Current through September 24, 2024
(1) Bulk storage
containers and accessories shall qualify under basic rules.
(2) Refrigerated aboveground storage:
(a) Aboveground storage containers with a
designed pressure of less than 200 psi for ASME shall be refrigerated to
maintain the pressure below the pop off pressure. Refrigeration shall be
accomplished as follows:
1. A minimum of one
electric engine automatically controlled compressor and cooling
coils.
2. A minimum of one
gasoline, oil, or other fuel propelled engine operated compressor and coils
maintained in standby condition; provided, however, where electric current is
not available there shall be a minimum of two such engines available for
use.
3. Other refrigeration units
approved by the National Board of Fire Underwriters of the
Commission.
(3) Protected aboveground storage:
(a) Aboveground containers of less than 250
psi for ASME and not less than 200 psi for ASME, shall be provided with a shed
that extends outward from and above the height of the container, at least 3',
and roof shall be constructed of non-flammable, heat reflecting material. In
lieu of the shed, a suitable sprinkling system may be installed.
1. The sprinkler system may consist of 1/2"
to 3/4" pipe running along the top of the container with 1/16" drill size,
perforations, space 1/2" to 1" apart on either side to allow a fine stream of
water to flow down the sides of the container.
(4) No container shall have a water capacity
larger than 30,000 gallons unless means are provided to refrigerate the
container.
(5) No storage container
shall have a shell or head thickness less than 3/16".
(6) Underground containers:
(a) All underground containers shall be
buried a minimum of 24" below the surface of the ground. All such containers
shall be coated with one coat of red lead and two heavy coats of coal tar or
asphalt. Any underground container that is not buried to a depth of 24" below
the ground, or any container that is "mounded" over or showing above the earth
shall fall under the classification of aboveground installation and must have
the necessary protective devices required for such installation.
(b) Containers once installed underground
shall not later be reinstalled aboveground or underground, unless they
successfully withstand hydrostatic pressure retests at the pressure specified
for the original hydrostatic test as required by the code under which
constructed, and show no evidence of serious corrosion. Where containers are
reinstalled underground, the corrosion resistant coating shall be put in good
condition.
(7)
Aboveground installations:
(a) Aboveground
containers shall be mounted on substantial masonry supports, or structural
steel supports on substantial masonry footings. These containers must be
supported through a minimum arch of 120' if masonry supports are used. 1/4"
insulation shall be placed between the masonry and the tank to prevent
corrosion and protect the life of the support. All such containers shall be
painted with a heat reflecting paint such as white or aluminum.
(8) Storage relief valve's vent
requirement:
(a) All storage containers shall
have their relief valves vented vertically and directly upwards to a point at
least 15' above the ground. Vent pipe shall not be restricted or smaller in
size than the relief valve it vents. All vent pipe shall have a suitable
raincap that will allow free discharge of the vapor and prevent the entrance of
water, and at the bottom of each vent pipe a small hole shall be cut to allow
any moisture that may collect in the vent to escape. If housed in a building or
sun-shade, openings shall be provided so that full advantage of a natural
ventilation may be obtained. All vent pipes shall be properly guyed.
(9) Underground installations:
(a) All underground storage containers having
a water capacity in excess of 1,200 gallons, shall have perforated drain tile
6" in diameter under each side of the tank, running parallel to the tank
leading into a main drain tile which empties into a catch basin. The catch
basin shall have a power driven pump operating automatically to keep water away
from the tanks. A hand operated water pump shall be maintained in standby
condition. All drain tile shall be at least the depth of the bottom of the
container, with the containers resting on firm earth, the tile on two inches of
slag, rock, or gravel and covered to a depth of at least 12" with the same
material. Where there are more than one tank in the same underground
installation, the tile may be arranged to drain the entire installation and not
necessarily each tank individually.
1. In lieu
of the drain tile requirements specified herein such underground tanks may be
installed on a concrete foundation and anchored at or near both ends of the
tank with a metal strap of sufficient tensil strength to keep the tank firmly
attached to the foundation. The amount of concrete used in the foundation shall
be such that its weight shall at all times be sufficient to prevent the tank
from rising out of the ground even though the tank should be completely
submerged in water.
2. All dealers
having underground systems installed prior to the effective dates of these
rules and regulations shall furnish the Office of the Commissioner of
Agriculture affidavits testifying that said installations comply with rules and
regulations or are equivalent thereof.
(10) Storage Areas:
(a) All areas occupied by a bulk storage
installation belonging to a dealer shall be enclosed by a substantial wire
fence. Fencing shall not be installed closer than 5' to any tank. All valves
shall be equipped with locking devices. Said storage areas shall have warning
signs cautioning against smoking, carelessness, and the presence of
unauthorized personnel.
(11) Distances between aboveground containers
of over 1,200 gallons' capacity shall be at least 5'.
(12) Electrical ground:
(a) Aboveground containers shall be grounded
by an adequate and separate ground. This shall consist of a separate ground rod
buried to a depth of 6' and connected to the tank by an approved type heavy
cable, attached to the tank by soldering or other approved means for a good
electrical bond.
(13)
Plan for approaching storage facilities:
(a)
In case of multiple storage facilities, a plan must be provided to easily
approach all shut-off valves used for isolating various parts of the storage
facilities. This is imperative, otherwise a serious leak under certain weather
conditions may blanket out completely the storage area and make approach
impossible.
(14)
Accessories:
(a) Wherever condensers, pumps,
and compressors are used, they shall be manufactured by a reputable concern and
recommended by the manufacturer for use with ammonia.
(15) All bulk storage plants shall have on
hand as a minimum, the following equipment:
(a) Approved type gas mask with refill
charges.
(b) One pair of rubber
gloves.
(c) One pair of rubber
boots.
(d) One rubber slicker
and/or rubber pants and jacket.
Easily accessible shower bath and/or 50 gallon open top drum
filled with water.
(e) One
pair tight fitting ventless type goggles.
(f) First aid kit.
(g) Fire extinguisher.
Authority: T.C.A. §43-1302.