Section 61:15:07:04 - Automatic sprinkler system requirements
Universal Citation: SD Admin Rules 61:15:07:04
Current through Register Vol. 51, page 43, September 23, 2024
An automatic sprinkler system must be installed in basements of school occupancies when the total area of unseparated uses exceeds 1,500 square feet in floor area. All valves controlling the water supply for automatic sprinkler systems must be electrically supervised when the number of sprinkler heads exceeds 100. All automatic sprinkler systems must have a water-flow switch which activates the building's fire alarm. For uses to be considered as separated, the separation may not be less than as required for a one-hour occupancy separation.
General Authority: SDCL 13-25-2.
Law Implemented: SDCL 13-25-3, 13-25-4.
Disclaimer: These regulations may not be the most recent version. South Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.