(1) General
requirements.
(a) Except as provided in
paragraph (2) of this rule, owners and/or operators of UST systems with
field-constructed tanks and airport hydrant systems installed on or before the
effective date of this rule must comply with the requirements of:
1. Rules
0400-18-01-.02
through
0400-18-01-.04
and
0400-18-01-.06
and
0400-18-01-.08
and
0400-18-01-.16
and 0400-18-01-.17 no later than three years after the effective date of this
rule except owners and/or operators may comply prior to such date;
and
2. Rules
0400-18-01-.05
and
0400-18-01-.07
no later than the effective date of this rule.
(b) For owners and/or operators of UST
systems with field-constructed tanks and airport hydrant systems installed
after the effective date of this rule, the requirements of the rules listed in
subparagraph (a) of this rule apply at installation.
(c) No later than three years after the
effective date of this rule, all owners of UST systems with field-constructed
tanks and airport hydrant systems in use as of the effective date of this rule
must submit a one-time notice of tank system existence to the Division in
accordance with subparagraphs (1)(b) and (c) of Rule
0400-18-01-.03
in a format established by the Division and in accordance with instructions
provided by the Division. Owners and/or operators of UST systems in use as of
the effective date of this rule must demonstrate financial responsibility at
the time of submission of the notification form.
(d) Owners and/or operators of UST systems
with field-constructed tanks and airport hydrant systems may use military
construction criteria, such as Unified Facilities Criteria (UFC) 3-460-01,
Petroleum Fuel Facilities, when designing, constructing, and
installing airport hydrant systems and UST systems with field-constructed
tanks.
(2) Additions,
exceptions, and alternatives for UST systems with field-constructed tanks and
airport hydrant systems.
(a) Exception to
piping secondary containment requirements. Owners and/or operators may use
single walled piping when installing or replacing piping associated with UST
systems with field-constructed tanks greater than 50,000 gallons and piping
associated with airport hydrant systems. Piping associated with UST systems
with field-constructed tanks less than or equal to 50,000 gallons not part of
an airport hydrant system must meet the secondary containment requirement when
installed or replaced.
(b) Upgrade
requirements. No later than three years after the effective date of this rule,
airport hydrant systems and UST systems with field-constructed tanks where
installation commenced on or before the effective date of this rule must be in
compliance with the following requirements or be permanently closed in
accordance with the closure procedures in Rule
0400-18-01-.07:
1. Corrosion protection. UST system
components in contact with the ground that routinely contain petroleum
substances must meet one of the following:
(i)
Except as provided in subparagraph (a) of this paragraph, the new UST system
performance standards for tanks in subparagraph (4)(a) of Rule
0400-18-01-.02
and for piping in subparagraph (4)(b) of Rule
0400-18-01-.02;
or
(ii) Be constructed of metal and
cathodically protected according to a code of practice developed by a
nationally recognized association or independent testing laboratory and meets
the following:
(I) Cathodic protection must
meet the requirements of subparts (4)(a)2.(ii), (iii) and (iv) of Rule
0400-18-01-.02
for tanks and subparts (4)(b)2.(ii), (iii), and (iv) of Rule
0400-18-01-.02
for piping.
(II) Tanks greater than
ten years old without cathodic protection must be assessed to ensure the tank
is structurally sound and free of corrosion holes prior to adding cathodic
protection. The assessment must be by internal inspection or another method
determined by the division to adequately assess the tank for structural
soundness and corrosion holes.
2. Spill and overfill prevention equipment.
To prevent spilling and overfilling associated with product transfer to the UST
system, all UST systems with field-constructed tanks and airport hydrant
systems must comply with new UST system spill and overfill prevention equipment
requirements specified in paragraph (3) of Rule
0400-18-01-.02.
(c) Walkthrough inspections. In
addition to the walkthrough inspection requirements in paragraph (8) of Rule
0400-18-01-.02,
owners and/or operators must inspect the following additional areas for airport
hydrant systems at least once every 30 days if confined space entry according
to the Occupational Safety and Health Administration (see 29 C.F.R. part 1910)
is not required or at least annually if confined space entry is required and
keep documentation of the inspection according to paragraph (8) of Rule
0400-18-01-.02.
1. Hydrant pits - visually check for any
damage; remove any liquid or debris; and check for any leaks, and
2. Hydrant piping vaults - check for any
hydrant piping leaks.
(d)
Release detection. On or before three years after the effective date of this
rule, owners and/or operators of UST systems with field-constructed tanks and
airport hydrant systems must begin meeting the release detection requirements
described in this subparagraph.
1. Methods of
release detection for field-constructed tanks. Owners and/or operators of
field-constructed tanks with a capacity less than or equal to 50,000 gallons
must meet the release detection requirements in Rule
0400-18-01-.04.
Owners and/or operators of field-constructed tanks with a capacity greater than
50,000 gallons must meet either the requirements in Rule
0400-18-01-.04
or use one or a combination of the following alternative methods of release
detection:
(i) Conduct an annual tank
tightness test that can detect a 0.5 gallon per hour leak rate;
(ii) Use an automatic tank gauging system to
perform release detection at least every 30 days that can detect a leak rate
less than or equal to one gallon per hour. This method must be combined with a
tank tightness test that can detect a 0.2 gallon per hour leak rate performed
at least every three years;
(iii)
Use an automatic tank gauging system to perform release detection at least
every 30 days that can detect a leak rate less than or equal to two gallons per
hour. This method must be combined with a tank tightness test that can detect a
0.2 gallon per hour leak rate performed at least every two years;
(iv) Another method approved by the Division
if the owner and/or operator can demonstrate that the method can detect a
release as effectively as any of the methods allowed in part (d)1.(i) through
(iii) of this paragraph. In comparing methods, the Division shall consider the
size of release that the method can detect and the frequency and reliability of
detection.
2. Methods of
release detection for piping. Owners and/or operators of underground piping
associated with field-constructed tanks less than or equal to 50,000 gallons
must meet the release detection requirements in Rule
0400-18-01-.04.
Owners and/or operators of underground piping associated with airport hydrant
systems and field-constructed tanks greater than 50,000 gallons must follow
either the requirements in Rule
0400-18-01-.04
or use one or a combination of the following alternative methods of release
detection:
(i) Perform a semiannual or annual
line tightness test at or above the piping operating pressure in accordance
with the table below:
Maximum Leak Detection Rate Per Test Section
Volume
|
Test section volume (gallons)
|
Semiannual test - leak detection rate not to exceed
(gallons per hour)
|
Annual test - leak detection rate not to exceed
(gallons per hour)
|
<50,000
|
1.0
|
0.5
|
>=50,000 to <75,000
|
1.5
|
0.75
|
>=75,000 to <100,000
|
2.0
|
1.0
|
>=100,000
|
3.0
|
1.5
|
(ii)
Piping segment volumes & 100,000 gallons not capable of meeting the maximum
3 gallon per hour leak rate for the semiannual test or maximum 1.5 gallon per
hour leak rate for the annual test may be tested at a leak rate up to 6 gallons
per hour according to the following schedule:
PHASE IN FOR PIPING SEGMENTS >=100,000 GALLONS
IN VOLUME
|
First test
|
No later than three years after the effective date
of this rule (may use up to 6.0 gph leak rate)
|
Second test
|
Between three years after the effective date of
this rule and six years after the effective date of this rule (may use up to
6.0 gph leak rate)
|
Third test
|
Between six years after the effective date of this
rule and seven years after the effective date of this rule (must use 3.0 gph
for leak rate)
|
Subsequent tests
|
After seven years after the effective date of this
rule, begin using semiannual or annual line testing according to the Maximum
Leak Detection Rate Per Test Section Volume table in subpart (i) of this
part.
|
(iii)
Another method approved by the Division if the owner and/or operator can
demonstrate that the method can detect a release as effectively as any of the
methods allowed in subparts (i) and (ii) of this part. In comparing methods,
the Division shall consider the size of release that the method can detect and
the frequency and reliability of detection.
3. Recordkeeping for release detection.
Owners and/or operators must maintain release detection records according to
the recordkeeping requirements in paragraph (5) of Rule
0400-18-01-.04.
(e) Applicability of closure
requirements to previously closed UST systems. When directed by the Division,
the owner and/or operator of an UST system with field-constructed tanks or
airport hydrant systems permanently closed before three years after the
effective date of this rule must assess the excavation zone and close the UST
system in accordance with the closure procedures in Rule
0400-18-01-.07
if releases from the UST may, in the judgment of the Division, pose a current
or potential threat to human health and the environment.