South Dakota Administrative Rules
Title 61 - Department of Public Safety
Article 61:08 - Boilers
Chapter 61:08:09 - Historic power boilers
Section 61:08:09:16 - Hydrostatic pretest - Steam gauge connections
Universal Citation: SD Admin Rules 61:08:09:16
Current through Register Vol. 51, page 70, December 27, 2024
Each boiler must have a steam gauge connected to the steam space by a siphon or an equivalent device of sufficient capacity to keep the gauge tube filled with water. This connection must be arranged so that the gauge cannot be shut off from the boiler except by a cock placed near the gauge. This cock must be provided with a tee or lever-type handle. When the cock is open, the tee or lever must be parallel to the pipe in which the cock is located.
General Authority: SDCL 34-29A-14.1.
Law Implemented: SDCL 34-29A-14.1.
Disclaimer: These regulations may not be the most recent version. South Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.