South Dakota Administrative Rules
Title 61 - Department of Public Safety
Article 61:15 - Fire safety
Chapter 61:15:07 - Fire safety requirements for school buildings
Section 61:15:07:20 - Laboratories and science rooms
Current through Register Vol. 51, page 43, September 23, 2024
Each laboratory and science work area in which hazardous chemicals are used or stored must conform to the following:
(1) Each laboratory or science room utilizing hazardous chemicals must be separated from each other and from the rest of the building by a minimum of a one-hour fire-resistive separation. Existing construction may be considered as complying, if in the opinion of the fire official, a distinct hazard to life is not found to exist. No separation is required in fully sprinklered buildings;
(2) Each laboratory must contain at least one portable fire extinguisher with a minimum rating of 2A-10BC per 1500 square feet of lab area;
(3) Flammable and combustible liquids and hazardous chemicals must be stored in approved metal storage cabinets or in a storage room constructed of one-hour fire-resistive construction;
(4) Each laboratory and chemical storage room must be provided with mechanical exhaust;
(5) A manual shutoff valve must be provided for LP-gas and other bulk compressed gas systems. A valve must be provided at the point of supply and at each point of use. A valve that is located near the instructors workstation or an emergency valve is acceptable for the required valve located at the point of use; and
(6) The maximum water capacity of individual LP-gas cylinders used for experimentation in educational occupancies shall be 50 lbs. Cylinders not in use may not be stored within the building.
General Authority: SDCL 13-25-2.
Law Implemented: SDCL 13-25-3, 13-25-4.