Article 44:76 - Ambulatory surgery center facilities
Chapter 44:76:11 - Construction standards
Section 44:76:11:22 - Food service ventilation

Universal Citation: SD Admin Rules 44:76:11:22
Current through Register Vol. 50, page 114, March 25, 2024

The air from dining areas may be used to ventilate the food preparation areas only after it has been passed through a filter with 80 percent efficiency. Exhaust hoods in food preparation centers shall have a minimum exhaust rate of 50 cubic feet a minute for each square foot (0.25 cubic meters a second for each square meter) of hood face area. All hoods over cooking ranges shall be equipped with fire extinguishing systems interconnected to shut off the fuel source. Cleanout openings shall be provided every 20 feet (6.10 meters) in horizontal exhaust duct systems serving hoods.

General Authority: SDCL 34-12-13(1), (3), and (4).

Law Implemented: SDCL 34-12-13(1), (3), and (4).

Disclaimer: These regulations may not be the most recent version. South Dakota may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.