South Dakota Administrative Rules
Title 61 - Department of Public Safety
Article 61:08 - Boilers
Chapter 61:08:09 - Historic power boilers
Section 61:08:09:19 - Hydrostatic pretest - Steam outlet requirements

Universal Citation: SD Admin Rules 61:08:09:19
Current through Register Vol. 51, page 70, December 27, 2024

Each threaded steam outlet from a power boiler, except to the water column, the fusible soft plug and the safety valve connections, must be fitted with a stop valve located as close as practicable to the boiler. Schedule 80 pipe must be used between the boiler and the first stop valve. If a globe valve is used, the inlet pressure must be under the disk of the valve.

General Authority: SDCL 34-29A-14.1.

Law Implemented: SDCL 34-29A-14.1.

Hydrostatic pretest -- Pipe requirements, § 61:08:09:15.

Disclaimer: These regulations may not be the most recent version. South Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.