South Dakota Administrative Rules
Title 61 - Department of Public Safety
Article 61:08 - Boilers
Chapter 61:08:05 - Safety requirements
Section 61:08:05:07 - Low-water fuel cutoffs required

Universal Citation: SD Admin Rules 61:08:05:07
Current through Register Vol. 51, page 70, December 27, 2024

Each automatically fired steam or vapor system boiler shall be equipped with one or more automatic low-water fuel cutoffs wired in series with the limit controls. It shall be located to cut off the fuel supply automatically when the surface of the water falls to the lowest safe water line. Steam boilers equipped with the electrode type of low-water fuel cutoff are required to have an additional float-operated low-water fuel cutoff.

General Authority: SDCL 34-29A-16.

Law Implemented: SDCL 34-29A-17, 34-29A-24.

Disclaimer: These regulations may not be the most recent version. South Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.