(1) General
requirements for release detection.
(a) Owners
and/or operators of UST systems shall provide a method, or combination of
methods, of release detection that:
1. Can
detect a release from any portion of the tank and the connected underground
piping that routinely contains petroleum;
2. Is installed and calibrated in accordance
with the manufacturer's instructions and is operated and maintained in
accordance with one of the following:
(i) The
manufacturer's instructions;
(ii) A
code of practice developed by a nationally recognized association or
independent testing laboratory; or
(iii) Requirements determined by the Division
to be no less protective of human health and the environment than the two
options listed in subparts (i) and (ii) of this part.
3. Ensures that electronic and mechanical
components are tested for proper operation in accordance with subparts 2.(i)
through (iii) of this subparagraph. The test must be performed at least
annually, and at a minimum, as applicable to the facility, cover the following
components and criteria:
(i) Automatic tank
gauge and other controllers: test alarm; verify system configuration; test
battery backup;
(ii) Probes and
sensors: inspect for residual buildup; ensure floats move freely; ensure shaft
is not damaged; ensure cables are free of kinks and breaks; test alarm
operability and communication with controller;
(iii) Automatic line leak detector: test
operation to meet criteria in subparagraph (4)(a) of this rule by simulating a
leak; and
(iv) Vacuum pumps and
pressure gauges: ensure proper communication with sensors and
controller.
4. Meets the
performance requirements of paragraph (3) or (4) of this rule or subparagraph
(2)(d) of Rule 0400-18-01-.17, as applicable, with any performance claims and
their manner of determination described in writing by the equipment
manufacturer or installer. In addition, the methods listed in paragraphs (3)
and (4) of this rule and subparagraph (2)(d) of Rule 0400-18-01-.17, as
applicable shall be capable of detecting the leak rate or quantity specified
for that method in subparagraphs (3)(a), (b), and (c) or (4)(a) and (b) of this
rule with a probability of detection of 0.95 and a probability of false alarm
of 0.05.
5. Has had a third party
evaluation reviewed by the National Work Group on Leak Detection Evaluations
(NWGLDE) and a listing of the leak detection equipment or method appears on the
list maintained by the NWGLDE. However, any NWGLDE listed leak detection
equipment or method for which there is no longer any technical support
available may not be used to meet the requirements of this paragraph.
(b) When a release detection
method operated in accordance with paragraph (3) or (4) of this rule or
subparagraph (2)(d) of Rule 0400-18-01-.17, as applicable, indicates a release
may have occurred, owners and/or operators shall notify the Division in
accordance with Rule
0400-18-01-.05.
If more than one method of release detection is operated on a UST system, a
suspected release shall be reported to the Division in accordance with Rule
0400-18-01-.05
if any one of the release detection methods indicates a release may have
occurred.
(c) If a method of
release detection that complies with the requirements of this rule cannot be
applied to and/or operated for any UST system, the owner and/or operator of
that UST system shall complete the closure procedures in Rule
0400-18-01-.07.
(d) If a release detection method selected by
the owner and/or operator cannot meet the requirements in paragraphs (3) and
(4) of this rule and subparagraph (2)(d) of Rule 0400-18-01-.17, as applicable,
to the satisfaction of the Division, then the owner and/or operator shall
select another method of release detection.
(e) The dispenser cover shall be opened and a
visual inspection for petroleum releases, including seeps and drips, shall be
performed at least quarterly, that is, at least once every three months. A log
of these inspections showing at a minimum the last 12 months shall be
maintained by the owner and/or operator.
(f) Under-dispenser containment sumps for
motor fuel dispensers required by subparagraph (1)(c) or paragraph (6) of Rule
0400-18-01-.02
to be secondarily contained in accordance with subparagraph (2)(c) of Rule
0400-18-01-.02
shall be visually inspected at least quarterly, that is, at least once every
three months. A log of these inspections, showing at a minimum the last 12
months, shall be maintained by the owner and/or operator. The visual inspection
shall check for the presence of petroleum and/or water in the sumps. If liquid
is observed in the dispenser sump, the liquid shall be removed from the sump in
such a manner as to prevent the release of petroleum into the
environment.
(2)
Requirements for petroleum UST systems.
Owners and/or operators of petroleum UST systems shall
provide release detection for tanks and piping as follows:
(a) Tanks.
Tanks shall be monitored at least monthly for releases using
one of the methods listed in subparagraphs (3)(c) through (f) of this rule,
except that tanks which meet the volume, diameter, and test duration
requirements as set forth in subpart (3)(a)1.(i) of this rule may use manual
tank gauging (conducted in accordance with subparagraph (3)(a) of this
rule).
(b) Piping.
Underground piping that routinely contains petroleum shall be
monitored for releases in a manner that meets one of the following
requirements:
1. Pressurized piping.
Underground piping that conveys petroleum under pressure
shall:
(i) Be equipped with an
automatic line leak detector conducted in accordance with subparagraph (4)(a)
of this rule; and
(ii) Have an
annual line tightness test conducted in accordance with subparagraph (4)(b) of
this rule or have monthly monitoring conducted in accordance with subparagraph
(4)(c) of this rule.
2.
Suction piping.
Underground piping that conveys petroleum under suction shall
either have a line tightness test conducted at least every three years and in
accordance with subparagraph (4)(b) of this rule, or use a monthly monitoring
method conducted in accordance with subparagraph (4)(c) of this rule. No
release detection is required for suction piping that is designed and
constructed to meet the following standards:
(i) The below-grade piping operates at less
than atmospheric pressure;
(ii) The
below-grade piping is sloped so that the contents of the pipe will drain back
into the storage tank if the suction is released;
(iii) Only one check valve is included in
each suction line;
(iv) The check
valve is located directly below and as close as practical to the suction pump;
and
(v) A method is provided that
allows compliance with subparts (ii) through (iv) of this part to be readily
determined.
(3) Methods of release detection for tanks.
Each method of release detection for tanks used to meet the
requirements of paragraph (2) of this rule shall be conducted in accordance
with the following:
(a) Manual tank
gauging.
1. Manual tank gauging shall only be
applicable to tanks as set forth below:
(i)
Tanks which meet the volume, diameter and test duration requirements as set
forth below may use manual tank gauging as the sole method of release
detection:
Nominal Capacity
|
Tank Diameter
|
Minimum Duration Of Test
|
up to 550 gallons
|
*
|
36 hours
|
551 - 1000 gallons
|
64 inches
|
44 hours
|
551 - 1000 gallons
|
48 inches
|
58 hours
|
*Any diameter of tank up to 550 gallons may use manual tank
gauging as the sole method of release detection if the duration of the test is
at least 36 hours.
(ii)
Manual tank gauging shall not be used as the sole method of release detection
for tanks of 551 to 1000 gallons nominal capacity which cannot meet the
diameter or test duration requirements as set forth in subpart (i) of this part
or for tanks of 1001 to 2000 gallon nominal capacity. These tanks shall use
manual tank gauging in combination with tank tightness testing in accordance
with subparagraph (2)(a) of this rule.
(iii) Tanks of greater than 2000 gallons
nominal capacity using this method shall not meet the requirements of this
rule.
2. Manual tank
gauging shall meet the following requirements:
(i) Tank liquid level measurements are taken
at the beginning and ending of a period of using the appropriate minimum
duration of the test value in the table in subpart 1.(i) of this subparagraph
during which no liquid is added to or removed from the tank;
(ii) Level measurements are based on an
average of two (2) consecutive stick readings at both the beginning and ending
of the required period;
(iii) The
equipment used is capable of measuring the level of petroleum over the full
range of the tank's height to the nearest one-eighth of an inch;
(iv) Petroleum levels are measured and
recorded to an accuracy of at least the nearest one-eighth of an
inch;
(v) A release is suspected
and subject to the requirements of Rule
0400-18-01-.05
if the variation between beginning and ending measurements exceeds the weekly
or monthly standards in the following table:
Nominal Capacity
|
Tank Diameter
|
Minimum Duration Of Test
|
Weekly Standard (One Test)
|
Monthly
Standard (Average Of 4 Tests)
|
Up to 550 gallons
|
|
36 hours
|
10 gallons
|
5 gallons
|
551 - 1000 gallons
|
|
36 hours
|
13 gallons
|
7 gallons
|
551 - 1000 gallons
|
64 inches
|
44 hours
|
9 gallons
|
4 gallons
|
551 - 1000 gallons
|
48 inches
|
58 hours
|
12 gallons
|
6 gallons
|
1001 - 2000 gallons
|
|
36 hours
|
26 gallons
|
13 gallons
|
(b) Tank tightness testing.
1. Tank tightness testing shall be capable of
detecting a 0.1 gallon per hour leak rate from any portion of the tank that
routinely contains petroleum while accounting for the effects of thermal
expansion or contraction of the petroleum, vapor pockets, tank deformation,
evaporation or condensation, and the location of the water table.
2. Tank tightness testing devices, automatic
tank gauging devices or other equipment may be used provided that the testing
meets the performance criteria set forth in part 1. of this
subparagraph.
3. The information
relating to the tank tightness test shall be reported in a format established
by the Division. The tank tightness test report shall include, but is not
necessarily limited to the following information:
(i) Information which identifies the tank and
the facility;
(ii) Information
which identifies the test method and test conditions established by the
manufacturer's specifications and/or required by the third party certification
of the method;
(iii) Information
which identifies the person and/or company performing the test;
(iv) Data gathered during the performance of
the test; and
(v) Results expressed
as follows:
(I) Leak rate in gallons per hour
and as "Pass" or "Fail" for volumetric test methods; or
(II) "Pass" or "Fail" for non-volumetric test
methods.
4. A
release is suspected and subject to the requirements of Rule
0400-18-01-.05
if the method detects a release rate greater than that established by the
manufacturer's specifications and/or third party certification.
(c) Automatic tank gauging.
Equipment for automatic tank gauging shall be permanently
installed in the tank and shall meet one of the following requirements:
1. For automatic tank gauging devices capable
of detecting at least a 0.2 gallon per hour leak rate from any portion of the
tank that routinely contains petroleum:
(i)
The monitor shall be placed in the leak test mode at least once per month;
and
(ii) A release is suspected and
subject to the requirements of Rule
0400-18-01-.05
if the monitoring results indicate that the underground storage tank has had a
release above the established threshold of the automatic tank gauging device as
determined through third party certification.
2. For automatic tank gauging systems which
are capable of detecting at least a 0.2 gallon per hour leak rate from any
portion of the tank that routinely contains petroleum using continuous
statistical release detection:
(i) The
automatic tank gauging system shall be placed in the leak test mode at least
once per month if a test cannot be obtained during any one month period, except
for those systems which also use statistical inventory reconciliation in
accordance with subparagraph (e) of this paragraph; and
(ii) A release is suspected and subject to
the requirements of Rule
0400-18-01-.05
if the monitoring results indicate that the underground storage tank has had a
release above the established threshold of the automatic tank gauging device as
determined through third party certification, except that those systems also
using statistical inventory reconciliation shall report suspected releases in
accordance with subparagraph (e) of this paragraph.
(d) Interstitial monitoring.
Interstitial monitoring between the UST system and a
secondary barrier immediately around it may be used, but only if the system is
designed, constructed and installed to detect a leak from any portion of the
tank that routinely contains petroleum and also meets one of the following
requirements:
1. For double-walled UST
systems, the monitoring method shall:
(i) Be
able to detect a leak through the inner wall in any portion of the UST system
that routinely contains petroleum;
(ii) Provide continuous monitoring;
and
(iii) Be installed, maintained
and operated in accordance with guidance provided by the division.
2. For tanks with an internally
fitted liner, an automated device can detect a leak between the inner wall of
the tank and the liner, and the liner is compatible with the substance
stored.
(e) Statistical
inventory reconciliation.
Statistical analysis of inventory, delivery and dispensing
data collected over a period of time shall meet the following
requirements:
1. Inventory control
shall be conducted in accordance with the following requirements:
(i) Inventory volume measurements for
petroleum inputs, withdrawals, and the amount still remaining in the tank are
recorded each operating day;
(ii)
Petroleum levels are measured and recorded to an accuracy of at least the
nearest one-eighth of an inch over the full range of the tank's
height;
(iii) The petroleum inputs
are reconciled with delivery receipts by measurement of the tank inventory
volume before and after delivery;
(iv) Deliveries are made through a drop tube
that extends to within one foot of the tank bottom;
(v) Petroleum dispensing is metered and
recorded within the local standards for meter calibration or an accuracy of six
(6) cubic inches for every five gallons of petroleum withdrawn, and the meters
are calibrated at least annually; and
(vi) The measurement of any water level in
the bottom of the tank is made and recorded to the nearest one-eighth of an
inch at least once a month.
2. A report shall be generated monthly, after
the end of the data collection for that time period. The report shall include,
but is not limited to the following:
(i) The
inventory records used, that is, the raw data (data consisting of daily product
levels, deliveries and sales as determined by direct measurement or automatic
tank gauges, and daily reconciliation of measured amounts in the tank compared
with calculated amounts in the tank); and
(ii) The statistical inventory reconciliation
determination;
3. For
quantitative statistical inventory reconciliation methods, the numerical leak
rate shall be reported unless the statistical inventory reconciliation
determination results in an "Inconclusive" under the provisions of subpart
4.(iii) of this subparagraph;
4.
The statistical inventory reconciliation determination shall be reported using
the term "Pass", "Fail" or "Inconclusive". For quantitative statistical
inventory reconciliation methods the applicable term shall be used in
accordance with subparts (i) through (iii) of this part:
(i) If the calculated leak rate does not
exceed 0.10 gallons per hour, the results shall be reported as a
"Pass";
(ii) If the calculated leak
rate exceeds 0.10 gallons per hour, the results shall be reported as a
"Fail";
(iii) If the leak rate
cannot be calculated using the available data, the results shall be reported as
an "Inconclusive";
5. If
there are too few operational days for statistical inventory reconciliation to
successfully analyze during any month, then another method of release detection
shall be utilized during that month; and
6. The owner and/or operator shall report a
suspected release in accordance with Rule
0400-18-01-.05:
(i) When the statistical inventory
reconciliation determination is reported as a "Fail"; or
(ii) When two consecutive "Inconclusive"
statistical inventory reconciliation determinations are reported.
(f) Other methods of
release detection.
1. Prior to use by the tank
owner and/or operator, division approval shall be obtained in writing for any
other type of release detection method, or combination of methods.
(i) The written approval shall be kept on
file at the facility or at the place of business of the tank owner and/or
operator while the method is being utilized for release detection and for at
least 12 months thereafter. If the owner and/or operator is unable to maintain
the approval document due to closure of the facility, the approval document
shall be submitted to the division with the closure records submitted in
accordance with subparagraph (7)(c) of Rule
0400-18-01-.07.
(ii) The written approval shall be valid for
two years. The written approval must be renewed every two years
thereafter.
2. The
Division may approve another method if that method has been third party
certified to effectively and consistently detect releases. In reviewing methods
for division approval, the Division shall consider the size of release that the
method can detect and the frequency and reliability with which it can be
detected as set forth in the third party certification.
3. If the method has been approved in writing
by the Division, the owner and/or operator shall comply with any conditions
imposed by the Division on its use to ensure the protection of human health and
the environment.
(4) Methods of release detection for piping.
Each method of release detection for piping used to meet the
requirements of paragraph (2) of this rule shall be conducted in accordance
with the following:
(a) Automatic line
leak detectors.
Methods which alert the operator to the presence of a leak by
restricting or shutting off the flow of petroleum through piping or triggering
an audible or visual alarm may be used only if they detect leaks of three
gallons per hour at ten pounds per square inch line pressure within one hour.
An annual test of the operation of the leak detector shall be conducted in
accordance with guidance provided by the Division.
(b) Line tightness testing.
A periodic test of piping may be conducted only if it can
detect a 0.1 gallon per hour leak rate at one and one-half times the operating
pressure.
(c) Interstitial
monitoring.
Interstitial monitoring between the primary piping and the
secondary barrier immediately around it may be used, but only if the system is
designed, constructed and installed to detect a leak from any portion of the
piping that routinely contains petroleum and also meets one of the following
requirements:
1. For double-walled UST
systems, the monitoring method shall:
(i) Be
able to detect a leak through the inner wall in any portion of the UST system
that routinely contains petroleum;
(ii) Operate continuously as designed, and
provide 30 day periodic testing;
(iii) Be installed, maintained and operated
in accordance with guidance provided by the Division; and
(iv) If owners and/or operators of UST
systems have containment sumps used for interstitial monitoring of piping, the
containment sumps must meet the following requirements to ensure the equipment
is operating properly and will prevent releases to the environment:
(I) Containment sumps used for interstitial
monitoring of piping must prevent releases to the environment by meeting one of
the following:
I. The equipment is double
walled and is periodically monitored at a frequency not less than the frequency
of the walkthrough inspections described in paragraph (8) of Rule
0400-18-01-.02.
Owners and/or operators must begin meeting subitem II of this item and conduct
a test within 30 days of discontinuing periodic monitoring of this equipment;
or
II. The containment sumps used
for interstitial monitoring of piping which are single walled or double walled
with a dry interstice and periodically monitored are tested at least once every
three years to ensure the equipment is liquid tight by using vacuum, pressure,
or liquid testing in accordance with one of the following criteria:
A. Requirements developed by the manufacturer
(Note: Owners and/or operators may use this option only if the manufacturer has
developed requirements);
B. Code of
practice developed by a nationally recognized association or independent
testing laboratory;
C. Guidance
provided by the Division; or
D.
Requirements determined by the Division to be no less protective of human
health and the environment than the options listed in sections A. and B. of
this subitem.
III.
Containment sumps which are double walled and constructed so that the inner and
outer walls are continuously monitored by interstitial sensors using brine
solution or vacuum do not require testing,
(v) When electronic sensors are used to
comply with this subparagraph in secondarily contained piping systems, sensors
must be installed in every sump and must be placed at the lowest point in the
sump and tested for proper operation at least once per year.
2. Reserved.
(d) Statistical inventory reconciliation.
Statistical analysis of inventory, delivery and dispensing
data collected over a period of time shall meet the following
requirements:
1. Inventory control
shall be conducted in accordance with the following requirements:
(i) Inventory volume measurements for
petroleum inputs, withdrawals, and the amount still remaining in the tank are
recorded each operating day;
(ii)
Petroleum levels are measured and recorded to an accuracy of at least the
nearest one-eighth of an inch over the full range of the tank's
height;
(iii) The petroleum inputs
are reconciled with delivery receipts by measurement of the tank inventory
volume before and after delivery;
(iv) Deliveries are made through a drop tube
that extends to within one foot of the tank bottom;
(v) Petroleum dispensing is metered and
recorded within the local standards for meter calibration or an accuracy of six
cubic inches for every five gallons of petroleum withdrawn, and the meters are
calibrated at least annually; and
(vi) The measurement of any water level in
the bottom of the tank is made and recorded to the nearest one-eighth of an
inch at least once a month.
2. A report shall be generated monthly, after
the end of the data collection for that time period. The report shall include,
but is not limited to the following:
(i) The
inventory records used, that is, the raw data (data consisting of daily product
levels, deliveries and sales as determined by direct measurement or automatic
tank gauges, and daily reconciliation of measured amounts in the tank compared
with calculated amounts in the tank); and
(ii) The statistical inventory reconciliation
determination;
3. For
quantitative statistical inventory reconciliation methods, the numerical leak
rate shall be reported unless the statistical inventory reconciliation
determination results in an "Inconclusive" under the provisions of subpart
4.(iii) of this subparagraph;
4.
The statistical inventory reconciliation determination shall be reported using
the term "Pass", "Fail" or "Inconclusive". For quantitative statistical
inventory reconciliation methods the applicable term shall be used in
accordance with subparts (i) through (iii) of this part:
(i) If the calculated leak rate does not
exceed 0.10 gallons per hour, the results shall be reported as a
"Pass";
(ii) If the calculated leak
rate exceeds 0.10 gallons per hour, the results shall be reported as a
"Fail";
(iii) If the leak rate
cannot be calculated using the available data, the results shall be reported as
an "Inconclusive";
5. If
there are too few operational days for statistical inventory reconciliation to
successfully analyze during any month, then another method of release detection
shall be utilized during that month; and
6. The owner and/or operator shall report a
suspected release in accordance with Rule
0400-18-01-.05:
(i) When the statistical inventory
reconciliation determination is reported as a "Fail"; or
(ii) When two consecutive "Inconclusive"
statistical inventory reconciliation determinations are reported.
(5) Release
detection record keeping.
All UST system owners and/or operators shall maintain records
in accordance with paragraph (2) of Rule
0400-18-01-.03
demonstrating compliance with all applicable requirements of this rule. Release
detection information shall be recorded in a format established by the Division
and in accordance with instructions provided by the division. These records
shall include the following:
(a) All
written performance claims pertaining to any release detection system used, and
the manner in which these claims have been justified or tested by the equipment
manufacturer or installer, shall be maintained for five years from the date of
installation or until such time as the release detection method to which the
performance claim pertains is no longer used at the facility, whichever is
later; for a release detection method that has been approved by the division
under the provisions of subparagraph (3)(f) of this rule, the division's
written approval shall be maintained by the tank owner and/or operator while
the method is being utilized for release detection and for at least 12 months
thereafter;
(b) The results of any
sampling, testing, or monitoring shall be maintained for at least one (1) year
except as follows:
1. The results of tank
and/or line tightness testing conducted in accordance with subparagraphs (3)(b)
or (4)(b) of this rule and subparagraph (2)(d) of Rule 0400-18-01-.17 shall be
retained until the next test is conducted;
2. The results of testing conducted in
accordance with part (1)(a)3. of this rule shall be maintained for three years.
At a minimum, the results must list each component tested, indicate whether
each component tested meets criteria in part (1)(a)3. of this rule or needs to
have action taken, and describe any action taken to correct an issue;
and
(c) Written
documentation of all calibration, maintenance, and repair of release detection
equipment permanently located on-site shall be maintained for at least one year
after the servicing work is completed. Any schedules of required calibration
and maintenance provided by the release detection equipment manufacturer shall
be retained for five years from the date of installation or until such time as
the release detection method to which the schedule of required calibration and
maintenance pertains is no longer used at the facility, whichever is
later.