requires a check
valve.
(iii) A tee to tee
connection between the manifold and laterals shall be used except in situations
where the topographic, soil and other site conditions allow the manifold and
laterals to be at right angles. If the manifold and laterals are at right
angles then crosses or tee to tee connections may be utilized.
3. Distribution Laterals
(i) The distribution laterals shall be
constructed with a minimum disposal field media depth of nine (9) inches, with
three (3) inches above the lateral pipe invert.
(ii) The disposal field media must be covered
with untreated building paper, straw or other acceptable material that will
allow movement of water and restrict soil movement.
4. Pump and Controls
(i) The pump must be placed so that the
intake is a minimum of eight (8) inches above the bottom of the pump
chamber.
(ii) As a means to remove
the pump from the pump chamber, a material of sufficient strength and
durability must be secured to the pump and access riser.
(iii) The pump control must be positioned so
the "pump off" switch is slightly above the top of the pump and the "pump on"
switch is at the desired dosing depth.
(iv) The pump outlet pipe must be connected
to the supply manifold with a threaded union or similar device.
(v) A PVC or bronze, gate or globe valve
shall be placed in the supply line to adjust the specific pressure
head.
(vi) If the effluent is
pumped downhill, a five thirty-seconds (5/32) inch siphon breaker hole must be
drilled in the bottom of the supply line above the water level inside the pump
tank.
(vii) All electrical
installations shall be installed to meet the current wiring methods of the
current edition of the "National Electric Code" (NEC) adopted by the State Fire
Marshall's office.
5.
The completed landscape must be shaped to prevent water from ponding or flowing
over the system.
(4) A Mound System is a soil absorption
system that is located above the natural soil surface and constructed with
suitable fill material. The system differs from the conventional subsurface
sewage disposal system in three (3) ways:
(1)
uniform distribution of effluent,
(2) dosing and resting cycles and (3) above
ground construction. When lots that are less than twenty thousand (20,000)
square feet are proposed, the department shall determine the necessity,
location and design of buffer zones. Mound systems shall not be used to dispose
of wastewater wherein the average concentration of grease exceeds one hundred
fifty (150) milligrams per liter (mg/L) because of the clogging potential of
the distribution network.
Mound systems designed to accommodate
wastewater flows in excess of seven hundred fifty (750) gallons per day must be
designed by a licensed engineer in accordance with T.C.A. §
62-2-101 et seq. The design shall
be reviewed by the department applying the requirements of paragraph (2) of
this rule.
(a) Site and Soil
Requirements
1. Prior to the design of the
mound system, the suitability of the site must be demonstrated through
acceptable soil absorption rates, acceptable soil conditions and other
topographic characteristics.
2. The
size of the mound system shall be determined by the following:
(i) An extra-high intensity soil map,
provided by a soil consultant approved by the department, shall establish the
soil absorption rate.
(ii) If the
extra-high intensity soil map, determines that a percolation test is necessary
to establish a rate, the percolation holes shall be located in a grid pattern
with the maximum perpendicular distances between the holes being twenty-five
(25) feet and the gridded portion shall encompass the entire area to be
utilized for the system and duplicate area. Greater distances may be allowed as
determined by the Commissioner. The percolation test procedure in Rule
0400-48-01-.05 shall apply.
(iii)
The daily wastewater flow divided by the infiltrative capacity of medium sand
(1.2 gal/ft2/day) shall determine the area (ft2) required for the distribution
bed.
3. The requirements
relating to rock, groundwater and other site conditions established in
paragraphs (2), (3) and (4) of Rule0400-48-01-.04 shall apply. A minimum soil
depth of twenty-four (24) inches over any underlying restrictive horizon is
required. However, a modified mound system may utilize up to four (4) inches of
additional sand backfill reducing the minimum depth of soil to any underlying
restrictive horizon to twenty (20) inches.
4. The acceptable soil absorption rate range
for the mound system shall be from ten (10) minutes per inch through
seventy-five (75) minutes per inch as determined by an extra-high intensity
soil map conducted by an approved soil consultant. If the soil absorption rate
is determined to be greater than seventy-five (75) minutes per inch based upon
a soils map prepared by an approved soil consultant, percolation tests may be
conducted. However, soils with absorption rates in excess of seventy-five (75)
minutes per inch due to wetness that cannot be corrected by drainage shall not
be eligible for percolation tests. Percolation rates from seventy-six (76)
minutes per inch through one hundred twenty (120) minutes per inch are
acceptable if no water problems exist.
5. An area of suitable soil must be available
to install the initial system and maintain a suitable area of adequate size for
one hundred (100) percent duplication.
6. If tree stumps or boulders are present
within the areas designated for the initial and duplicate systems, adequate
area must be available to compensate for the area occupied by the boulders and
tree stumps.
7. The basal area
available for a mound must be equal to or greater than the basal area required
for a given soil absorption rate.
(i) On
sloping sites, the basal area available is that area directly below and
downslope of the distribution bed. On level sites, the basal area available is
that area below and on both sides of the distribution bed. That area below the
end slopes shall not be included as available basal area.
(ii) The basal area required is determined by
dividing the daily flow by infiltrative capacity of the soil. The infiltrative
capacity for a given soil absorption rate can be found below:
Absorption Rate
(mpi)
|
Infiltrative Capacity
(gal/ft2/day)
|
10-29
|
1.20
|
30-60
|
0.74
|
61 - 120
|
0.24
|
8. Slopes steeper than
twelve (12) percent shall not be utilized. Sites with soil absorption rates of
sixty-one (61) through one hundred twenty (120) minutes per inch shall not
exceed a slope of six (6) percent.
9. When cluster mounds are used, buffer zones
are required at a frequency and size as determined by an extra-high intensity
soil map and site evaluation.
(b) Layout of the Mound System
1. The mound shall be located so as to insure
that the distribution bed is situated parallel to slope contour.
2. The location of the septic tank, dosing
tank and disposal mound shall be in accordance with Rule
0400-48-01-.11.
3. The distribution
bed shall be constructed level and its thickness shall be constant. A layer of
uncompacted straw six (6) inches thick, untreated building paper or acceptable
synthetic fabric shall be placed between the distribution bed and the clay
cap.
4. Configuration
(i) The end slope gradient of the mound shall
not be steeper than three (3) horizontal to one (1) vertical. The distance from
the gravel bed to the toe of the end slope is calculated by multiplying the
average mound height by the horizontal slope figure.
(ii) The upslope and downslope gradient of
the mound shall not be steeper than three (3) horizontal to one (1) vertical.
The distance from the gravel bed to the toe of either the upslope or the
downslope side is calculated by multiplying the mound height at the appropriate
edge of the gravel bed by the horizontal slope figure and then by the slope
correction factor found in
Table IV.
Table IV.
Downslope and Upslope Width Corrections for Mounds on Sloping
Sites
Slope Percent
|
Downslope Correction
Factor
|
Upslope Correction Factor
|
0
|
1.00
|
1.00
|
2
|
1.06
|
0.94
|
4
|
1.14
|
0.89
|
6
|
1.22
|
0.86
|
8
|
1.32
|
0.80
|
10
|
1.44
|
0.77
|
12
|
1.57
|
0.73
|
(iii) The distribution bed
thickness shall be a minimum of nine (9) inches with a minimum of six (6)
inches of aggregate below the distribution network.
(iv) The bed width shall not exceed ten (10)
feet.
(v) The sand fill thickness
beneath the gravel bed shall be a minimum of one (1) foot.
(vi) The cap above the distribution bed shall
consist of one (1) foot of clayey subsoil at its center tapering to one-half
(1/2) foot at its edges.
(vii) The
entire finished mound shall be covered with one-half (1/2) foot of soil
material suitable for plant growth.
(c) Dosing and Distribution System Design
1. The dosing rate per linear foot of lateral
shall be uniform throughout the entire distribution network.
2. Hole spacing and location shall be such so
as to provide uniform distribution of effluent over the entire distribution
bed. If the last hole is equal to or greater than one-half (1/2) of the hole
spacing distance from the distal end of the lateral, a hole shall be placed in
the end cap or adjacent to it.
3.
Hole sizing, spacing, lateral length and diameter shall be derived from Table
V. The hole diameter shall range from five thirty-seconds (5/32) through one-
fourth (1/4) inch.
4. The system
must be designed and placed so that the laterals and manifold drain after each
dosing.
5. Calculation of gallons
per minute (gpm) flow and total dynamic head (TDH).
(i) The gallons per minute flow, which the
pump must provide, shall be determined by adding the combined gallons per
minute flows of each hole.
(ii) The
total dynamic head (TDH) shall be determined by adding the following:
(I) Elevation head is the difference in
elevation between the bottom of the pump and the laterals in the distribution
bed. The minimum assigned elevation head shall be five (5) feet.
(II) Friction head shall be determined from
Appendix III plus fittings loss.
Table V.
Allowable Lateral
Lengths (ft) for Three (3) Pipe Diameters, Three (3) Perforation Sizes and Two
(2) Perforation Spacings
Perforation
|
Pipe Diameter (in)
|
Spacing
|
Diameter
|
1
|
1 1/4
|
1 1/2
|
30 in
|
5/32 in
|
42 ft
|
68 ft
|
85 ft
|
30 in
|
3/16 in
|
34 ft
|
52 ft
|
70 ft
|
30 in
|
7/32 in
|
30 ft
|
45 ft
|
57 ft
|
30 in 36 in
|
1/4 in 5/32 in
|
25
ft 45 ft
|
38 ft 70 ft
|
50 ft 90 ft
|
36 in
|
3/16 in
|
36 ft
|
60 ft
|
75 ft
|
36 in
|
7/32 in
|
33 ft
|
51 ft
|
63 ft
|
36 in
|
1/4 in
|
27 ft
|
42 ft
|
54 ft
|
(III) A pressure head average of
three (3) feet shall be used for TDH calculations. The range shall be one (1)
through five (5) feet.
6. The minimum dosing volume shall be
determined by adding the volume of the supply line, manifold and five (5) times
the volume of the laterals.
7. The
dosing volume shall be between one-fourth (1/4) and one-half (1/2) daily flow,
except in those situations where the minimum dose exceeds one-half (1/2) daily
flow, then the calculated minimum dose shall be the dosing volume.
8. When pumping uphill, a check valve must be
utilized if the volume of the supply line, manifold and the volume of the
laterals that drain back into the pump tank exceeds one-fourth (1/4) of the
daily flow. If a check valve is utilized, the minimum dosing volume shall be
determined by adding the volume of the manifold and five (5) times the volume
of the laterals.
(d)
Equipment and Material Specifications
1.
Septic Tank and Dosing Tank
(i) The septic
tank shall conform to all design, construction and installation criteria set
forth in Rules 0400-48-01-.08 and 0400-48-01-.09.
(ii) The dosing chamber shall conform to all
design, construction and installation criteria set forth in Rule
0400-48-01-.12.
2. Pipe
and Fittings
(i) All pipe materials shall be
PVC and have a minimum equivalent strength of Schedule 40.
(ii) All fittings shall be pressure
fittings.
(iii) All connections
shall be adequately cleaned with cleaning solvent and glued with PVC solvent
cement.
(iv) The gate or globe
valve(s) and check valve shall be either bronze or PVC.
(v) The lateral pipe diameter shall be a
minimum of one (1) inch.
(vi) The
distal end of at least one (1) lateral shall be equipped with a capped
turn-up.
3. Pump, Float
Controls and Alarm System
(i) The pump shall
be an effluent pump of sufficient quality and size to meet or exceed the
gallons flow requirement and the total dynamic head requirement of the
system.
(ii) The pump float
controls must be adjustable and must be sealed against entry of effluent or
gases.
(iii) Alarm System
(I) A high water alarm shall be required and
consist of an audible and visible alarm located in a visible place and clearly
marked "wastewater system alarm."
(II) The alarm and alarm switches shall be
placed on a separate electrical circuit from the pump power line.
(III) The alarm float control shall be placed
so as to be activated when the pump chamber water level rises above the "pump
on" float control.
4. Disposal Field Media
The media size
shall be within the range of one-half (1/2) to one (1) inch. It must be washed
and free of fines.
5. Sand
(i) The particle sizes shall be predominantly
(fifty (50) percent or greater) medium sand (0.50 to 0.25 mm) with no more than
twenty (20) percent fine sand (0.25 to 0.10 mm) and be free from silt and
clay.
(ii) The sand shall be
composed of stable materials and not subject to chemical
deterioration.
6. Clay
Cap Above the Distribution Bed - The cap shall be clayey subsoil.
7. Final Cover - The final cover shall
consist of non-clayey, friable, fertile soil capable of supporting plant
growth.
(e) Installation
Procedures
1. Site Preparation and Imported
Fill
(i) The soil area reserved for the
initial and duplicate systems must not be cut, filled, compacted or disturbed
in any manner prior to or after system installation.
(ii) No site preparation shall occur if the
soil is wet. The designated person responsible for monitoring system
installation shall determine when the soil is adequately dry.
(iii) All trees within the area designated
for the mound shall be cut to ground level and all excess vegetation shall be
removed.
(iv) The area designated
for the mound shall be plowed to a minimum depth of eight (8) inches prior to
addition of the sand fill. This area shall be plowed on contour.
(v) After any area is plowed there shall be
no large equipment or wheeled traffic on or over said area. If a small tracked
vehicle is used for construction there shall be a minimum of six (6) inches of
sand between the track and plowed layer.
2. Supply Line and Manifold
(i) The manifold and laterals shall be
designed and installed to drain after each use.
(ii) The supply line shall be designed and
installed to drain after each use unless the system design requires a check
valve.
(iii) The supply line shall
be installed so as to prevent freezing and shall not enter from the downslope
side.
3. Pump and
Controls
(i) The pump must be placed so that
the intake is a minimum of eight (8) inches above the bottom of the pump
chamber.
(ii) As a means to remove
the pump from the pump chamber, a material of sufficient strength and
durability must be secured to the pump and access riser.
(iii) The pump control must be positioned so
the "pump off" switch is slightly above the top of the pump and the "pump on"
switch is at the desired dosing depth.
(iv) The pump outlet pipe must be connected
to the supply manifold with a threaded union or similar device.
(v) Immediately after the union, a gate or
globe valve shall be placed in the supply line. The valve may be either PVC or
bronze and shall be used to adjust the pressure on the system to the desired
head.
(vi) If the effluent is
pumped downhill, a five thirty-seconds (5/32) inch siphon breaker hole must be
drilled in the bottom of supply line above the water level in the pump
tank.
(vii) All electrical
installations shall be installed to meet the current wiring methods of the
current edition of the "National Electric Code" (NEC) adopted by the State Fire
Marshall's office.
4.
The completed system must be shaped to prevent water from ponding or flowing
over the system.
(5) A Waste Stabilization Lagoon may provide
satisfactory sewage treatment for residences where soil conditions are not
suited for absorption systems and flows are seven hundred fifty (750) gallons
per day or less. Waste stabilization lagoons require a minimum tract of five
(5) acres.
(a) Site and Soil Requirements
1. Prior to the design of the waste
stabilization lagoon, the suitability of the site must be demonstrated through
acceptable soil absorption rates, acceptable soil conditions and other
topographic characteristics.
2. The
soil characteristics shall be determined by the following:
(i) An extra-high intensity soil map shall
establish the soil rate. The absorption rate may be estimated by an approved
soil consultant but may require approval by the department.
(ii) A pit profile description to a depth of
six (6) feet below ground surface shall be generated for each lagoon cell
(primary and duplicate). Each description shall identify: soil structure, soil
color, including mottles, texture including coarse fragments, plasticity and
consistency for each distinct horizon in the soil profile.
(iii) The depth of the seasonal high water
table shall be noted if it is located within six (6) feet of the soil
surface.
3. The soil
absorption rate must be a minimum of one hundred twenty (120) minutes per inch
as estimated by an approved soil consultant.
4. An area of suitable soil must be available
to install the initial system and maintain a suitable area of adequate size for
one hundred (100) percent duplication.
5. The lagoon shall be located in soils where
the vertical separation from the bottom of the lagoon and bedrock and rock
formations, or more permeable material, are a minimum of one (1)
foot.
6. Predominant redoximorphic
features shall not be located within six (6) inches of the ground surface. The
lagoon shall not be located in areas subject to flooding as determined by the
department. The soil profile shall not be hydric in classification.
7. Slopes greater than eight (8) percent
shall be considered unsuitable.
8.
Selection of the site shall include a clear sweep of the surrounding area by
prevailing winds. Heavy timber must be removed for a distance of one hundred
(100) feet from the water's edge to enhance wind action and prevent
shading.
9. Areas consisting of
fill shall be excluded from the area considered for installation of the waste
stabilization lagoon and disposal field.
10. Lot Grading - The area to be used for the
waste stabilization lagoon and disposal field shall not be disturbed when
grading the lot. However, where this is unavoidable, a re-evaluation shall be
made by an approved soil consultant after grading has been completed. After the
suitability of any area to be used for a waste stabilization lagoon has been
evaluated and approved for construction, no change shall be made to this area
unless the Commissioner is notified and a re-evaluation of the area's
suitability is made prior to the initiation of construction.
(b) Location - A minimum acreage
tract of five (5) acres is required and larger areas may be necessary.
1. Minimum Separation Distances
(i) The lagoon shall be located a minimum of
two hundred (200) feet from property lines, as measured from the water's
edge.
(ii) The lagoon shall be
located a minimum of two hundred (200) feet from the nearest residence,
commercial or industrial establishments, any habitable building or public use
area. With the owner's permission the lagoon may be within a lesser distance of
his home.
(iii) The lagoon shall
not be located closer than fifty (50) feet away from any spring or well.
Greater horizontal separation distances may be required depending on
engineering and hydrogeological data and type of water supply.
(iv) The lagoon shall not be closer than
fifty (50) feet away from a stream, lake or impoundment.
(v) The lagoon shall not be located closer
than fifty (50) feet from gullies, ravines, dry stream beds, natural drainage
ways, sinks, caves and cut banks.
(c) Design of the Waste Stabilization Lagoon
1. The capacity of a two (2) cell lagoon
shall be equivalent to a sixty (60) day minimum retention time based upon an
average daily sewage flow of one hundred fifty (150) gallons per bedroom for
residences. The minimum water surface area of both cells shall be one thousand
two hundred fifty (1,250) square feet.
2. A properly sized and constructed two (2)
compartment septic tank shall precede the lagoon.
3. The shape of the lagoon shall be such that
there are no narrow or elongated portions. Round, square or rectangular cells
are considered most desirable. Rectangular cells shall have a length not
exceeding three (3) times the width. No islands, peninsulas or coves shall be
permitted. Embankments must be rounded at corners to minimize accumulations of
floating materials.
4. The
embankment top width shall be a minimum of two (2) feet.
5. The embankment slopes shall not be steeper
than two (2) horizontal to one (1) vertical on the inner and outer
sides.
6. Inner embankment slopes
shall not be flatter than three (3) horizontal to one (1) vertical. Outer
embankment slopes shall be sufficient to prevent the entrance of surface water
into the lagoon.
7. Freeboard (the
distance from the top of the water to the top of the embankment) shall be at
least two (2) feet after settling. Additional freeboard may be
provided.
8. Embankments shall be
seeded with a locally hardy grass from the outside toe to the water line, to
minimize erosion and facilitate weed control. Alfalfa or similar long-rooted
crops that may interfere with the water holding capacity of the embankment
shall not be used. Riprap may be necessary under unusual conditions to provide
protection of embankments from erosion.
9. On sloping areas, a diversion ditch or
soil improvement practices shall be located immediately upslope from the
embankment. The ditch or soil improvement practice shall be installed to
intercept and remove all surface and subsurface water and shall be protected
from erosion.
10. The gravity flow
lagoon influent line shall be Schedule 40 PVC or equivalent and have a minimum
diameter of three (3) inches with a minimum grade of one-fourth (1/4) inch per
foot. When gravity flow is utilized, the outlet invert of the septic tank shall
be a minimum of one (1) foot above the high water level in the lagoon. The
water level of each cell shall be at an elevation lower than the original
ground surface.
11. The influent
line shall be center discharging at a point two (2) feet beneath the water
level. A watertight cleanout shall be provided in the influent line near the
lagoon embankment and shall extend upwards to finished grade.
12. The effluent line from each cell shall be
designed to maintain the water level of that cell at a depth of four (4) feet
and be located so as to minimize short-circuiting from the influent
line.
13. The effluent from the
second cell shall be disposed of by a subsurface sewage disposal
system.
14. The subsurface sewage
disposal system shall be constructed according to paragraph (4) of Rule
0400-48-01-.07 and shall require a minimum of one hundred fifty (150) square
feet of soil absorption trench bottom area.
15. The finished grade above the subsurface
sewage disposal system shall be lower in elevation than the invert of the
effluent discharge line from the last cell.
(d) Dosing of the System (applicable only
when pumping is necessary)
1. If pumping to
the lagoon is necessary, the total dynamic head (TDH) shall be determined by
the summation of the elevation head, friction head and three (3) feet of
pressure head.
2. The gallons per
minute (gpm) flow amount, which the pump must provide shall be a minimum of ten
(10) gpm.
3. The dosing volume
shall be less than one-half (1/2) daily flow.
4. A check valve must be utilized when
pumping uphill.
(e)
Equipment and Material Specifications
1.
Septic tank and dosing tank.
(i) The septic
tank shall conform to all design, construction and installation criteria set
forth in Rules 0400-48-01-.08 and 0400-48-01-.09.
(ii) The dosing chamber shall conform to all
design, construction and installation criteria set forth in Rule
0400-48-01-.12.
2. Pipe
Materials
(i) All pipe materials shall be PVC
and have a minimum equivalent strength of Schedule 40 PVC.
(ii) If pumping is necessary, all fittings
shall be pressure fittings.
(iii)
All connections shall be adequately cleaned with cleaning solvent and glued
with PVC solvent cement.
(f) Construction
1. The area designated for the lagoon liquid
storage area and embankments shall be stripped of vegetation. The organic
material removed during excavation of the lagoon shall not be used in
embankment construction.
2. The
area designated for the lagoon liquid storage area and embankments shall be
stripped of soils that will not form an effective seal.
3. The liquid storage area of the lagoon must
be sealed to prevent excessive exfiltration.
4. Embankments shall be constructed of
impervious materials and compacted sufficiently to form a stable
structure.
5. The influent line
shall be installed at sufficient depth to protect the line from freezing and be
properly bedded to prevent structural damage to the pipe from wheeled vehicles
that cross the area. Slope of the line shall be such that excessive flow
velocities do not cause scouring at the discharge point, but shall be adequate
to prevent deposition within the line.
6. Effluent from the last cell shall be
withdrawn from six (6) inches below the water surface. This shall be
accomplished by placing a tee, with the run in a vertical position, on the
inlet end of the effluent pipe.
7.
The lagoon area shall be enclosed with a minimum four (4) feet high woven or
chain-link or other restricting fence to preclude livestock and discourage
trespassing. The fence shall be so located to permit mowing of the embankment
top and slopes. A gate of sufficient width to accommodate mowing equipment
shall be provided.
8. Appropriate
warning signs shall be provided to designate the nature of the facility and
discourage trespassing.
(g) Operation and Maintenance
1. It shall be necessary to fill the lagoon
with water prior to using it for waste disposal.
2. Vegetation growing along the water's edge
and in the water shall be mowed or otherwise removed at least
annually.
3. It shall be necessary
to maintain a consistent water depth of four (4) feet at all times of the
year.
(6) A
Subsurface Drip Disposal (SDD) System is a subsurface sewage disposal system,
which utilizes pressurized drip irrigation line for the uniform application of
treated wastewater throughout the disposal field. SDD systems shall be designed
and installed to utilize the upper profiles of a suitable soils area through
the uniform distribution of effluent, dosing and resting cycles, and shallow
installation of the disposal line. SDD systems are to be proceeded by a
treatment device capable of achieving secondary effluent treatment standards
unless otherwise determined by this department.
SDD systems designed to
accommodate wastewater flows in excess of seven hundred fifty (750) gallons per
day must be designed by a licensed engineer. The design shall be reviewed by
the department applying the requirements of paragraph (6) of this rule.
(a) Site and Soil Requirements
1. Prior to the design of the SDD system, the
suitability of the site must be demonstrated through acceptable soil
properties, soil conditions and topographical characteristics. Acceptable soil
textural and structural properties are shown in Table VII.
2. The design and installation of the SDD
system shall be based on the most restrictive naturally occurring soil horizon
or layer to a depth of twenty (20) inches or twelve (12) inches below the
installation depth of the drip line, whichever is greater.
3. An area of suitable soil must be available
to install the primary system and maintain a suitable area of adequate size for
a one hundred (100) percent duplicate area.
4. An extra-high intensity soil map, provided
by a soil consultant listed by the department, shall establish the soil
properties.
(i) An extra-high intensity soil
map for use to design a SDD system shall provide site-specific profile
descriptions establishing the texture and structure (shape and grade) for each
suitable soil unit mapped.
(ii)
Profile descriptions require the excavation of soil pits in order to allow for
site-specific pedon descriptions. The soil column shall be described to a depth
of thirty-six (36) inches or to rock or fragipan whichever is shallower. There
shall be a minimum of two (2) pits per acre with at least one pit in any
suitable soil unit intended for use, unless a different frequency is specified
by the Commissioner.
(iii) Slope
classes (Table VI) for extra-high intensity soil maps used for SDD systems
shall be delineated as follows:
Table VI.
Slope
Classes
Slope Classes
|
0 - 9
%
|
10 - 20 %
|
20 - 30 %
|
30 - 40 %
|
40 - 50 %
|
>50 %
|
(iv) Percolation tests shall not be allowed
to establish soil properties for the design of SDD systems.
5. The size of the SDD system
shall be determined by the following:
(i) The
daily wastewater flow divided by the loading rate (Table VII) shall determine
the area (ft2) required for the initial system.
Table VII.
Hydraulic Loading Rates (gpd/ft2) - For Subsurface Drip Disposal (SDD)
Systems
|
STRUCTURE
|
HYDRAULIC LOADING RATE (gpd / ft
2) BOD<=30 mg/L
|
TEXTURE
|
SHAPE
|
GRADE
|
Coarse Sand, Loamy Coarse Sand
|
NA
|
NA
|
NA*
|
Sand
|
NA
|
NA
|
NA
|
Loamy Sand, Fine Sand, Loamy
Fine Sand, Very Fine Sand, Loamy Very Fine Sand
|
Single Grain
|
Moderate, Strong
|
0.50
|
Massive, Weak
|
0.40
|
Coarse
Sandy Loam, Sandy Loam
|
Massive
|
Structureless
|
0.30
|
Platy
|
Weak
|
0.20
|
Moderate, Strong
|
Not Used
|
Blocky, Granular
|
Weak
|
0.40
|
Moderate,
Strong
|
0.50
|
Loam
|
Massive
|
Structureless
|
0.20
|
Platy
|
Weak, Moderate, Strong
|
Not Used
|
Blocky, Granular
|
Weak
|
0.30
|
Moderate, Strong
|
0.40
|
Silt Loam
|
Massive
|
Structureless
|
0.20
|
Platy
|
Weak, Moderate, Strong
|
Not Used
|
Blocky, Granular
|
Weak
|
0.20
|
Moderate, Strong
|
0.30
|
Sandy Clay Loam, Clay Loam, Silty Clay
Loam
|
Massive
|
Structureless
|
NA
|
Platy
|
Weak, Moderate, Strong
|
Not Used
|
Blocky, Granular
|
Weak
|
0.20
|
Moderate, Strong
|
0.20
|
Sandy Clay, Clay, Silty
Clay
|
Massive
|
Structureless
|
Not
Used
|
Platy
|
Weak, Moderate, Strong
|
Not Used
|
Blocky, Granular
|
Weak
|
0.075
|
Moderate, Strong
|
0.10
|
* Requires a special site
investigation
Table VII compiled from: EPA, Netafilm, GeoFlow, AL,
NC, MS, GA, TX, AR and TN
(ii) When slopes exceed nine (9) percent,
slope correction factors (Table VIII) shall be used to adjust area
requirements.
Table VIII.
Slope Correction Factors
Slope
Class
|
Depth to R Lay<=23 in
|
estrictive er >=24 in
|
10%-20%
|
15%
|
0%
|
20% - 30%
|
35%
|
15%
|
(iii) Slopes of more than fifty
(50) percent shall be considered unsuitable.
(iv) For sites with slopes between thirty
(30) to fifty (50) percent a special investigation shall be conducted to
evaluate those soils to determine: depth to rock, kind of rock and particle
size class designation to a depth of six (6) feet or to hard rock, whichever is
shallower.
(v) SDD systems designed
for sites with slopes greater than thirty (30) percent must be designed by a
licensed engineer. The department shall review the design.
(b) Design and Layout of the SDD
System
1. The required minimum linear tubing
footage is determined by dividing the amount of required square footage of
suitable soil area by two (2). However when slope correction factors are
required, the minimum linear tubing footage is calculated on the required
square footage (without the addition of the slope correction factors) divided
by two (2). The approximate tubing spacing is then determined by dividing the
required square footage (including the slope correction factor) by the minimum
linear tubing footage. Complete coverage of the required square footage
(including any slope correction factor) is required. Designers are permitted to
specify a closer tubing spacing and additional tubing, as soil and site
conditions may accommodate to insure complete coverage of the disposal
area.
2. The location of the septic
tank, effluent treatment unit, dosing chamber, and the disposal field shall be
in accordance with Rule0400-48-01-.11.
3. The drip disposal lines shall be placed on
contour. The maximum length of a single line or maximum drip zone size shall be
in compliance with the manufacturer's recommendations and is subject to
approval by the department.
4. Drip
disposal lines and drip emitters shall be spaced on twenty-four (24) inch
centers unless an alternative spacing is required by the use of slope
correction factors. Tubing spacing other than twenty-four (24) inch centers may
be considered on a case-by-case basis through the GWP Central Office.
5. All components of an SDD system shall be
designed and manufactured to resist the corrosive effects of wastewater and
household chemicals, and meet applicable ASTM standards.
6. All SDD systems shall include an automatic
filtration system capable of removing suspended solids to a level recommended
by the drip disposal line manufacturer or to a maximum particle size of no more
than 120 microns, whichever is smaller. The filtration system shall be sized to
provide the specified filtration level at or above peak flow
conditions.
7. All SDD systems
shall be designed to automatically flush each disposal field or zone at a
minimum fluid velocity of two (2) feet per second. Flushing velocity is
measured at the distal end of the drip disposal line. Flushing frequency shall
be at least the minimum frequency recommended by the drip disposal line
manufacturer or at a minimum once every thirty (30) days.
8. The filter flush, and network forward
flushing volumes are to be hydraulically acceptable to and not adversely affect
the pretreatment unit design for systems that flush to the pre-treatment tank.
Systems designed to continuously forward flush to the dosing tank shall
incorporate a system to automatically flush the filter to the pre-treatment
tank.
9. Air / vacuum release
valves shall be placed at the highest point of each zone. All valves shall be
installed under a protective cover allowing grade level access.
10. Non-pressure-compensating turbulent flow
drip emitters shall not be used in any SDD or packaged SDD system.
11. Valves or appropriate fittings to allow
for easy measurement of system pressures shall be provided on the pump output,
and on each supply and return manifold of each zone.
12. SDD systems shall be timed dosed at
regular intervals. Demand dosing shall not be used. Minimum dose calculations
shall include at least three (3) times the volume of the tubing plus the volume
of the supply and return manifolds. All SDD systems shall incorporate a flow
meter to accurately determine the volume of flow to the disposal field. The
approved system shall also provide the means to calculate pump cycles, alarm
events, pump run time, and automated flushing events.
13. Systems designed to continuously forward
flush shall incorporate a flow meter on the supply and return in order to
accurately determine the volume of flow dosed in the disposal field.
14. SDD systems shall have a dosing tank
capacity that will allow float placement to provide for a minimum working
volume of fifty (50) percent of the peak design flow. This volume should be
calculated from the timer enable to the high water alarm floats. The dosing
chamber shall also provide a reserve capacity of at least fifty (50) percent of
the peak daily flow above the high water alarm. The alarm and alarm switches
shall be placed on a separate electrical circuit from the pump power
line.
15. SDD systems shall be
designed to prevent the redistribution of effluent by gravity in the disposal
area.
(c) Construction
Specifications
1. All supply and return
manifolds, lines and pressure pipe network elements shall be constructed using
Schedule 40 PVC or equivalent.
2.
Any turn in the drip disposal line greater than ninety (90) degrees shall be
made using flexible sections of PVC or functional equivalent. The drip line
shall be secured to the flexible PVC using fittings manufactured for that
purpose.
3. All electrical
installations shall be installed to meet the current wiring methods of the
current edition of the "National Electric Code" (NEC) adopted by the Department
of Commerce and Insurance.
4. Drip
disposal line shall be installed at a depth of eight (8) to twelve (12) inches
below the natural soil surface. A buffer of twelve (12) inches of undisturbed
soil below the drip disposal line to rock or restrictive horizon shall be
maintained throughout the disposal field.
5. Drip disposal line shall be installed with
the contour of the ground and in such a manner to prevent damage to the tubing
and comply with the manufacturer's recommendations.
(d) General Requirements
1. SDD systems may only be used if the
effluent introduced to the SDD system has been treated to secondary effluent
treatment standards.
2. Permits for
SDD systems will only be considered for systems that are designed by a licensed
engineer or have been previously approved as a packaged SDD system by this
department.
3. This Department will
maintain a list of approved SDD systems either packaged with an ATS or
independently.
4. No manufacturer
marketing an SDD system independently or packaged with an ATS in Tennessee
shall deny the sale of replacement parts or deny technical guidance to any
maintenance provider listed in accordance with Rule 0400-48-01-.23.
5. The property owner at the time of initial
installation of a SDD system and any subsequent owner, for the life of the
system, shall have in effect a contract for operation and maintenance of the
SDD with an approved maintenance provider under Rule 0400-48-01-.23. These
contracts will be reviewed by this department on an annual basis. This
requirement can be included with the ATS contract specified in Rule
0400-48-01-.10.
6. SDD systems will
not be considered for the purposes of subdivision plat approval or permit
issuance unless the SDD system is to be utilized as the primary
system.
7. SDD systems will be
considered for residential applications up to and including fifteen hundred
(1500) gallons per day. However, commercial applications may be considered by
the department on an individual basis.
8. Upon installation of a packaged SDD
system, a representative of the company holding the packaged approval shall
inspect the system to certify that the system was installed to the approved
specifications and provide GWP with a detailed layout of the system components.
For systems designed by a licensed engineer, the engineer must submit
construction as-built drawings showing the location of all components of the
system.