South Dakota Administrative Rules
Title 61 - Department of Public Safety
Article 61:15 - Fire safety
Chapter 61:15:07 - Fire safety requirements for school buildings
Section 61:15:07:32 - Special provisions for kindergarten, first, and second grades

Universal Citation: SD Admin Rules 61:15:07:32
Current through Register Vol. 51, page 43, September 23, 2024

Rooms used for kindergarten, first, or second grade pupils may not be located above or below the first story, except in basements or stories that have floor levels located within four feet, measured vertically, from the adjacent ground level at the point of exit, provided the basement or story has exits directly to the exterior at that level. In buildings equipped with an automatic sprinkler system throughout, rooms used for kindergarten, first, and second grade pupils may be located on the second story if there are at least two exits directly to the exterior for the exclusive use of the occupants. The authority having jurisdiction may modify the requirements of this section if exigent circumstances are encountered in a specific case.

General Authority: SDCL 13-25-2.

Law Implemented: SDCL 13-25-3, 13-25-4.

Disclaimer: These regulations may not be the most recent version. South Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.