South Dakota Administrative Rules
Title 61 - Department of Public Safety
Article 61:08 - Boilers
Chapter 61:08:09 - Historic power boilers
Section 61:08:09:29 - Ultrasonic examination for thickness determination

Universal Citation: SD Admin Rules 61:08:09:29
Current through Register Vol. 51, page 70, December 27, 2024

Ultrasonic examination for thickness determination may be made using the pulse-echo technique. Ultrasonic examination provides indications of surface and subsurface discontinuities. If an ultrasonic thickness reading is below a desired value, the area around that reading must be examined as follows:

Using the low reading point as the center, superimpose an 8-inch point as the center, superimpose an 8-inch square on the area, and take 20 readings spaced on 2-inch centers on the perimeter and within the square. The average of these 20 readings is used as the minimum boiler thickness in the 8-inch square area.

General Authority: SDCL 34-29A-14.1.

Law Implemented: SDCL 34-29A-14.1.

Disclaimer: These regulations may not be the most recent version. South Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.