South Dakota Administrative Rules
Title 61 - Department of Public Safety
Article 61:15 - Fire safety
Chapter 61:15:07 - Fire safety requirements for school buildings
Section 61:15:07:13 - Enclosure of vertical shafts
Universal Citation: SD Admin Rules 61:15:07:13
Current through Register Vol. 51, page 43, September 23, 2024
Interior vertical shafts, including stairways, elevator hoistways, service shafts, and utility shafts, must be enclosed by a minimum of one-hour fire-resistive construction. All openings into such shafts must be protected with one-hour fire assemblies which are self-closing or automatic-closing by smoke detection. All other openings must be protected from fire in a manner approved by the authority having jurisdiction. An enclosure is not required for openings serving only one adjacent floor. Vertical openings need not be protected if the building is protected by an automatic sprinkler system throughout.
General Authority: SDCL 13-25-2.
Law Implemented: SDCL 13-25-3, 13-25-4.
Disclaimer: These regulations may not be the most recent version. South Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.